En-8

 WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 
cables with the ring terminal, the ring terminal’s pressure bonding may malfunction 
and cause the cables to abnormally heat up.

B. For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table for the terminal screw tightening torques.
(7)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Strip 10 mm

Ring terminal

Screw with 
special washer

Ring terminal

Terminal block

Cable

Screw with 
special washer

 Sleeve

Ring terminal

Cable

 WARNING

Use ring terminals and tighten the terminal screws to the speci

fi

 ed torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the 
unit.

Tightening torque

M4 screw 
(Power supply/L, N, GND)

1.2 to 1.8 N·m 

(12 to 18 kgf·cm)

6.3.2. Transmission and Remote controller cable

25 mm

35 mm

Shielded cable (no 

fi

 lm)

Transmission cable

Remote controller cable

25 mm

25 mm

For 3-wire type

For 2-wire type

•  Connect remote controller and transmission cables as shown in Fig. B.

•  When the 2 cables are attached.

Fig. B

GOOD

PROHIBITED

Different diameter

Connect to 1 side

 WARNING

Tighten the terminal screws to the speci

fi

 ed torques, otherwise, abnormal overheating 

may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M3 screw (Transmission/X1, X2)
(Remote controller/Y1, Y2, Y3)

0.5 to 0.6 N·m

(5 to 6 kgf·cm)

 CAUTION

To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening 
the screw. On the other hand, an undertightened screw can cause faulty contact, which 
will lead to a communication failure.

6.4. Connection of wiring 

(1)  Remove the control box cover and install each connection cable.

Loosen the screws. 
(2 locations)

Cover box

(2)  After wiring is complete, clamp the remote controller cable, transmission cable and 

power supply cable with cable tie.

 CAUTION

When switching the DIP switch (SW1), be sure to turn off the power supply to the 
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.

Cable clamp

Earth 
(ground)

X1, X2:
Transmission cable

L, N: 
Power supply cable

*1:  If you connect the remote controller cable to the terminal 

Y3, 2-wire type remote controller does not work. 

Y1, Y2, Y3: 
Remote controller 
cable

Cable tie (Medium)

(Accessories) 

DIP switch

(SW1)

For 2-wire type

For 3-wire type

Connect the remote 
controller cable

Y1:Non-polar
Y2:Non-polar
Y3:Do not connect *1

Y1:Red
Y2:White
Y3:Black

Set the DIP switch 
(SW1)

2WIRE
(Factory setting)

3WIRE

 CAUTION

When installing a screw on the terminal block, do not cut the cable by overtightening 
the screw. On the other hand, an undertightened screw can cause faulty contact, 
which will lead to a communication failure.

(3)  Attach the control box cover.

9373870203_IM.indb   8

9373870203_IM.indb   8

2016/1/8   8:41:21

2016/1/8   8:41:21

Summary of Contents for ARXC36GBTH

Page 1: ...6GBTH TM MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado MANUALE...

Page 2: ...service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING D...

Page 3: ...unting position together with the customer as follows WARNING Select installation locations that can properly support the weight of the indoor unit Install the units securely so that they do not toppl...

Page 4: ...G Install the air conditioner in a location which can withstand a load of at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not...

Page 5: ...pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break CAUTION To prevent people from touching the parts insid...

Page 6: ...tion and the product 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe VP25 and connect it with adhesive polyvinyl chloride so that there is no leakage The position of the installed dr...

Page 7: ...g the terminals electric shock or fire Do not modify the power cables use extension cables or use any branches in the wiring Improper connections insufficient insulation or exceeding the allowable cur...

Page 8: ...B units If the total number of units connected to the breaker exceeds 44 either add a 30mA breaker or use breakers with a greater capacity 6 1 1 Cable specifications Follow the specifications below fo...

Page 9: ...bles are attached Fig B GOOD PROHIBITED Different diameter Connect to 1 side WARNING Tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly ca...

Page 10: ...Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correc...

Page 11: ...onnector Input signal Command Ch3 of CNA03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input...

Page 12: ...lation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB C...

Page 13: ...1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting mu...

Page 14: ...Disable Cool Air Preven tion 43 00 Super low Restrain the cold airflow with mak ing the airflow lower when starting heating operation To correspond to the ventilation set to 01 01 Follow the setting o...

Page 15: ...unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan mo...