G-15
A-070336_EN • Rev. A
T
echnical
S
pecificaTionS
Combustion and Gas Data
N 120 FS
(min. - max.)
N 160 FS
(min. - max.)
N 200 FS
(min. - max.)
N 250 FS
(min. - max.)
chimney type(s)
B
23
- B
23P
- C
43
- C
53
- C
83
flue gas temperature at 80/60°C
°C
52 - 60
55 - 61
54 - 62
55 - 61
flue gas temperature at 50/30°C
°C
30 - 34
30 - 34
30 - 34
30 - 35
overheat flue gas temperature
°C
97
max. flue gas pressure
(incl. max wind condition)
Pa
200
mass flow rate of flue gases
g/s
6 - 47
9 - 64
12 - 80
9 - 101
max. condensate volume
kg/h
14.4
18.6
24.0
30.0
CO emissions
mg/kWh
64.5
64.5
64.5
64.5
CO
2
contents*
Min output
%
8.2
Max output
%
9.2
NOx level
mg/kWh
36.6
39.4
38.7
36
NOx class
6
gas type(s)
G20 - G25 - G25.1 - G25.3
gas category
I2E(S) - I2E - I2H - I2L - I2ELL - I2HS - I2N - I2EK
gas pressure
G20 (20 mbar)
mbar
17 - 25
G25 (25 mbar)
mbar
20 - 30
G25.1 (25 mbar)
mbar
18 - 33
G25.3 (25 mbar)
mbar
20 - 30
gas flow rate (G20)**
m
3
/h
1.1 - 10.7
1.6 - 14.3
2.0 - 18.2
1.7 - 21.9
gas flow rate (G25)**
m
3
/h
1.3 - 12.4
1.9 - 16.6
2.3 - 21.2
2.0 - 25.5
*
Tolerance is +/- 0,1%
**
15°C, 1013.25 mbar, dry gas