secondary to keep droplets out but allow trapped 
condensate into secondary fittings.  
 

CAUTION

  Since coil is upstream of the 

blower; all drains 

MUST

 be trapped or sealed. 

Failure to do so will result in condensate overflow 
from the drain pan. Airmark will 

NOT

 be 

responsible for any damages resulting from failure 
to follow these instructions.   

 

 

2" MINIMUM

3" MINIMU

FLEXIBLE

TUBING-HOSE

OR PIPE

A POSITIVE

LIQUID SEAL IS

REQUIRED

DRAIN

CONNECTION

 

 
Fig.1. Typical drain line trap set up 

 

Ductwork 

Duct systems should be installed in accordance 
with standards for air-conditioning systems, 
National Fire Protection Association Pamphlet No. 
90A or 90B. They should be sized in accordance 
with National Environmental System Contractors 
Association Manual K, or whichever is applicable. 

 

On any job, non-flammable flexible collars should 
be used for the return air and discharge 
connections to prevent transmission of vibration. 
Although these units have been specially designed 
for quiet vibration-free operation, air ducts can act 
as soundboards can, if poorly installed, amplify the 
slightest vibration to the annoyance level. 

 

All main supply and return air drops should be 
properly sized as determined by the designer of 
the duct system and should not necessarily be the 
size of the duct flange openings of the unit. 
 
These models have a bottom or front return. 
Discard the drain access panel in the bottom of the 
unit if this is a bottom return application. In case of 
a front return application, the front access panel 
should be removed and discarded. If an accessory 
grill as shown in Fig 2. is being used; the front 
access panel should be removed and discarded.  
 

A filter rack is provided for 

"

20

"

20

"

1

nominal 

size filter. Inspect and clean or replace fliter every 
month. A blocked filter can reduce air flow to the 
coil and hinder the performance of the system.  
 
It is recommended that wherever supply and return 
air sheet metal ducts pass through unconditioned 
areas, they be insulated to prevent excessive heat 
loss during heating operation. When applied in 
conjunction with summer air conditioning, sheet 
metal duct routed through unconditioned areas 
should be insulated and have an outside vapor 
barrier to prevent formation of condensation. 

 

 

 

Fig.2. GFW air handler grill and drain connections  

 

Installation  

 

CAUTION

  Ensure that the unit is adequately 

sized. The tonnage of the outdoor unit should 
never exceed the tonnage of this unit.  

 

WARNING

  The coil was manufactured with a 

dry nitrogen pre-charge. Release the pressure 
through the Schrader valve test port prior to 
installation. If holding pressure is not present, 
return coil to distributor for exchange.   

 

Clean coil fins with degreasing agent or mild 
detergent and rinse fins clean prior to installation.   

 

All connection joints should be burr-free and clean. 
Not removing burr and cleaning may increase the 
chance of a leak. It is recommended to use a pipe 
cutter to remove the spun closed end of the 
suction line.  

 

Summary of Contents for GFW SERIES

Page 1: ..._________________________ SERIAL ____________________________________________________ INSTALLER __________________________________________________ INSTALLATION DATE ___________________________________...

Page 2: ...dification of the unit to operate with alternative power sources Inspection On receiving the product visually inspect it for any major shipping related damages Shipping damages are the carrier s respo...

Page 3: ...he drain access panel in the bottom of the unit if this is a bottom return application In case of a front return application the front access panel should be removed and discarded If an accessory gril...

Page 4: ...ton is stamped on the piston body Instruction for piston change 1 Turn the 13 16 nut once to release any residual pressure in the coil 2 After ensuring that the coil is free of any residual pressure d...

Page 5: ...ilure to eliminate gaps will impair the proper functioning of the TXV valve It is recommended that the TXV bulb be installed parallel to the ground in a horizontal plane The bulb position should be ab...

Page 6: ...inlet side threaded male port and the outlet side female swivel nut port 6 After ensuring that the white Teflon seal is still in place inside the flowrator body screw the female swivel nut onto the f...

Page 7: ...Note Terminals T and N located on the top right side of the board are not intended for field use and should be left un connected CAUTION The aquastat AQ jumper must be in the OFF position at all times...

Page 8: ...9 Use flexible piping and insulate all pipes Plumbing must be in compliance with state or local codes Code CMR248 in Massachusetts The units for hydronic heat have different top and heater box config...

Page 9: ...To properly check the unit s operation the installer should have an electrical current measuring device 0 10 amp Amprobe Fluke air pressure measuring device 0 1 0 in slope gauge and a temperature mea...

Page 10: ...he equipment The filter s removes dust and debris from the air thus helping to keep your air conditioned space clean More important the filter keeps dust and debris from collecting on the heat transfe...

Page 11: ...er heater BTU INPUT assumes a water heater recovery efficiency of 76 For mild climates BTU INPUT structure s heat loss x 1 51 For colder climates BTU INPUT structure s heat loss x 1 58 3 Pump Replacem...

Page 12: ...ndler is undersized for space being heated h Water heater is undersized Note All units installed in Massachusetts are required to be in compliance with CMR 248 Massachusetts State Plumbing Code and or...

Page 13: ...IO 123090 GFW 020113 2013 AirMark HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lea d to safety hazard Wiring diagram for GFW models...

Reviews: