background image

9

3.4. 

Ducts, Grilles and Wall Cover

The length of the air ducts is calculated on the basis of the 
thickness of the wall/dimensions of the roof.

NB! Please note that the duct holes in the wall must 
have an outward downward gradient of 1-2% to 
prevent heavy rain from entering the unit.

NB! Exhaust air ducts and supply air ducts must be 
insulated against condensation on the ducts, if they 
are within the building envelope. 

NB! Condensation and heat insulation should be 
performed according to standards and rules in effect.

NB! Fire requirements according to standards and 
rules in effect must be observed.

NB! The installation of ventilation ducts should be 
performed according to standards and rules in effect.

NB! Exhaust air ducts and supply air ducts must be 
insulated against noise if they are visible. Service 
access must be provided to all components.

Finally, fit a suitable circular grille with the slats pointing 
downwards on the outside of the wall or a roof cap up on 
the roof.

NB! The supply air grille is fitted with the slats pointing 
downwards and the exhaust air grille is fitted with 
vertical slats, at the AM 900 pointing to the right. 

NB! To avoid an increase in noise level, it is important 
that the pipes should not get twisted or compressed 
against the air spigots of the unit.

NB! Remember to seal around the penetrations. See 
section “Sealing the Gaps Around Ducts”.

An external wall cover may be fitted as an optional alter-
native to grilles at the AM 900.

3.5. 

Roof Cap

2

3

1

Fit roof caps on the roof to finish off the installation of 
exhaust and supply through a roof. Installation will depend 
on the roof construction (3). The illustration shows which 
roof caps are for exhaust (1) and supply (2).

NB! Fire requirements for the installation of multiple 
systems must be observed according to the standards 
and rules in effect.

3.6. 

Sealing the Gaps Around Ducts

Sealing of the gaps around ducts is performed as shown in 
the sectional drawing below.

1

2

3

4

4

5

2

5

Application of a seal (shown here on a model with wall 
ducts) is important at the ducts (3) indside and the outside 
edges (4) in order to prevent draughts between the unit 
(1) and the wall/roof (2) as well as between the ducts (3) 
and the wall/roof (2).

Sealing on the inside between the pipes (3) and the wall/
ceiling (2) can also be performed between the air handling 
unit (1) and the wall/roof (2) at position (5) before fitting 
the air handling unit.

Depending on the condition of the wall/ceiling and the 
dimensions of the air handling unit, a sealant that retains 
elasticity over the long term or expanding sealing tape can 
be used to obtain a flexible seal. This material is to be applied 
to the rear of the unit around the air spigots, or at the side 
of the duct holes on the wall to even out irregularities on 
the wall/ceiling.

Summary of Contents for AM 1200 H

Page 1: ...1 2 3 AM 900 1200 INSTALLATION ...

Page 2: ... unit should not be used without the filters specified in the Operator s Manual The manufacturer cannot be held liable for damage arising from use or installing in contravention of these instructions Themanufacturerreservestherighttomake changes without notice All values stated are nominal values and can be affected by local conditions Failure to observe the warnings indicated by a danger symbol i...

Page 3: ...ir Handling Unit 7 3 4 Ducts Grilles and Wall Cover 9 3 5 Roof Cap 9 3 6 Sealing the Gaps Around Ducts 9 3 7 Fitting of Panels AM 1200 10 3 8 Installation Check 10 Appendix 1 Dimensional Drawings 11 AM 900 H 11 AM 900 V 11 AM 1200 H 12 AM 1200 V 13 Appendix 2 Additional Dimensions 15 Water Comfort Heater and condensate drain 15 AM 1200 15 3 ...

Page 4: ...4 ...

Page 5: ...tion 1 Airmaster air handling unit AM 2 Control panel Airlinq Viva Airlinq Orbit or 3 Carbon dioxide CO2 sensor optional 4 Motion sensor PIR sensor optional 5 Set of pipes optional 6 Grilles optional 7 Wall cover optional 8 Operator s Manual for programming and Mounting Instructions and Installation Manual for installation to be handed over to the owner ...

