Top menu
Pgm No.
Submenu 1
Submenu 2
Default
Setting
Heating circuit 1
700
»
Operating mode
Automatic
Protection
Reduced
Comfort
Automatic
710
»
Comfort setpoint
21°C
712
»
Reduced setpoint
19°C
714
»
Protection setpoint
10°C
720
»
Heating curve slope
0,8
721
»
Heating curve displacement
0°C
726
»
Heating curve adaptation
Off
730
»
Summer/winter heating limit
18°C
740
»
Flow temp setpoint min
8°C
741
»
Flow temp setpoint max
50°C
Heating circuit 2
1000
»
Operating mode
Automatic
Protection
Reduced
Comfort
Automatic
1010
»
Comfort setpoint
21°C
1012
»
Reduced setpoint
19°C
1014
»
Protection setpoint
10°C
1020
»
Heating curve slope
0,8
1021
»
Heating curve displacement
0°C
1026
»
Heating curve adaptation
Off
1030
»
Summer/winter heating limit
18°C
1040
»
Flow temp setpoint min
8°C
1041
»
Flow temp setpoint max
50°C
Heating circuit 3
1300
»
Operating mode
Automatic
Protection
Reduced
Comfort
Automatic
1310
»
Comfort setpoint
21°C
1312
»
Reduced setpoint
19°C
1314
»
Protection setpoint
10°C
1320
»
Heating curve slope
0,8
1321
»
Heating curve displacement
0°C
1326
»
Heating curve adaptation
Off
1330
»
Summer/winter heating limit
18°C
1340
»
Flow temp setpoint min
8°C
1341
»
Flow temp setpoint max
50°C