I-45
A-070336_EN • Rev. A
M
aintenance
Tasks
@ inspection
(1 year)
@ maintenance
(2 years max)
Check that the boiler room ventilation / boiler air and flue
ducts are unobstructed.
X
X
Verify flue gas and combustion air ducts are in good condi-
tion, sealed tight and properly supported.
X
X
Open the front panel and check the general condition inside
the cabinet. Clean and vacuum as required.
X
X
Clean the condensate pipe and trap. Refer to
Condensate Pipe and Trap” on page I-47.
X
X
Clean/service the condensate neutralisation system (if any).
Refer to manufacturer’s documentation.
X
X
Clean any filter/dirt separator, plate heat exchanger or bal-
ance header present in the hydraulic system, as required.
Refer to manufacturer’s documentation.
X
X
Check for leaks, both inside and outside the appliance: wa-
ter, gas, flue and condensate.
X
X
Check boiler water pressure (at least
1.2 bar when cold). Top
up the system with water if required.
X
X
Check the operation of the burner (flame) through the sight
glass and that the combustion parameters (CO & CO
) are
according to requirements. See
X
X
Check the gas pressure and that the gas supply shut-off
devices are operating properly.
X
Check that the pump(s) is/are operating properly.
X
Check that the fan is operating properly.
X
Remove the burner and check its general condition. Clean
as required. See
“Removing and Installing the Burner” on
X
Replace the ignition and ionization electrodes. Refer to
moving and Installing the Ignition and Ionization Elec-
X
Check all control wiring and connections.
X
X
Check the condition of the combustion chamber and clean it
if required. See
“Checking and Cleaning the Combustion
X
Check water quality and record in log sheet, See
Parameters - Log Sheet” on page I-70
X
X
Check the operation of the flue damper (non-return valve),
if any, and perform the required maintenance. Refer to the
manufacturer’s documentation.
X
X
Record the operations and results in the Log Sheets provid-
ed at the end of the manual
X
X
Maintenance Requirements