ULTIMA 2000
Chillers
Chillers
Installation & Maintenance Manual : 903-099 IM E 05/00
9
Installation Data
as TM
DIMENSIONS &
WEIGHTS
Note: Water connections shown are standard, other handing options are available
upon request.
A
85
2595
85
2200
B
H
J
G
E
D
C
F
2100
Electrical Panels
with Mains
Isolator
Acoustic Enclosure
(DQ & DSQ Only)
P1
P2
P3
P4
P5
P6
P7
P8
20mm Ø Mounting Holes
(located on the underside of
the base frame)
90
90
Water Connections:
USC250-8 to USC350-12 = DN150 PN16
USC400-12 to USC650-16 = DN200 PN16
50
50
Dimensions
A
B
C
D
E
F
G
H
J
USC250DSQ-8 to
USC300DSQ-8
mm
4040
460
435
1120
(1)
(1)
655
1837
1753
USC350DSQ-12
mm
5740
460
400
1410
1465
1880
585
2198
1753
USC400DSQ-12 to
USC500DSQ-12
mm
5740
475
400
1410
1465
1880
585
2213
1723
USC575DSQ-16 to
USC650DSQ-16
mm
7440
525
400
2000
1645
2810
585
2522
1723
Point Loadings & Total Weights
P1
P2
P3
P4
P5
P6
P7
P8
Machine
Operational
USC250DSQ-8
kg
680
540
(1)
340
680
540
(1)
340
3120
3208
USC275DSQ-8
kg
690
550
(1)
340
680
540
(1)
340
3140
3228
USC300DSQ-8
kg
690
550
(1)
340
690
550
(1)
340
3160
3248
USC350DSQ-12
kg
655
680
540
255
615
640
510
245
4140
4217
USC400DSQ-12
kg
655
680
540
255
655
680
540
255
4260
4383
USC450DSQ-12
kg
675
700
540
255
655
680
540
255
4300
4416
USC500DSQ-12
kg
675
700
540
255
675
700
540
255
4340
4449
USC575DSQ-16
kg
885
915
650
365
780
800
650
365
5410
5550
USC650DSQ-16
kg
885
915
650
365
885
915
650
365
5630
5770
(1)
Only 6 fixing and loading points to this model.