background image

A16 

 
 
 
 
 
 
 

MOTOR WIRING GUIDE 

(BRANCH CIRCUIT) 

WIRING

 

 

 

To connect motor for proper voltage and rotation, refer to connection diagram on nameplate or inside terminal/conduit 

box. If power factor correction capacitors are used for individual motor power factor correction, do not exceed maximum 
recommended value. 
 

All aspects of the installation must conform to the requirements of the NEC, including Article 430 (Motor Circuits and 

Controllers), and all local codes. Wherever possible, each motor should be powered from a separate circuit of adequate 
capacity to keep voltage drop to a minimum during starting and running.  Increase wire size where motor is located a 
distance from the power source. Wire size must be adequate to minimize voltage drop during starting and running. Refer to 
Tables A and B for suggested wire sizes. Distances shown are one-way between source and load.  Portable cords, if used, 
should be as short as possible  to minimize voltage drop. Long or inadequately sized cords, especially on hard starting 
loads, can cause motor failure. Insulate and protect motor lead connections to prevent cut-through from sharp edges and 
vibration. Tape wire nuts to prevent loosening. All electrical connections in system must be secure to prevent voltage drop 
and localized heating. 
 

Determine direction of rotation before connecting driven equipment to prevent damage.  Remove shaft key if motor is to 

be operated at no-load. On three phase motors, interchange any two line leads (not motor leads) to reverse rotation. On air 
compressors, rotation of flywheel should direct air towards the cylinders.  Look for rotational arrow on flywheel. 
 

All motors must be securely and adequately grounded by wiring with a grounded, metal-clad raceway system, using a 

separate ground bond wire connected to bare metal on the motor frame, or other suitable means. Refer to NEC Article 250 
(Grounding) for additional information. 
 

Explosion-proof motors incorporating over temperature thermostats should be controlled with a magnetic starter. The 

thermostat circuit must be wired in series with the holding coil circuit, as shown on tag or nameplate on motor, to remove 
power from the starter coil if motor overheats. 
 

TABLE A - MINIMUM WIRE SIZES FOR THREE-PHASE MOTORS 

 

MOTOR 

25 FT 

TO  

50 FT 

 

100 FEET 

 

150 FT 

TO  

200 FT 

HP 

200V 

230V 

460V 

200V 

230V 

460V 

200V 

230V 

460V 

1/8 

14(18)

14(18)* 

14(18)* 

14(18)

14(18)* 

14(18)* 

14(16)

14(18)* 

14(18)* 

1/6 

14(18)

14(18)* 

14(18)* 

14(18)

14(18)* 

14(18)* 

14(16)

14(16)* 

14(18)* 

1/4 

14(18)

14(18)* 

14(18)* 

14(16)

14(18)* 

14(18)* 

14 

14 

14(18)* 

1/3 

14(18)

14(18)* 

14(18)* 

14(16)

14(16)* 

14(18)* 

12 

14 

14(18)* 

1/2 

14(16)

14(18)* 

14(18)* 

14 

14 

14(18)* 

10 

12 

14(18)* 

3/4 

14 

14(16)* 

14(18)* 

12 

14 

14(18)* 

10 

14(16)* 

14 

14(16)* 

14(18)* 

10 

12 

14(18)* 

10 

14 

1½ 

12 

14 

14(18)* 

10 

10 

14(16)* 

14 

12 

12 

14(18)* 

10 

14(16)* 

12 

10 

12 

14(18)* 

14 

12 

[*]Type S, SO, SJ, SJO, etc. flexible cable wire sizes.  See NEC Article 400 for ampacity

Note:  

Above wire sizes based on approximate 5% voltage drop during starting; copper conductors; and 75°C type TH, THW, RH, RHW, etc. 

insulation. For aluminum wire, increase two wire size steps minimum. See NEC Article 310 for ampacities of aluminum conductors and 60°C 
type RUW, T, etc. insulation

 

TABLE B - MINIMUM WIRE SIZES FOR SINGLE-PHASE MOTORS 

 

MOT0R 

25 

FT 

50 

FT 

100 

FT 

150 

FT 

200 

FT 

Summary of Contents for V410

Page 1: ...ORE OBTAIN THE SERVICES OF A PROFESSIONAL INSTALLER A FIRE PROTECTION EXPERT SHOULD BE OBTAINED IN THE EVENT THE PRODUCT IS INTENDED FOR USES WHICH PRESENT A POTENTIAL RISK OF FIRE OR FIRE PROPAGATION...