Page 6: ...itmustbeevenandlevel 3 1 Positioning of the Unit The diagram below shows the most important dimensions relating to the positioning of the unit Shown here on an AM 900 B C A A CO2 sensor B Approximately 1 m C Approximately 2 m NB TheCO2 sensormustnotbefittedclosetoawindow or door NB Smoke detectors must not be too close to the inlet and extraction air flow NB For the minimum floor to ceiling height...

Page 7: ...ader 4 Adjust the feet in a way so the unit is at level 5 Move the air handling unit to its final position so that the duct connections fit into the holes without touchingthewall roof Theunitcanbemovedtothe place with for instance a pallet loader 6 Fit the floor panel 7 Fit the brackets to the top of the air handling unit and the wall 8 Seal the gap between the air handling unit and the wall by us...

Page 8: ... and adjust the wheels of the exchanger section in line with the ventilator section 5 Run the cables from the heat exchanger section into the electrical connection compartment at the top of the ventilator section 6 Push the heat exchanger section up against the ventilator section 7 Adjustthemachinefeetattheendoftheexchanger section The sections should now be up against each other both level and al...

Page 9: ...nit NB Remember to seal around the penetrations See section Sealing the Gaps Around Ducts An external wall cover may be fitted as an optional alter native to grilles at the AM 900 3 5 Roof Cap 2 3 1 Fit roof caps on the roof to finish off the installation of exhaust and supply through a roof Installation will depend on the roof construction 3 The illustration shows which roof caps are for exhaust ...

Page 10: ... side see black arrows The angels should point upwards The top half of the unit shows the 2 mounting strips for large design panels the bottom half shows the 4 mounting strips for small design panels see white and black arrows 2 Fit all the design panels on the angels of the unit the top strips and the extract panel set on the unit 3 Fit the plinths 3 8 Installation Check yes no Data and serial nu...

Page 11: ...30 52 27 80 Ø315 Ø315 800 2323 588 602 4 3 7 6 5 1 2 Appendix 1 11 Appendix 1 Dimensional Drawings AM 900 H 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Electrical connections 6 Condensate drain 7 Wall bracket Dimension can be reduced by up to 50 mm when there is no panel and the machine shoes are fully screwed down AM 900 V ...

Page 12: ...4 5 3 7 8 AM1200HL 750 248 1076 400 400 72 2098 2427 496 25 3 5 1 2 6 4 7 8 AM1200HR Appendix 1 12 AM 1200 H 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Connection compartment electrics 6 Condensate drain 7 Service cover 8 Valves water comfort heater ...

Page 13: ...48 496 AM1200HC 496 2427 72 2098 450 249 Ø400 Ø400 248 25 2406 2 1 5 3 4 6 7 8 AM1200VL Appendix 1 13 AM 1200 V 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Connection compartment electrics 6 Condensate drain 7 Service cover 8 Valves water comfort heater ...

Page 14: ...6 AM1200VR 4 6 3 5 2 1 7 8 496 2427 72 2098 450 249 Ø400 Ø400 2406 248 2 1 5 3 4 6 7 8 AM1200VC Appendix 1 14 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Connection compartment electrics 6 Condensate drain 7 Service cover 8 Valves water comfort heater ...

Page 15: ...ensions Water Comfort Heater and condensate drain AM 1200 Connection from beneath 1 DELIVERY FREM 2 RETURN RETUR 3 CONDENSATE KONDENS 107 141 175 130 148 107 141 175 83 83 92 92 101 101 130 148 139 139 207 249 Ø20 12xØ20 2427 496 3 6x 1 6x 2 ...

Page 16: ...13912 Version 2017 10 19 Industrivej 59 Tel 45 98 62 48 22 info airmaster dk DK 9600 Aars Fax 45 98 62 57 77 www airmaster as com Denmark ...

Reviews: