background image

operation, testing, maintenance, false

alarms, escape plans and siting.

TESTING AND MAINTENANCE

Regular routine testing and maintenance

is very important and should be

considered at the design stage.

The Code states that the user has a

responsibility for routinely testing the

system and should be supplied with

simple instructions on how to do this.

All smoke alarm systems should be tested

at least weekly using the integral test

button. Remote test and false alarm

control switches can be used to avoid

the need for the user to reach up to the

alarms. Systems should also be checked

if the occupier has been away or the

power has failed.

In Grade D to F applications, smoke

alarms should be cleaned periodically in

accordance with manufacturers’

recommendations. Where experience

shows that excessive levels of dust are

compromising the effectiveness of the

system, more frequent cleaning and

servicing may be required.

NEGLIGENCE

The exact question of negligence and

liability falls outside the scope of the

standard. It is up to the courts to judge

these issues.

From some considered opinion covering

the area of legal liability we quote

below extracts from an article written on

behalf of the National Housing and

Town Planning Council (NHTPC) by

Martin Daley, to whom we are grateful

for granting us permission to quote from

his work.

According to Daley, the NHTPC has

been fortunate in having sight of

independent research on smoke alarm

liability by Dr Anne Everton. The

following ten situations, based on Dr

Everton’s research, should, says Daley,

‘be avoided at all costs’:

1

Where the smoke alarm is defective

in design

17

provisions might have previously

technically precluded the use of wireless

systems and overcomes this by pointing

out that issues relating to power supplies,

fault monitoring and integrity and

performance may not be the same for

hard wired and radio linked systems.

Special recommendations are also

given to their use in HMOs.

WIRING OF MAINS

POWERED SMOKE AND

HEAT ALARMS

When installing, any cable may be

used which is suitable for domestic

mains wiring, provided it is in

accordance with the relevant parts of

BS 7671.

•  There is no requirement for fire

resistant cable and the use of red-

sheathed cable is not required

when installing Grade D, E and F

systems

•  6243Y mains cable is recommended

using the third core for the

interconnect circuit. The earth wire

must not be used for the

interconnect circuit. The maximum

recommended cable run is 250

metres, with 1mm

2

or 1.5mm

2

cable

Amendment No 2 to BS 7671: 2001

allows 'harmonised' cable colours to

be used for installations after 31st

March 2004 (they must be used for

installations commencing after 31st

March 2006). The NICEIC

recommends that 6243Y cable with

the following colours should be used

for smoke alarm systems.

Live - 

Brown

Neutral - 

Grey 

(oversleeve 

blue at terminations)

Interconnect - 

Black

Great care should be exercised in

ensuring correct identification of the

wiring connections as an

interconnected smoke/heat alarm

system will suffer irreparable damage if

the live and neutral connections are

reversed, or if a 240V phase conductor

is connected to the interconnect

terminal.

•  Connect to an independent circuit

at the distribution board if the alarm

does not have a standby supply -

Grade E

•  RCD Protection is generally not

required, but if used it should be

dedicated only to the smoke alarm

circuit or be independent of circuits

supplying sockets or portable

equipment

•  Smoke alarms should not be

installed in new or renovated

buildings until all work is completed

(including floor coverings) and the

building has been fully cleaned,

unless using an Easi-fit style alarm.

Excessive dust and debris from

building work can contaminate the

smoke chambers and cause false

alarms. It will also invalidate the

guarantee. If alarms must be

installed before work is finished,

either use an ‘Easi-fit’ alarm or

ensure that the alarm is completely

covered, particularly around the

edges, with the dust cover that is

supplied with each of our smoke

alarms

Where appropriate, cable penetrations

should be fire-stopped. If there is any

danger of impact damage, abrasion

or rodent attack, appropriate

protection should be fitted.

A convenient and reliable alternative

to hard wired interconnection is now

readily available in the form of

RadioLINK from Aico (see page 22).

CERTIFICATION AND

PAPERWORK

The installer should certify that the

installation conforms to BS 5839: Pt.6 for

the correct Category and Grade of

system. If any variations have been

agreed to, these should be duly noted.

The Code provides a model certificate

for installers to complete.

Suppliers of the equipment should

provide the occupier of the dwelling

with clear and readily understood

information on the system and its use.

All alarms should come complete with

user instructions, designed to be easily

understood, covering such topics as

Summary of Contents for Ei127

Page 1: ...A Guide to Residential Fire Detection With Reference to BS 5839 Pt 6 2004 Ahead on Quality Ahead on Performance Ahead on Features 68 52 X...

Page 2: ...SPECIALIST SUPPLIER Many years of experience in both its professional management and technical sales support teams coupled with a high standard of service and back up have enabled Aico to firmly estab...

Page 3: ...he private or public sector all of whom were required to familiarise themselves with these important recommendations Landlords in particular needed to abide by these recommendations as legal liability...

