background image

507148-01

Page 5 of 14

Issue 1406

Vertical 

Venting 

    

1.  Local building codes may have more stringent 

installation requirements and should be consulted 

before installation of the unit.

2.  The flue pipe should be as short as possible to do the job.

3.  The  flue  pipe  should  not  be  smaller  than  the  outlet 

diameter of the flue outlet of the furnace.

4.  Single wall flue pipe should not run outside or through 

any unconditioned space.

5.  The chimney should terminate 2’ above the highest peak 

of a peaked roof, and 3’ higher than a flat roof.

6.  The flue pipe must not pass through a floor or ceiling. 

Clearances to single wall flue pipe should be no less than 

specified in the Clearances section beginning on page 3.

7.  The flue pipe may pass through a wall where provisions 

have been made for a thimble as specified in the 

Standards of the National Board of Fire Underwriters 

(see Figure 6).

8.  The flue pipe should slope upward toward the chimney 

on a horizontal run of at least 1/4” per foot and should 

be supported by something other than the furnace (see 

Figure 7 on this page and Figure 8 on page 8).

9.  Extend the flue pipe into the chimney so that it is flush 

with the inside of the flue liner.  Seal the joint between 

the pipe and the liner.

10. The furnace shall be connected to a factory-built 

chimney or vent complying with a recognized standard, 

or a masonry or concrete chimney lined with a lining 

material acceptable to the authority having jurisdiction.

11.  When two or more appliances vent into a common flue, 

the area of the common flue should not be less than the 

area of the largest flue or vent connection plus 50% of 

the areas of the additional vents or flue connections. The 

chimney must be able to sufficiently vent all appliances 

operating at the same time.

12.

  The flue pipe shall not be connected to a chimney 

flue serving a solid fuel appliance or any mechanical 

draft system.

13. All unused chimney openings should be closed.

14.  All vent pipe run through unconditioned areas or outside 

shall be constructed of factory-built chimney sections 

(see Figure 7).

15. Where condensation of flue gases is apparent, the vent 

shall be constructed to prevent the condensation from 

entering the flue transition box opening.  Provisions shall 

be made to drain off the condensate (see Figure 7).

16. Vent connectors serving this appliance shall not be 

connected into any portion of a mechanical draft system 

operating under positive pressure.

17. Keep the area around the vent terminal free of snow, 

ice, and debris.

Wall Thimble

Figure 6

Thimble

Flue Pipe

Combustible Wall

Figure 7

Factory-Built Chimney

Rear Flue

Barometric Control

(in either location)*

Factory-Built
Chimney

Drain for
Condensate

Factory-Built

Chimney

Barometric Control
(in either location)*

Drain for
Condensate

*  Barometric control may be installed in either the vertical or 

horizontal section of the flue pipe within 18” of the flue outlet of 

the furnace.

Front Flue

Summary of Contents for L85BF Series

Page 1: ...actions that could cause property damage personal injury or death WARNING Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit CAUTION This furnace is not approved for installation in a mobile home Do not install this furnace in a mobile home Installation in a mobile home could result in actions that could cause property damage persona...

Page 2: ... adjust pressure to 145 or 150 psig ____________________________________________ Always verify proper pump pressure to corresponding tables with instructions supplied with unit F After 10 minutes of operation obtain flue temperature reading 1st __________ 2nd __________ 3rd _________ G Obtain smoke reading 1st __________ 2nd __________ 3rd _________ H Measure CO2 1st __________ 2nd _________ 3rd _...

Page 3: ...e nearly the same length This allows each room to receive an equal and proper amount of heat This may vary with each particular installation Position the furnace so the pipe connection to the chimney will be of minimum distance and have a minimum of fittings In utility rooms or similar installations the door or access opening should be large enough to permit replacement of the furnace or another a...

Page 4: ...un full size to a location outside the confined space and completely sealed so that no air from the confined space can be circulated through the heating duct system Outdoor Make Up Air A minimum mixed return air temperature of 60 65 F must be maintained for outdoor make up air to prevent condensation and corrosion Venting Chimney Before installing the furnace a thorough inspection of the chimney s...

Page 5: ...ncrete chimney lined with a lining material acceptable to the authority having jurisdiction 11 When two or more appliances vent into a common flue the area of the common flue should not be less than the area of the largest flue or vent connection plus 50 of the areas of the additional vents or flue connections The chimney must be able to sufficiently vent all appliances operating at the same time ...

Page 6: ...n of this furnace has been approved for horizontal venting with the following mechanical vent systems Refer to the manufacturer s installation instructions for proper installation procedures and service parts information Vent systems are available through the local distributor Barometric draft control must be used in the horizontal venting sidewall system It must be located within 18 of the furnac...

Page 7: ...he appliance All wiring must be appropriate Class I wiring Wiring must be installed in rigid metal conduit intermediate metal or be otherwise suitably protected from physical damage Refer to the wiring diagrams supplied with the venter kit for proper electrical connections 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction l...

Page 8: ...lected cooling CFM Passive and Active Dehumidification For situations where humidity control is a problem a dehumidification feature has been built into the variable speed motor At the start of each cooling cycle the variable speed motor will run at 82 of the rated airflow for 7 5 minutes After 7 5 minutes has elapsed the motor will increase to 100 of the rated airflow To achieve additional dehumi...

Page 9: ... CFM 50 Static Heat Set ting A Heat Set ting B Heat Set ting C Heat Set ting D Cool Setting A Cool Set ting B Cool Set ting C Cool Set ting D L885UFC67V14 1 2 D 1200 1500 1400 1300 1200 1400 1200 1000 800 L85UFC87V14 1 2 A 1500 1500 1400 1300 1200 1400 1200 1000 800 L85UFC104V20 3 4 C 1550 1850 1730 1550 1400 2000 1800 1600 1200 L85UFC118V20 3 4 A 1850 1850 1730 1550 1400 2000 1800 1600 1200 L85BF...

Page 10: ...ampling hole should be at least two flue diameters above the breech or elbow at the breech but ahead of the barometric damper 2 Operate burner for approximately 5 to 10 minutes 3 Take a draft reading at the service hole in the flue outlet Adjust barometric draft control in the stack to achieve an overfire draft of 01 to 02 and a breach of 02 to 04 4 Pull and record a smoke reading at the service h...

Page 11: ...ent against the center lines marked on the gauge 2 If nozzle is not centered but found to be too far left or right a new nozzle will need to be ordered Do not attempt to adjust by bending the 90 elbow in oil line Sequence of Operation Heating see Figure 13 on page 12 Thethermostatcallsforheat activatingtheburnermotor After a 15 second pre purge period power is sent to the burner and ignition is es...

Page 12: ...dification mode After 7 5 minutes the blower motor runs at 70 of the selected cooling air flow until 1st stage cooling demand is satisfied A call for 2nd stage cooling from the thermostat closes the R to Y2 circuit on the blower interface board The blower motor ramps up to 100 of the selected cooling air flow When the demand for cooling is met the blower ramps down to Y1 until satisfied then ramps...

Page 13: ...s Department 11 West 42nd Street New York NY 10036 MAINTENANCE AND SERVICE Oil Burner It is recommended that the nozzle and oil filter be checked before each heating season Also recheck the conditions shown on the OIL FURNACE START UP CHECKLIST found on page 2 Close the oil line shutoff valve if the burner is shut down for an extended period of time Flue Pipe Have the flue pipe inspected annually ...

Page 14: ...507148 01 Page 14 of 14 Issue 1406 Figure 17 Wiring Diagram P N 48252 001 ...

Reviews: