4. Operation
4.5 Stopping Procedures
(Procedure)
CD
Switch "OFF" the breaker on the operation panel of the generator.
@ After performing cooling down operation about 5 minutes, place the starter switch to the "STOP"
position to stop the engine.
® While the machine is kept unused, keep the operation selector switch placed to the "OFF" position.
4.6 Adjustment of frequency
• When it is necessary to adjust frequency during operation, take the following steps.
(Procedure)
CD
Loosen the locknut of the engine governor adjusting bolt.
@ Watching the frequency meter, adjust the frequency to the value mentioned in 4.4.1 by
turning the adjusting bolt. Turning & screwing in the adjusting bolt to right increases
frequency. On the other hand, loosening to the left lowers frequency.
® After this adjustment is finished, be sure to tighten the lock·nut securely so that the nut can
be fixed not to get loose during operation.