Page 2: ...ND FILTERS TO MAINTAIN WARRANTY TO ORDER SPARE PARTS CONTACT The Local Exhaust Ventilation Company Inc 22 1050 Brock Rd Pickering Ontario L1W 3X4 Tel 905 831 7001 Fax 905 831 7443 Toll Free 1 888 862...

Page 3: ...7 Vibra Pulse Filter Cleaning System 7 8 Electrical 8 Three phase 8 9 Operation 9 10 Maintenance 10 Vibra Pulse System Hose Replacement 10 11 Filter Service 13 Filter Replacement Removal for Cleaning...

Page 4: ...by a dust collector unless it is determined that mixing of materials does not cause hazardous conditions to occur or creates a condition of operation for which the equipment was not intended 2 Under...

Page 5: ...ron particles are captured The main filters have 150 ft2 collection area each for maximum intervals between service The Vibra Pulse is for filter cleaning with dry dust applications After passing thro...

Page 6: ...8 Figure 1...

Page 7: ...SE LEVEL 10 HP STD 76 dBA 5 72 dBA 5 w optional silencer ELECTRICAL Standard Blower Motor 10 HP 7 46 kW TEFC BB motor 3450 RPM 208 230 460 3 60 27 3 25 15 A FILTRATION STANDARD OPTIONAL 1st Stage 16 D...

Page 8: ...f the air cleaner is maintained while the filter is cleaning of 80 PSI Pressure over 100 PSI is NOT recommended at any time and generally reduces cleaning performance A pressure below 70 PSI may decre...

Page 9: ...he Full Load Rating FLA refer to the TROUBLESHOOTING Section of this manual THREE PHASE MOTORS Three phase motors do not have overload protection included in the standard configuration and must be sup...

Page 10: ...VERSING SWITCHES ARE AVAILABLE IF REQUIRED CAUTION CABINET DOORS MUST BE CLOSED WHEN OPERATING THE BLOWER MOTOR WILL BE OVERLOADED IF RUN WITH THE FILTER DOOR OPEN OPERATION Operation of the Model V41...

Page 11: ...Vibra Pulse hose that is used to clean the filter will eventually wear out Check for signs of excessive wear when doing normal filter service or if a decrease in filter cleaning effectiveness is obser...

Page 12: ...ches to the 3 8 hose barb Slide the spring and hose clamp down the VP hose and set aside for later use Next remove the old VP hose this is sometimes easiest to do by cutting the hose at the top where...

Page 13: ...ew Vibra Pulse hose onto the air cleaner s hose barb until fully seated against brass hex on barb see Figure 9 Lubricate with water or Windex to ease installation Do not use oil or grease as lubricant...

Page 14: ...pre coat will stay on the filters Save any material that falls into the pan for treating replacement filters A Material Safety Data Sheet MSDS will be furnished upon request Please contact the Airflow...

Page 15: ...10 seconds Next PULL the button outwards for 5 10 seconds This will clean the other side of the filter Repeat this process 2 or 3 times See Figure 12 4 Open the filter access door Remove and empty the...

Page 16: ...al activated carbon or other can be emptied from the module and refilled with fresh adsorber Refer to the Figure 13 Use the large opening to fill the majority of the module After as much material can...

Page 17: ...some dust may be expelled when unit is first turned on The unit should be test run after each refilling operation OTHER SERVICE Most other components of your Model V410 air cleaner require little or n...

Page 18: ...Access Door Gasket 8 7KB2 3001 2 Knobs Door Retaining 9 1PN3 2735 1 Filter Access Door 10 7PH3 8003 A R Filter Access Door Gasket 11 7HG4 3002 2 Lift Turn Latch 12 1PN3 2740 1 Dust Tray 13 1AC5 7743...

Page 19: ...A12 Figure 14 Model V410 filter lifting assembly Figure 15...

Page 20: ...ource inadequate Static load on blower too low Check voltage at motor with motor running Voltage should be 10 of motor rating If not check 1 Power source 2 Wire size from source Check running amps of...

Page 21: ...FROM NAMEPLATE MOTOR VOLTAGE FROM NAMEPLATE ALWAYS USE AIRFLOW SYSTEMS REPLACEMENT PARTS AND FILTERS TO MAINTAIN WARRANTY TO ORDER SPARE PARTS CONTACT The Local Exhaust Ventilation Company Inc 22 1050...

