Exiting Lock-Out Mode:
To exit the lock-out mode, remove
24 volts to the defrost control by removing power to the unit
or by shorting the two defrost control test pins together.
ENHANCED FEATURE DEFROST CONTROL DIAGNOSTIC
CODES
REPLACEMENT PARTS
Contact your local distributor for a complete parts list.
CHARGE INFORMATION
Refer to the appropriate charge chart on the unit, or in this
booklet.
TROUBLESHOOTING
Refer to the troubleshooting chart included in this manual.
WIRING DIAGRAMS
Refer to the appropriate wiring diagram included in this manual.
LED 1
LED 2
Control Board Status
OFF
OFF
No Power
ON
ON
Coil Sensor Failure
OFF
ON
Ambient Sensor Failure
FLASH
FLASH
Normal
OFF
FLASH
Low Pressure Lockout (short test pins to reset)
FLASH
OFF
High Pressure Lockout (short test pins to reset)
ON
FLASH
Low Pressure Control Open
FLASH
ON
High Pressure Control Open
Alternate Flashing
5 Minute Time Delay