4. Operation
4
-
5
Reset
Grounding method
4.2.5 Circuit protector (CP) for AVR protection
AVR is equipped with circuit-protector (CP) for protection
against overcurrent. Under the following cases, it
happens to function.
In case the machine gets overloaded while engine
speed is still lower.
In case the output voltage of generator is increased
higher than the specified voltage.
<
Symptom
>
When circuit protector functions and load is applied to
the machine, such trouble as larger variance of voltage
and/or delayed voltage recovery follow.
<
How to reset
>
Press the white colored AVR button inside the control
panel for resetting the circuit-breaker.
Note: Do not hold the button with such sharply pointed
things as a screwdriver, ball point pens etc.
A040188
Machine grounding
terminal
Load equipment
Grounding rod
Grounding rod
A040174-1
Summary of Contents for SDG25S-6A7
Page 13: ...1 Safety 1 10 SDG45S 6A6 SDG65S 6A6 6 2 3 5 4 7 8 1 DETAIL OF INSTRUMENT PANEL 9 A040572...
Page 14: ......
Page 15: ......
Page 17: ......
Page 19: ......
Page 21: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 37: ......
Page 38: ......
Page 40: ......
Page 41: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 53: ......
Page 55: ......
Page 63: ...8 Specifications 8 5 8 2 Outline drawing SDG25S 6A7 A040577...
Page 64: ......
Page 65: ......
Page 66: ......
Page 70: ...9 Wiring Diagram 9 4 9 2 Engine Wiring Diagram SDG25S 6A7 A040580...
Page 71: ...9 Wiring Diagram 9 5 SDG45S 6A6 A040581...
Page 72: ...9 Wiring Diagram 9 6 SDG65S 6A6 A040582...
Page 73: ...9 Wiring Diagram 9 7 SDG100S 6A6 A040659...
Page 74: ......
Page 75: ......