Page 22: ...BRANCH WIRING A1 2 MOTOR TROUBLE GUIDE A2 3 TYPICAL INSTALLATION WIRING DIAGRAM A3 4 4KT11096 OWNERS MANUAL ADDENDUM OPTIONAL AUTO CLEAN CONTROLLER SYSTEM A4 5 OWNERS MANUAL ADDENDUM STATIC PRESSURE R...

Page 23: ...ompressors rotation of flywheel should direct air towards the cylinders Look for rotational arrow on flywheel All motors must be securely and adequately grounded by wiring with a grounded metal clad r...

Page 24: ...an electric motor service firm for assistance TROUBLE CAUSE WHAT TO DO MOTOR 1 Blown Fuses 1 Replace with time delay fuses FAILS or circuit breakers Check for TO START grounded winding 2 Low voltage 2...

Page 25: ...VIBRATES 2 High voltages 2 Check wiring connections OR IS transformer EXCESSIVELY 3 Worn damaged dirty or 3 Replace check loading and NOISY overloaded bearings alignment 4 Loose or defective or 4 Tigh...

Page 26: ...A19 TYPICAL INSTALLATION WIRING DIAGRAM...

Page 27: ...E IMPOSSIBLE TO LIST THEREFORE OBTAIN THE SERVICES OF A PROFESSIONAL INSTALLER A FIRE PROTECTION EXPERT SHOULD BE OBTAINED IN THE EVENT THE PRODUCT IS INTENDED FOR USES WHICH PRESENT A POTENTIAL RISK...

Page 28: ...A21 PART 4KT1 1096 REV 11 98 A 26 1894...

Page 29: ......

Page 30: ...ND FILTERS TO MAINTAIN WARRANTY TO ORDER SPARE PARTS CONTACT The Local Exhaust Ventilation Company Inc 22 1050 Brock Rd Pickering Ontario L1W 3X4 Tel 905 831 7001 Fax 905 831 7443 Toll Free 1 888 862...

Page 31: ...2 Airflow Systems Sets the Standard 4 3 Specifications 4 Electrical 4 4 Inspection 4 5 Preparation and Installation 5 6 Electrical 5 Single phase 6 Three phase 7 7 Autoclean Unit Operation 9 8 Mainten...

Page 32: ...3...

Page 33: ...leaning times are easily set on the board In the case of the single filter systems the duration of the cleaning is controlled by a time delay relay SPECIFICATIONS ELECTRICAL Standard Input Voltage 115...

Page 34: ...VAC single phase units supply 115V to the AUTOCLEAN control with one power lead and the neutral connection The step down transformer is located inside the enclosure with the AUTOCLEAN board to minimi...

Page 35: ...5...

Page 36: ......

Page 37: ...electrical connections for a 115 VAC single phase unit with a single cartridge See Figure 2 for 115 VAC single phase dual cartridge units with a relay Figure 3 illustrates115 VAC single phase dual car...

Page 38: ...ing any two of the leads will reverse the motor but will not have any effect on the AUTOCLEAN control e g reverse L1 and L2 or L2 and L3 Figure 4 shows the typical electrical hook up for the AUTOCLEAN...

Page 39: ...7 Figure 5 Dual Cartridge with Relay Figure 6 Dual Cartridge without Relay...

Page 40: ......

Page 41: ...8 Figure 7 DT 3000 with Relay Figure 8 DT 3000 without Relay...

Page 42: ...8...

Page 43: ......

Page 44: ...TIME duration or start with an initial setting of 15 seconds Once the complete sequence has been followed the control waits for motor startup to occur again Restarting the motor during a cleaning cycl...

Page 45: ...9...

Page 46: ......

Page 47: ...EPLACEMENT PARTS Listed below are common replacement parts for the AUTOCLEAN controller system Check nameplate for actual voltage used Consult with a local Airflow Systems Representative for ordering...

Page 48: ...10...

Page 49: ......

Page 50: ...N AIR PLENUM WHICH INCLUDES THE STATIC PRESSURE RELIEF VALVE The Local Exhaust Ventilation Company Inc 22 1050 Brock Rd Pickering Ontario L1W 3X4 Tel 905 831 7001 Fax 905 831 7443 Toll Free 1 888 862...

Reviews: