![Aircel AES Series User Manual Download Page 40](http://html1.mh-extra.com/html/aircel/aes-series/aes-series_user-manual_2876267040.webp)
| VF, DHT, AES Series Manual
Refrigerated Air Dryer User Manual
36
APPENDIX A:
SPECIFICATIONS
A.1 Tables of specifications - VF Series
For dimensions, weights, and connection sizes, see the drawing of the dryer model provided at purchase.
Type of dryer:
Refrigerated
Power supply:
115, 230, 460 Volt / single or three
phase / 60Hz
Refrigerant type:
R-134A & R-404A
Chemical Composition:
HFC
All Models
R-134a
R-404a
Parameter
Description
Air Pressure
Air Inlet
Temperature
Ambient
Temperature
Evaporator
Temperature
Suction Gauge
Reading
Discharge Gauge
Reading
Suction Gauge
Reading
Discharge Gauge
Reading
Optimum
100 psig
100 (°F)
100 (°F)
35 - 42 (°F)
28 - 40 psig
160 - 230 psig
75 - 90 psig
290 - 400 psig
Maximum
200 psig
140 (°F)
120 (°F)
60 (°F)
60 psig
260 psig
130 psig
410 psig
Minimum
40 psig
40 (°F)
35 (°F)
32 (°F)
28 psig
80 psig
75 psig
160 psig