Page 4: ...t bearing on their performance as borne out by the Fire Statistics A badly installed alarm may have its reaction time cut in half offering occupants as little as 90 seconds or two minutes to get out B...

Page 5: ...ng room CHANGES TO GRADES There is essentially no change to Grade F although a five year minimum battery life is recommended in tenanted properties along with a recommendation that the battery can onl...

Page 6: ...of conducting current e g if the means of interconnection comprises radio communication rather than wiring OTHER ALARM TYPES For the first time BS 5839 Pt 6 now covers CO fire alarms and multi sensor...

Page 7: ...and hostels are not included neither are caravans BS 5839 Pt 6 is primarily concerned with saving lives and reducing injuries However it does contain within it recommendations for helping to reduce pr...

Page 8: ...nt if a fire does break out in that type of room ASSESSING FIRE RISK The Code discusses the generally relevant factors in carrying out a fire risk assessment to determine the most appropriate design o...

Page 9: ...alled within rooms the living room and the dining room should be the first priority However this consideration could be reversed if the bedroom presents a particular fire risk such as the occupant smo...

Page 10: ...o BS 5446 Pt 1 are recommended However these alarms do have serious drawbacks Occupants on a tight budget may not be able to afford to replace the batteries A significant number of tenants have also b...

Page 11: ...the tripping of a protective device or even in some cases by the fire itself Householders may also disable them at the mains all too easily if false alarms are a problem MAINS POWERED SMOKE ALARMS WIT...

Page 12: ...em Within the A F grades defined earlier the Code identifies three different categories of protection LD1 A system installed throughout the dwelling incorporating detectors in all circulation spaces t...

Page 13: ...iteria cannot be met a Grade E or higher system should be installed Existing tenanted dwellings of two or more storeys should have Grade D systems installed From a landlord s point of view the case fo...

Page 14: ...ikely that CO fire alarms have a significant role to play in domestic dwellings at present A Multi sensor alarm is defined in the standard as a fire detector that monitors more than one physical and o...

Page 15: ...ceilings the horizontal distance from any point in the protected area to the detector nearest to that point should not exceed 5 3 metres for heat detectors and 7 5 metres for smoke detectors 15 SITIN...

Page 16: ...ept for a dedicated monitoring device or a separate electrically protected regularly used local lighting circuit A Grade E system may only use the former option Hard wired interconnected smoke alarms...

Page 17: ...re for the interconnect circuit The earth wire must not be used for the interconnect circuit The maximum recommended cable run is 250 metres with 1mm2 or 1 5mm2 cable Amendment No 2 to BS 7671 2001 al...

Page 18: ...on normal smoke fumes or excessive dust Keep the smoke alarm at least 6m away from sources of smoke or vapours that may cause nuisance alarms Do not place Heat Alarms in any of the following areas bat...

Page 19: ...he alarm will not function correctly with the cover in place Alternatively with Easi fit style alarms simply remove the detector head in the advised manner vi Do not paint an alarm or allow paint to c...

Page 20: ...to outlast the life of the alarm Safety The cells have been tested and approved by the British Standards Institute and Underwriters Labs Inc USA for use in this application They have also been compre...

Page 21: ...esigned to outlast the alarm life expectancy of cells endorsed by Panasonic Kitemarked to BS 5446 Pt 2 2003 Ei166 Optical With Hush More responsive to slow smouldering fires Advanced suppression and c...

Page 22: ...Held Same features as the Ei411 but is a key fob size designed for personal use Ei407 Wireless Manual Call Point Allows manual testing of the system Allows manual alarm to warn other occupants Same si...

Page 23: ...acility Alarm clock input Can be used with RadioLINK Ei169 Control box with integral strobe vibrating pad and cable for connections for use with the 150 series alarms not supplied EI169 160 As above f...

Page 24: ...or constant or pulse operation Features rechargeable lithium back up cells with 10 yr life Ideal for signalling to devices not affected by a mains failure such as Warden Call Systems MODIFIRE A Modifi...

Page 25: ...watts and flash frequency of 9Hz Clear or red lens options For operation via an Ei158R or Ei128R relay Suitable for use with Modifire SABV4 High Intensity Strobe Xenon Beacon Mains powered Ideal for u...

Page 26: ...d of mains and battery powered Carbon Monoxide alarms Please contact us for more information SAT332 Smoke Alarm Tester This useful device used in conjunction with an SAA300 aerosol of synthetic smoke...

Page 27: ...r will flash rapidly only on the unit which is the source of the alarm Press hush button if fitted Check for fumes steam etc from the kitchen or bathroom paint and other fumes can cause nuisance alarm...

Page 28: ...tinuous development we reserve the right to amend designs and specifications without prior notice Every care has been taken to ensure that the contents of this document are correct at the time of publ...

Reviews: