Air King AKEV Series Operating Manual Download Page 5

need to be cleaned or replaced. Press and hold the power button for 5 seconds to reset the 

maintenance clock. Some units feature a red LED that will light after 3 months if the initial 

service reminder is not turned off.

OPERATION FOLLOWING A POWER INTERRUPTION

If the electrical service to the ventilator is for some reason interrupted, the mode of operation 

active in the wall control at the time of the interruption will resume when the electrical service to 

the ventilator resumes. Any custom settings will have been saved.

CUSTOM SETTINGS

The control allows adjustments to customize its use for unique circumstances. Any of these 

changes are written into the control’s memory but can be changed an infinite number of times. 

We recommend that only a qualified technician make these adjustments as they can affect the 

nature of the ventilator’s performance. The customizable features include:
 

1. Adjusting the run time of the maintenance clock

 

2. Calibrating the humidity sensor

 

3. Turning off/on recirculation functions.

To access the custom settings menu, simultaneously press and hold the up and down arrow 

buttons for 15 seconds. You will note that the backlight would have turned on after 10 seconds. 

Once in the custom settings menu, use the arrow buttons to navigate among choices for a 

given setting. Pressing the mode button will preserve factory settings or initiate any change 

and will move you on to the next customized feature. After 5 seconds of no button activity, 

current settings will be written and the control will resume regular operation as programmed.

ADJUSTING THE RUN TIME MAINTENANCE CLOCK

Once you are in the custom settings mode the first option will be maintenance 

clock. You will see the factory setting of this feature: 3 months. To keep factory 

setting, press the mode button or use the up and down arrow buttons to change 

the setting in the range of 1-12 months. Once any desired change to the setting 

is in place (if any), press the mode button.

CALIBRATING THE HUMIDITY SENSOR

If calibration is not desired, skip this step by simply pressing the mode button 

to keep factory calibration active. If calibration is desired, use the up and down 

arrow keys to calibrate the humidity sensor in 5% increments. To program any 

changes, press the mode button.

TURN OFF/ON RECIRCULATION FUNCTIONS

You will now see an animated recirculating arrow indicating that the 

recirculation by factory default is enabled. Use the up and down arrow keys to 

turn off the recirculation functions (static arrow) or on (animated arrow).
As noted previously, recirculation functions must be turned off for use with ventilators that do 

not have a recirculation damper. For such units, use of recirculation functions would only result 

in full-time, low-speed operation.

SECTION 11

Status LED

1.  Your control board is equipped with status lights to indicate mode of operation as follows:

SECTION 12

Start-Up

1.  Ensure the controls are connected in accordance with Section 7 and/or 10.
2.  For electrical hook-up, plug into a properly grounded 120 volt receptacle.
3.  Ensure that the machine is piped to an adequate drainage source, i.e. through the drain 

hose supplied.

SECTION 13

Operating Your System

It is recommended that the unit run on low speed at all times to ensure a steady supply of 

fresh air and removal of indoor pollutants. How much a home needs ventilation can depend 

on several factors such as number of inhabitants, cooking habits, hobbies, presence of pets, 

opening windows, etc. so no two households are necessarily the same for the amount and 

frequency of ventilation they need. Observance of moisture on windows, lingering odors and a 

sensation of stuffy, stagnant air are all signs for the need of ventilation in general or increased 

ventilation in specific cases. The controls for your ventilation system offer means to regulate 

how much and how often the home is ventilated.
The included control is equipped with a dehumidistat, or “d-stat”. A d-stat monitors ambient 

relative humidity (RH) and has selectable settings, generally 30%-80% RH. When ambient 

humidity is detected above the setpoint, it will trigger high speed in the ventilator. The unit 

will run in high speed until the ambient air returns to the setpoint RH. 

Your ventilator is not 

a dehumidifier

, however ventilating can have a dehumidifying effect by simply removing 

high RH air from the space, particularly during cooler/cold seasons when outdoor humidity is 

typically lower than indoor humidity. Typical dehumidistat settings are as follows:

Winter Operation:

 40% - 60%. Lower settings may be necessary in colder zones to keep 

windows free of condensation. If you notice the air is uncomfortably dry in winter, you 

might set humidity to a higher level or choose an operation mode above which operates 

the ventilator less or for shorter periods.

Spring/Fall Operation:

 50% - 60%.

Summer Operation:

 For air conditioned homes run the ERV/HRV as recommended for 

winter operation, i.e. continuous low speed or use a 20/40 setting. In homes without 

air conditioning, there is no need to run the ERV/HRV during the day when windows are 

open. If the ERV/HRV is connected to the bathrooms(s) or kitchen, use the standby setting. 

The typical dehumidistat summer setting is 65%-80% or OFF.

SECTION 14

Use and Care

CAUTION:

 MAKE SURE UNIT IS UNPLUGGED BEFORE SERVICING.

NOTE:

 Exact location of components will vary according to the specific unit. 

1. 

Filters (A):

 Dirty filters can reduce 

ventilation efficiency, result in unbalanced 
airflow and damage or shorten the life of 
the motors. Filters are located either on top 
or below the core depending on your exact 
model and remove easily by opening the 
front cover of the unit and sliding out.

 

Polyester Filters:

 Vacuum every three 

months. Replaced every 1-3 years.

 

Option MERV Air Filters:

 If optional air 

filters have been installed, they should be 
replaced every 3 months. When replacing, 
take special note of the airflow direction. 

2. 

Fan (B):

 Wipe all parts with a dry cloth or 

gently vacuum the fan. NEVER IMMERSE ELECTRICAL PARTS IN WATER. No other service 

is required as these fans are designed to operate continuously without lubrication.

3. 

Condensate Drain (C) (HRV UNITS 

ONLY) :

 Twice per year wipe clean 

the condensate drain pan. Check the 

condensate drain and tubing to ensure 

they are free flowing. The tubing must 

have an “S” or loop that traps a quantity 

of water to prevent air from entering the 

unit via this tubing.

4. 

Recovery Core (D):

 The core (located 

behind the cover) should be removed and cleaned at least once a year. Unlatch the latch(es) 

and slide the door to right to release from hinges and clean as follows:

ERV Units:

  Clean by vacuuming at least once a year. 

DO NOT USE SOAP, WATER OR ANY 

CLEANING AGENTS ON THE FIBER-MEDIA CORE.

HRV Units:

  Clean using a mild detergent in cold water at least once a year. Make sure 

the core is completely dry before re-installing into the unit.

 

When re-installing the core make sure the arrow on the core is pointing to the top of the unit.

5. 

Exterior Hoods:

 Regularly check the outside vents and clean any obstructions such as 

grass, leaves or other debris. Do not replace the screen with mesh smaller than 1/4” as 

this will restrict airflow. During winter operation, ensure snow and frost does not build up 

and restrict or block openings.

6. 

Grills & Duct Work:

 Clean the grills when they are dusty or greasy with soap and water. 

Check for punctures in the insulation jacket on the fresh air and exhaust air ducts. Repair 

any punctures using foil tape.

7. 

Annual Servicing:

 Your ERV/HRV should undergo annual general servicing by an 

accredited contractor. This servicing should include the following:

 

a)  The six maintenance items above.

 

b)  A general check for proper operation. Controls and electrical connections should

 

  be inspected.

 

c)  Verification that intake and exhaust air flows are properly balanced.

 

d)  Re-balancing as necessary.

CAUTION:

 ONLY QUALIFIED TECHNICIANS SHOULD SERVICE CONTROLS 

OR INTERNAL COMPONENTS.

www.airkinglimited.com

6728104 Rev. B 5-20

5 of 8

Water

A

B

C

D

B

A

CONDITION

LED AND STATUS

NO LED

UNIT/TRANSFORMER IS NOT POWERED

UNIT OFF

Red is off, Green is blinking slow, every 1 s. Also 

indicates processor is programmed and running.

STANDBY

Green is OFF. Red led is blinking slow, every 1 s.

EXHCHANGE LOW SPEED

Green ON. Red blinking slow, every 1 s.

EXCHANGE HIGH SPEED

Green ON. Red blinking fast.

DEFROST*

Green ON, Red ON.

RECIRCULATION HIGH SPEED* Red led ON, Green led blinking fast.
*Where available

03

60%

Summary of Contents for AKEV Series

Page 1: ...perature falls below 32 F i This unit must be grounded The power cord is equipped with a three prong grounded plug that must be inserted into a matching receptacle Under no circumstances should the gr...

Page 2: ...used to transfer stale air from the wet rooms to the ERV HRV 2 Extended System Continuous Ventilation The furnace fan may not need to run continuously with this system Check local code requirements Fo...

Page 3: ...ITH METHODS OF INSTALLING ELECTRICAL WIRING SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN For simplified return return duct systems it is mandatory that the unit be interlocked with the furnace blowe...

Page 4: ...ed until the humidity level drops below setpoint Available humidity setting range 20 80 In cases where humidity control is not desired or practical use the arrow keys to toggle the humidity setpoint t...

Page 5: ...peed in the ventilator The unit will run in high speed until the ambient air returns to the setpoint RH Your ventilator is not a dehumidifier however ventilating can have a dehumidifying effect by sim...

Page 6: ...re present Install back draft dampers as needed Check defrost system Note minimal frost build up is expected on cores before unit initiates defrost cycle function The supply air feels cool ERV HRV air...

Page 7: ...NTY INCLUDE I INCIDENTAL OR CONSEQUENTIAL DAMAGES FROM ANY CAUSE WHATSOEVER OR II REPLACEMENT OR REPAIR OF ANY HOUSE FUSES CIRCUIT BREAKERS OR RECEPTACLES NOTWITHSTANDING ANYTHING TO THE CONTRARY IN N...

Page 8: ...Latch 5S7759004 8 2 Keeper 5S7759005 9 1 Door Switch 5S7760006 10 1 Core 5S7759006 11 1 Door Assembly 5S7759007 12 1 Fuse Holder 5S7760002 13 1 Fuse 2 5 amp 5S7760003 14 1 Transformer 5S7759001 15 2 C...

Reviews: