AirStage ASHA18GACH Installation Manual Download Page 14

En-13

Heat air 

tempera-

ture trigger

31

00

Default

Adjust the heat air trigger 
temperature. To lower the trigger tem-
perature by 6 degrees C, use setting 
01. To lower the trigger temperature 
by 4 degrees C, use setting 02. To 
raise the trigger temperature, use set-
ting 03.

01 Adjust (1)

02 Adjust (2)

03 Adjust (3)

Auto restart

40

00

Enable

Enable or disable automatic system 

restart after a power outage.

*  Auto restart is an emergency func-

tion such as for power failure etc.

Do not start and stop the indoor unit 

by this function in normal operation.

Be sure to operate by the control 

unit, converter or external input 

device.

01

Disable

Cool Air 

Prevention

43

00 Super low

Restrain the cold air

fl

 ow with making 

the air

fl

 ow lower when starting heat-

ing operation. To correspond to the 

ventilation, set to 01.

01

Follow the 

setting 

on the 

remote 

controller

External 

control

46

00 Start/Stop

Allow an external controller to start 

or stop the system, or to perform an 

emergency stop.

*  If an emergency stop is performed 

from an external controller, all refrig-

erant systems will be disabled. 

*  If forced stop is set, indoor unit stops 

by the input to the external input ter-

minals, and Start/Stop by a remote 

controller is restricted.

01

Emergen-

cy stop

02

Forced 

Stop

Error report 

target

47

00

All

Change the target for reporting er-
rors. Errors can either be reported in 
all locations, or only on the central 
remote controller.

01

Display 
only on 

central 

remote 

controller

Fan set-

ting when 

cooling 

thermostat 

OFF

49

00

Follow the 

setting 

on the 

remote 

controller

When set to 01, the fan stops when 
the thermostat is OFF in cooling 
operation. Connection of the wired re-
mote controller (2-wire type or 3-wire 
type) and switching its thermistor are 
necessary.

01

Stop

7.4.1. Button name and function

OPERATION indicator lamp (Green)

FILTER indicator lamp (Red)

TIMER indicator lamp (Orange)

7.4.2. Checking the function settings

Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check 
the function settings. It is necessary to disconnect the power in order to return to normal 
operation mode.

(1) Indoor unit and refrigerant address indication

Indication pattern

Indicator name

Indication pattern

Indoor unit address

Refrigerant address

OPERATION indicator lamp (Green)

ON

Flash (1.0s ON/1.0s OFF)

TIMER indicator lamp (Orange)

Address: tens place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Address: ones place (0.5s ON/0.5s OFF)

•  Indoor unit address example

(Example) ADDRESS : 24

OPERATION 

indicator lamp 

(Green)

TIMER 

indicator lamp 

(Orange)

FILTER indica-

tor lamp

(Red)

10 sec

1 cycle 12 sec

8 sec

ON

OFF

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

ON

•  Refrigerant address example

(Example) ADDRESS : 30

OPERATION 

indicator lamp 

(Green)
TIMER 

indicator lamp 

(Orange)

FILTER indica-

tor lamp

(Red)

9 sec

1 cycle 12 sec

ON

OFF

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

1.0s

0.5s 0.5s 0.5s 0.5s 0.5s 0.5s

ON

OFF

ON

OFF

OFF

• Setting details

Function number

Item

Setting number

01

Indoor unit address

00 to 63

02

Refrigeration address

00 to 99

For use with a remote controller, set all rotary switches to 0, and refer to “7.1. Setting the 
address” for details.
All switches are set to 0 at the factory.

(2) Others

Indication pattern

Indicator Name

Indication pattern

OPERATION indicator lamp (Green)

Function number; tens place (0.5s ON/0.5s OFF)

TIMER indicator lamp (Orange)

Function number; ones place (0.5s ON/0.5s OFF)

FILTER indicator lamp (Red)

Setting number: (0 to 9) (0.5s ON/0.5s OFF)

(Example) Function : 31, Setting number : 2

OPERATION 

indicator lamp 

(Green)
TIMER 

indicator lamp 

(Orange)
FILTER indica-

tor lamp

(Red)

11 sec

10 sec

9 sec

1 cycle 12 sec

ON

OFF

0.5s 0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s

0.5s 0.5s 0.5s

ON

OFF

ON

OFF

9373370147-02_IM.indb   13

9373370147-02_IM.indb   13

1/21/2013   4:10:23 PM

1/21/2013   4:10:23 PM

Summary of Contents for ASHA18GACH

Page 1: ...APPAREIL INT RIEUR Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTE...

Page 2: ...rvice person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 1 2 1 Precautions for using R410A refrigerant WARNING Do no...

Page 3: ...ates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Are...

Page 4: ...y strong so that the wall can support the weight Fig A UNIT mm UNIT centre UNIT size UNIT size hole hole hole for tapping screw 80 hole 80 hole Piping inlet Piping inlet hole hole hole hole hole hole...

Page 5: ...flare R410A pipes the dimension A should be approximately 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure...

Page 6: ...breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break For 1 Rear piping 2 Right piping and 3 Bottom piping Install the indoor unit piping in the direct...

Page 7: ...ly making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as overheating the terminals...

Page 8: ...1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cabl...

Page 9: ...ld be separate from the power cable line 6 3 3 Remote controller cable Remote controller cable modification 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remo...

Page 10: ...d at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 t...

Page 11: ...operation 3 Connection methods Wire modification Remove insulation from wire attached to wire kit connector Remove insulation from field supplied cable Use crimp type insulated butt connector to join...

Page 12: ...frigerant system set the address at IU AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of mul...

Page 13: ...oling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18 to 32 C NOTE Please do not make a standard setup and an extension setup intermingled in remote controller group...

Page 14: ...lamp Green FILTER indicator lamp Red TIMER indicator lamp Orange 7 4 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function sett...

Page 15: ...6 Center piping and 7 Left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with vinyl tape so that there is no gap 1 Rear 2 Right and...

Page 16: ...ge Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat...

Page 17: ...n manual of the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UT...

Reviews: