![AHRI RJNL-B Installation Instructions Manual Download Page 7](http://html1.mh-extra.com/html/ahri/rjnl-b/rjnl-b_installation-instructions-manual_2870559007.webp)
7
GENERAL DATA
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci-
ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with AHRI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet
bulb at AHRI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
Model RJNL-Series
B090CL/C090CL
B090CM/C090CM
B090CN/C090CN
B090DL/C090DL
Cooling Performance
1
Gross Cooling Capacity Btu [kW]
98,000 [28.71]
98,000 [28.71]
98,000 [28.71]
98,000 [28.71]
EER/SEER
2
11.1/NA
11.1/NA
11.1/NA
11.1/NA
Nominal CFM/ARI Rated CFM [L/s]
3000/2925 [1416/1380]
3000/2925 [1416/1380]
3000/2925 [1416/1380]
3000/2925 [1416/1380]
ARI Net Cooling Capacity Btu [kW]
94,000 [27.54]
94,000 [27.54]
94,000 [27.54]
94,000 [27.54]
Net Sensible Capacity Btu [kW]
70,800 [20.74]
70,800 [20.74]
70,800 [20.74]
70,800 [20.74]
Net Latent Capacity Btu [kW]
23,200 [6.8]
23,200 [6.8]
23,200 [6.8]
23,200 [6.8]
IEER
3
11.9
11.9
11.9
11.9
Net System Power kW
8.47
8.47
8.47
8.47
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
87,000 [25.49]
87,000 [25.49]
87,000 [25.49]
87,000 [25.49]
System Power KW / COP
7.5/3.4
7.5/3.4
7.5/3.4
7.5/3.4
Low Temp Btuh [kW] Rating
52,000 [15.24]
52,000 [15.24]
52,000 [15.24]
52,000 [15.24]
System Power KW / COP
6.62/2.3
6.62/2.3
6.62/2.3
6.62/2.3
Compressor
No./Type
1/Scroll
1/Scroll
1/Scroll
1/Scroll
Outdoor Sound Rating (dB)
5
88
88
88
88
Outdoor Coil—Fin Type
Louvered
Louvered
Louvered
Louvered
Tube Type
Rifled
Rifled
Rifled
Rifled
Tube Size in. [mm] OD
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
24.88 [2.31]
24.88 [2.31]
24.88 [2.31]
24.88 [2.31]
Rows / FPI [FPcm]
2 / 22 [9]
2 / 22 [9]
2 / 22 [9]
2 / 22 [9]
Refrigerant Control
TX Valves
TX Valves
TX Valves
TX Valves
Indoor Coil—Fin Type
Louvered
Louvered
Louvered
Louvered
Tube Type
Rifled
Rifled
Rifled
Rifled
Tube Size in. [mm]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
0.375 [9.5]
Face Area sq. ft. [sq. m]
13.5 [1.25]
13.5 [1.25]
13.5 [1.25]
13.5 [1.25]
Rows / FPI [FPcm]
3 / 18 [7]
3 / 18 [7]
3 / 18 [7]
3 / 18 [7]
Refrigerant Control
TX Valves
TX Valves
TX Valves
TX Valves
Drain Connection No./Size in. [mm]
1/1 [25.4]
1/1 [25.4]
1/1 [25.4]
1/1 [25.4]
Outdoor Fan—Type
Propeller
Propeller
Propeller
Propeller
No. Used/Diameter in. [mm]
2/24 [609.6]
2/24 [609.6]
2/24 [609.6]
2/24 [609.6]
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
Direct/1
CFM [L/s]
8000 [3775]
8000 [3775]
8000 [3775]
8000 [3775]
No. Motors/HP
2 at 1/3 HP
2 at 1/3 HP
2 at 1/3 HP
2 at 1/3 HP
Motor RPM
1075
1075
1075
1075
Indoor Fan—Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used/Diameter in. [mm]
1/15x15 [381x381]
1/15x15 [381x381]
1/15x15 [381x381]
1/15x15 [381x381]
Drive Type/No. Speeds
Belt/Variable
Belt/Variable
Belt/Variable
Belt/Variable
No. Motors
1
1
1
1
Motor HP
2
2
3
2
Motor RPM
1725
1725
1725
1725
Motor Frame Size
56
56
56
56
Filter—Type
Disposable
Disposable
Disposable
Disposable
Furnished
Yes
Yes
Yes
Yes
(No.) Size Recommended in. [mm x mm x mm]
(6)2x18x18 [51x457x457]
(6)2x18x18 [51x457x457]
(6)2x18x18 [51x457x457]
(6)2x18x18 [51x457x457]
Refrigerant Charge Oz. [g]
350 [9922]
350 [9922]
350 [9922]
350 [9922]
Weights
Net Weights lbs. [kg]
1009 [458]
1009 [458]
1017 [461]
1009 [458]
Ship Weights lbs. [kg]
1089 [494]
1089 [494]
1097 [498]
1089 [494]
CONTINUED
Summary of Contents for RJNL-B
Page 5: ...5 ST A1132 04 ST A1132 05 FIGURE 3 UNIT DIMENSIONS FIGURE 4 UNIT DIMENSIONS FRONT VIEW ...
Page 6: ...6 ST A1132 06 ST A1132 07 FIGURE 5 BOTTOM VIEW FIGURE 6 REAR VIEW SUPPLY AIR RETURN AIR ...
Page 18: ...18 Model RJNL B090 C090 ...
Page 19: ...19 ...
Page 27: ...27 FIGURE 18 JNL SERIES 7 5 10 TON ...
Page 28: ...28 FIGURE 19 JNL SERIES 7 5 10 TON ...
Page 29: ...29 FIGURE 20 JNL SERIES 7 5 10 TON ...