Page 8
calculations, select the
MaxAir
™ model unit
that will properly meet the load requirements.
.
Table 1 Unit Performance Ratings
Model
MaxAir 30 LV
MaxAir 30e LV
Btuh Heating @180F E.W.T.
48,393
46,236
Btuh Heating @170F E.W.T.
43,938
41,983
Btuh Heating @160F E.W.T.
39,488
37,735
Btuh Heating @150F E.W.T.
35,045
33,492
Btuh Heating @140F E.W.T.
30,610
29,257
Btuh Heating @130F E.W.T.
26,186
25,031
DX Cooling (Tons) (1)
1
1
C.F.M. @ 0.5" E.S.P.
450
425
HP-RPM
¼-1,075
1/3-1,250
FL Amps @ 120/1/60
5.4
5.3
G.P.M. Flow rating
5
5
Fan Coil Size (L/W/H)
24"x14"x18 1/2"
24"x14"x18 1/2"
Supply Air Size
11" x 15 ½”
11" x 15 ½”
Return Air Size Required
12" x 14" min.
12" x 14" min.
Model
MaxAir 50 LV
MaxAir 70 LV
MaxAir 100 LV
Btuh Heating @180F E.W.T.
60,047
79,316
122,103
Btuh Heating @170F E.W.T.
54,496
71,780
110,753
Btuh Heating @160F E.W.T.
48,953
64,428
99,427
Btuh Heating @150F E.W.T.
43,422
57,098
88,132
Btuh Heating @140F E.W.T.
37,904
49,795
76,875
Btuh Heating @130F E.W.T.
32,404
42,523
65,664
DX Cooling (Tons) (1)
1 to 1.5
2
3
C.F.M. @ 0.5" E.S.P.
600
850
1300
HP-RPM
1/4-1,075
1/3-1,075
1-1,075
FL Amps @ 120/1/60
5.1
7.0
12.0
G.P.M. Flow rating
5
7
8
Fan Coil Size (L/W/H)
24"x14"x18 1/2"
30"x19 1/2"x18"
30"x25 1/2"x18"
Supply Air Size
11" x 15 ½”
15" x 16 ½
15" x 22 ½
Return Air Size Required
12" x 14" min.
16" x 15" min.
16" x 16" min.
Summary of Contents for MaxAir 100 LV
Page 31: ...Page 31 WIRING DIAGRAM STANDARD UNITS...
Page 32: ...Page 32 WIRING DIAGRAM MAXe UNITS...
Page 33: ...Page 33 FAN COIL DIMENSIONS AND RETURN AIR SIZE LOCATION...
Page 34: ...Page 34...
Page 35: ...Page 35...
Page 36: ...Page 36...
Page 41: ...Page 41 2 AND 2 5 TON EVAPORATOR COIL SIZES 70 IPCE 24 30A...
Page 42: ...Page 42 SAMPLE PIPING SCHEMATICS...
Page 43: ...Page 43...
Page 44: ...Page 44...
Page 45: ...Page 45...