background image

En-10

Tightening torque

M3 screw

(Transmission /X1, X2)

(Remote controller /Y1, Y2, Y3)

0.5 to 0.6 N·m

(5 to 6 kgf·cm)

 

CAUTION

  To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

  When installing a screw on the terminal block, do not cut the cable by overtightening 

the screw. On the other hand, an undertightened screw can cause faulty contact, which 
will lead to a communication failure.

6.4. Connection of wiring

(1) Remove the control box cover and install each connection cable.

Screw

Control box cover

(2) After wiring is complete, secure the remote controller cable, connection cable, and 

power cable with the cable clamps.

Power supply cable 
(Field supply)

Cable tie (Medium) 
(Accessories)

Remote control-
ler cable, Trans-
mission cable
(Field supply)

Cable tie (Medium) (Accessories)

Cable clamp

L, N:Power supply cable

X1, X2:
Transmission cable

Remote controller cable
Y1:Red
Y2:White
Y3:Black

 

CAUTION

  When switching the DIP switch (SW1), be sure to turn off the power supply to the 

indoor unit. Otherwise, the PC board of the indoor unit may be damaged.

Remote controller cable

DIP switch

(SW1)

For 2-wire type

For 3-wire type

Connect the remote 
controller cable

Y1:Non-poler
Y2:Non-poler
Y3:Do not connect *1

Y1:Red
Y2:White
Y3:Black

Set the DIP switch 
(SW1)

2WIRE

(Factory setting)

3WIRE

*1:  If you connect the remote controller cable to the terminal 

Y3, 2-wire type remote controller does not work.

6.5. Air 

fl

 ow changing

When using the ARXB24/30/36/45L model with external Static Pressure under 40 Pa, 
the Wire (FAN MOTOR) must be replaced as explained below.

Replacement method 
(1) Remove the cover.
(2) Remove the Wire (TYPE A) connector from Wire (FAN MOTOR).
(3) Remove the Wire (TYPE A) connector from CN110 of the PCB.
(4) Insert the Wire (TYPE B) connector into CN110 of the PCB.
(5) Insert the Wire (TYPE B) connector into Wire (FAN MOTOR).
(6) Insert the cover.

Cover

Wire

 (Fan motor)

External Static Pressure and Required Connector Type

Type

A

B

External Static 

Pressure

40 to 80 Pa

0 to 40 Pa

Wire

1

2

3

4

5

6

1

2

3

4

5

1

  BLACK

2

  WHITE

3

  PINK

4

  PURPLE

5

  BLUE

      ARXB24
      ARXB30
      ARXB36

1

  BLACK

2

  WHITE

3

  RED

4

  BLUE

5

  PINK

6

  PURPLE

      
      ARXB45
      

1

  BLACK

2

  WHITE

3

  RED

4

  PINK

5

  PURPLE

6

  BLUE

Remark

Factory setting 

(Standard static pressure)

Accessories 

(Low static pressure)

]1

9373385141-01_IM.indb   Sec1:10

9373385141-01_IM.indb   Sec1:10

7/12/2012   11:16:13 AM

7/12/2012   11:16:13 AM

Summary of Contents for ARXA24GALH

Page 1: ...ltyp Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para person...

Page 2: ...e parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for usin...

Page 3: ...indoor unit from ceiling Drain hose 1 For installing drain pipe VP25 O D 32 I D 25 Hose band 1 For installing drain hose Drain hose insulation 2 Insulates the drain hose and drain cap Wire 1 2 3 4 5...

Page 4: ...sures so that they cannot reach the unit Decide the mounting position with the customer as follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the w...

Page 5: ...la tion WARNING When fastening the hangers make the bolt positions uniform The distance of is adjustable according to the place of the hanging bolts MAX 550 mm MIN 410 mm Slide the unit in the arrow d...

Page 6: ...waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do not use c...

Page 7: ...able below for the flare nut tightening torques CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If...

Page 8: ...evenly until the gauge line and seal 3 Check the drainage 4 Install the heat insulation 5 Use the attached heat insulation to insulate the drain port and band parts of the body Ensure there is no spa...

Page 9: ...earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable an...

Page 10: ...Terminal block Cable end Loop Cable end Loop Loop Screw with special washer Cable Cable WARNING When using solid core cables do not use the ring terminal If you use the solid core cables with the rin...

Page 11: ...he PC board of the indoor unit may be damaged Remote controller cable DIP switch SW1 For 2 wire type For 3 wire type Connect the remote controller cable Y1 Non poler Y2 Non poler Y3 Do not connect 1 Y...

Page 12: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Page 13: ...03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate exter...

Page 14: ...ring arrangement Controller PCB Shield cable Cable tie Field supply Clamps Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The o...

Page 15: ...tary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 to 99 Setting example 63...

Page 16: ...tch SET 4 SW3 referring to the Table C DIP switch SET4 ON OFF SW 1 SW 2 SW 3 SW 4 Table C DIP switch SET 4 SW3 Cooling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18...

Page 17: ...is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has ther...

Page 18: ...the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UTY RNKG UTY...

Reviews: