INST APD0397 C140529

2

PACKAGE CONTENTS AND STROBE CONSTRUCTION

Remote accessories that include the indicator/control unit are shipped with the following parts:
 

• Installation Instructions

 

• Indicator/Control Unit with back box mounting screws (back box not supplied)

 

• Keys for Test/Reset function (MSR-50RK) OR Magnet for magnet test function (MSR-50RM)

 

• Decora Style Cover Plate with mounting screws (single gang)

Remote accessories that include the indicator/control unit and sounder module are shipped with the

following parts:
 

• Indicator/Control Unit package

 

• Sounder Module with back box mounting screws (back box not supplied)

 

• Decora Style Cover Plate with mounting screws (double gang)

Remote accessories that include the indicator/control unit, sounder module and strobe assembly are 

shipped with the following parts:
 

• Indicator/Control Unit package

 

• Sounder Module package

 

• Strobe Assembly 

 

• Strobe Lens Decals for optional use: “SMOKE”, “FIRE” 

 

  

(1 of each version in horizontal orientation plus 1 each     vertically set)

Strobe Assembly Units may be ordered seperately but are only functional when paired with the 

MSR-50A Sounder Module. Strobe Assemblies are shipped with:
 

• Installation Instructions

 

• Strobe Assembly 

 

• Strobe Lens Decals for optional use: “SMOKE”, “FIRE” 

 

  

(1 of each version in horizontal orientation plus 1 each     vertically set)

Decora Cover 

Plate 

Sounder Module

(MSR-50A)

Strobe Assembly

(MSR-50V)

STROBE CONSTRUCTION

MSR-AV and MSR-A Module Audible Sounder Output Configurations

The sound output level is selectable at either 83 db (low) or 87 db (high).  The unit is shipped 

pre-set to the higher level. To change the selection to the lower tone simply remove the pre-

installed jumper plug where shown (at right).

The sound output format on these units is selectable for Steady Tone or Temporal (Code 3) 
Pattern.  The unit is shipped with the output format programmed for Temporal (Code 3).

Simply remove the pre-installed jumper plug where shown (at right) for Steady Tone. 

Note:  As with all final completed installations, equipment should be completely  

tested to insure proper functionality.

MECHNICAL SPECIFICATIONS 

 

Power Requirements: 

 

 

MSR-50RM        

 

 

MSR-50RK                           

Standby:                  

 

06mA 

 

 

Standby:   

 

06mA        

 

Detector Alarm:         

 

22mA 

 

 

Alarm:   

 

22mA       

Remote Alarm Test:    

 

37mA 

 

 

Alarm w/Sounder:   

138mA     

Detector Alarm w/Sounder:          

57mA 

 

 

Alarm w/Sounder & Strobe:  92mA       

Detector Alarm w/Sounder & Strobe:  92mA
Remote Alarm w/Sounder:      

72mA

Remote Alarm w/Sounder & Strobe:  107mA

 

MSR-50AV 

   MSR-50A 

  MSR-50V

 

Standby 

current: 

 

0.0 

mA 

    0.0 

mA 

   0.0 

mA

Alarm 

current: 

70.0 

mA    35.0 

mA 

   70.0 

mA 

Alarm db: 

68 db @10 ft 

(high)

; 53 db @ 10 ft

 (low)

 

69 db @10 ft 

(high)

; 54 db @ 10ft 

(low)

 N/A

Alarm 

candela: 

2.0 

on 

axis 

   N/A 

   2.0 

on 

axis

Temperature: 0

o

C to 49

o

C (32

o

F to 120

o

F) 

 

0

o

C to 49

o

C (32

o

F to 120

o

F)   

0

o

C to 49

o

C (32

o

F to 120

o

F)

Dimensions: 

Single Gang Plate: 4½” (114.3mm)H x 2¾” (69.85mm)W

 

Double Gang Plate: 4½” (114.3mm)H x 4½” (114.3mm)W

Wiring: 

14-28AWG, Solid or Stranded

Approvals: 

UL Listed for use with Air Products and Controls duct smoke detectors referenced herein including all RW- Series, SM- Series

 

and SL- Series duct smoke detectors. Listings and Approvals shown are for MSR-50RK and MSR-50RM Series ONLY

 

 

 

UL URRQ.S7425 •  CSFM 7300-1004:107 • MEA 73-92-E Vol.31

Pre-installed Jumpers 

set output to High Level 
Sound, Temporal Pattern. 

Take off the jumper(s) for 
alternate settings.

Rear View of MSR-A  

Control Unit