5  Procedure 

Test procedure (controller must be connected to power supply): 

1 step. 

To  check  the  set  desired  value,  press  the 

“+/-”  key  briefly  once.  The  menu  item  “desired 

temperature

” appears in the display for approx. 5 secs. The set temperature is displayed as a 

hexadecimal  value,  e.

g.  “A1”.  By  pressing  the  “+/-”  key  again,  in  a  “U”-shaped  unit  for 

example you can switch to another set desired value, e.g. 

“A3”. The last hex value shown in 

the display is always considered to be the set desired value. 

2 step. 

Wait until the display again shows the current temperature in the display. 

3 step. 

To  get  into  the  address  menu  of  the  controller,  the 

“standby/reset”  key  should  be  pressed 

briefly once. In the display

, “Adr” is shown alternating, for example, with “1” for bus address 1. 

By  pressing  the  key 

“+/-”  (up)  or  “standby/reset”  (down),  the  bus  address  can  be  adjusted 

between 1 and 247. 

4 step. 

To store the bus address, press the 

“man. defrost” key once to quit the address menu and get 

back to the current temperature. 

5 step. 

To  get  into  the  main  menu,  press  the 

“+/-”  key  three  times  to  get  to  the  code  input  for  the 

main menu. 

“Cod” and “0” are displayed. The correct code should be entered using the key 

“+/-” (up) or “standby/reset” (down). The code can be a number between “-999 and +999”. If 
the  correct  code  is  shown  in  the  display,  this 

should  be  confirmed  using  the  “man.  defrost” 

key in order to get into the main menu. The first enabled menu item is then displayed. 

6 step. 

To change a selected value, the parameter must be confirmed using the 

“man. defrost” key in 

order  get  to  the  parameter  value.  This  should  then  be  changed  using  the  key 

“+/-”  (up)  or 

“standby/reset”  (down).  To  store  the  set  value,  the  “man.  defrost”  key  must  be  pressed. 
Following this you return to the set parameter. 

7 step. 

If you are in the main menu, you can be switched through the parameter level using the key 
“+/-”  (up)  or  “standby/reset”  (down).  If  no  change  occurs  for  approx.  30  seconds,  the 
controller returns from the main menu to the current temperature display. 

8 step. 

Following this the controller will again function normally.

Summary of Contents for Secop GP 105N4627

Page 1: ... Application Is relevant for all divisions which are working with the Secop GP electronic controller 3 Terms 4 Responsibility Contents 5 1 Setups for Cabinets with Plastic Tank 3 5 1 1 Setups for Cabinets with AD Function and with Buzzer 3 5 1 2 Setups for Cabinets with AD Function and without Buzzer 4 5 2 Setups for Cabinets with ALU Tank 10 5 2 1 Setups for Cabinets with AD Function and with Buz...

Page 2: ...bus address can be adjusted between 1 and 247 4 step To store the bus address press the man defrost key once to quit the address menu and get back to the current temperature 5 step To get into the main menu press the key three times to get to the code input for the main menu Cod and 0 are displayed The correct code should be entered using the key up or standby reset down The code can be a number b...

Page 3: ...8 t45 t46 t47 L03 r15 r01 o17 r4 r5 MIAMI 185 ECO L AD VS KSW LIDL A1 with buzzer 221670 A1 16 50 50 A1 on off off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C MIAMI 210 250 ECO AD VS KSW LIDL A1 with buzzer 221671 A1 16 50 50 A1 on off off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 24 50 0 C 16 50 50 A1 on off on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C 5 5 100 A3 on off on off off ...

Page 4: ...P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 40 A1 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 26 40 0 C 16 50 40 A2 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 28 40 0 C Ibiza 100 145 L AD VS A D CH Unilever EU AHT 209962 A1 16 50 40 A1 on off off off off on 8 50 0 3 1 1 1 1 1 1 1 1 1 40 24 40 0 C 16 50 50 A1 on on off ...

Page 5: ...10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 50 A1 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 26 50 0 C 16 50 50 A2 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 28 50 0 C 5 5 100 A3 on on on off off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C Athen ECO 175 210 AD VS KSW D Norma 221361 A1 16 50 50 A1 on off off of...

Page 6: ...5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 9 1 40 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 40 4 40 0 C 16 50 50 A1 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C 16 50 50 A2 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 27 50 0 C 16 50 50 A1 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C 16 50 50 A2 on on on on off on 8 70 0 3 1 1 ...

Page 7: ... 1 1 1 1 1 40 26 40 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 9 1 40 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 40 4 40 0 C 16 50 50 A1 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 26 50 0 C 16 50 50 A2 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 28 50 0 C 16 50 50 A1 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 26 50 0 C 16 50 50 A2 on on...

Page 8: ...7 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 40 A1 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 26 40 0 C 16 50 40 A2 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 28 40 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 9 1 40 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 40 4 40 0 C 16 50 40 A1 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 24 40 0 C 16 50 ...

Page 9: ...inutes day month year Relay 3 configuration s3 S4_S5 weighting for Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 50 A1 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 24 50 0 C ...

Page 10: ...S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A1 on on off off off...

Page 11: ... d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 0 A1 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 9 1 0 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 0 4 0 0 C 16 50 0 A1 on on off off off on 10 40...

Page 12: ... r5 16 50 0 A1 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A2 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 27 0 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 9 1 0 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 0 4 0 0 C 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10...

Page 13: ...set s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 0 A1 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 5 5 100 A3 on on on on of...

Page 14: ...17 r4 r5 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 27 0 0 C 16 50 0 A1 on on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A2 on on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 27 0 0 C 5 5 100 A3 on on on off off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 16 50 0 A1 on on off off off...

Page 15: ...n on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A2 on on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 28 0 0 C 5 5 100 A3 on on on off off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A1 on on on off off on 10 40 10 10 1 1 1 ...

Page 16: ...or Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 ATHEN 175 XL AD VS ALU NORMA 232139 A1 16 50 0 A1 on off off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A1 on off on of...

Page 17: ...nable A5 Allow local display to start defrost Defrost Stop Temperatur Max defrost Time Drain postheating time Drain preheating tmie Number of Defrost day Sunday day Monday day Tuesday day Wednesday day thurstay day Friday day Saturday hour minutes day month year Relay 3 configuration s3 S4_S5 weighting for Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset ...

Page 18: ...ratur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 Athen 207 210 XL S VS 224505 A3 5 5 100 A3 off off on off off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 16 50 0 A1 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 0 24 0 0 C 16 50 0 A2 on on on on off off 8 70 0 3 0 ...

Page 19: ...y day Monday day Tuesday day Wednesday day thurstay day Friday day Saturday hour minutes day month year Relay 3 configuration s3 S4_S5 weighting for Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 ...

Page 20: ...the man defrost key in order get to the parameter value This should then be changed using the key up or standby reset down To store the set value the man defrost key must be pressed Following this you return to the set parameter 4th step To store the bus address press the man defrost key once to quit the address menu and get back to the current temperature 7th step If you are in the main menu you ...

Page 21: ...124 at 5 1 2 page 8 Add new Setup 232139 232252 232264 and 232268 at 5 2 2 page 15 Add new Setup 232266 at 5 2 3 page 16 WI 550 4 22 10 2012 M Horn Add new Setup 232272 at 5 1 2 page 8 Add new Setup 232108 at 5 2 1 page 9 WI 550 5 23 10 2012 M Horn Add new Setup 233463 at 5 1 2 page 8 WI 550 6 29 10 2012 M Horn Change Parameter r01 from 27 to 29 for A1 and from 29 to 31 for A2 and Parameter r4 for...

Reviews: