Trou
ble
sh
oo
tin
g
IT Cooling
LogiCool InRak™
87
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Alarms
Code
Description
Auto Reset
Unit
Disabled
Component Disabled
Cause
Action
AL02
Clock board fault or not connected
●
●
Indicates an error with the real time clock on-
board the controller. During alarm any time
zones set up would be ignored.
Once the clock returns to
functioning correctly the alarm
will be automatically reset and
any time zones set up will be
restored.
AL03
Extended memory fault
●
●
Controller memory fault
Alarm is generated
AL04
Liquid pressure probe alarm
●
●
Indicates that there is a fault with the
corresponding probe/input, possible causes are
the sensor going open circuit or there is a wiring
fault. All sensor alarms are auto reset once the
fault has been rectified.
Head pressure control is
disabled and the outdoor coil fan
is set to probe alarm level
AL05
Return humidity probe alarm
●
●
Alarm is generated
AL06
Supply air temperature probe
alarm
●
●
AL07
Return air temperature probe
alarm
•
•
AL08
Differential pressure probe alarm
•
•
•
Alarm is generated. Unit shuts
down – airflow fail
AL10
Liquid line temperature probe
alarm
•
•
Alarm is generated
AL11
Aisle/differential pressure probe
alarm
•
•
AL13
Low pressure switch alarm
•
•
•
Indicates that the low pressure safety switch has
been tripped and the controller has switched off
the unit.
Alarm will auto-reset up to 3
times in 24 hours. A further trip
will require manual reset.
AL14
Backup power supply active
•
•
Alarm is generated. Heating and
humidification are disabled
AL15
Refrigerant leak detector alarm
•
Indicates the unit has detected a refrigerant leak.
Once the refrigerant level in the
air has fallen below set point
the alarm will reset. Unit will
either shutdown or pumpdown
depending on setting chosen.
AL16
High pressure alarm
•
•
•
Indicates high liquid pressure. Unit is shut down.
Alarm will auto-reset up to 3
times in 24 hours once the
pressure has decreased to
a safe level. A further trip will
require manual reset.
AL17
High pressure alarm critical trip
count
•
•
Indicates high pressure alarm has tripped 3
times in 24 hours.
Unit is disabled. Alarm must be
manually reset.
AL18
pLAN offline alarm
•
Indicates that there is a network fault between
the units. If the unit is configured as standby
then the unit will become active until the network
fault is corrected.
The alarm will automatically
reset once the network fault is
corrected.
AL19
Master unit offline alarm
•
Indicates that the master unit has been lost from
the network. If the unit is configured as standby
then the unit will become active until the network
fault is corrected.
AL20
High discharge temperature
warning
•
Discharge temperature has reached 120°C
Alarm will reset once the
temperature is below threshold
AL21
High discharge temperature alarm
•
•
The discharge temperature is over the threshold.
Unit is disabled after 3 occurrences in 24 hours
AL22
Discharge temp. alarm critical trip
count
•
•
•
Indicates high discharge temperature alarm has
tripped 3 times in 24 hours.
Unit is disabled. Alarm must be
manually reset.
AL24
Fan trip alarm
•
•
The alarm is generated if the controller receives
a fan trip signal from the fan.
Alarm is generated