Mounting
AGD155 Product Manual Rev.2.2
Page 14
3.2.2 Mounting Multiple Power Amplifiers
When mounting multiple amplifiers within a cabinet, clearance between units must be at least
10 mm. In addition, top and bottom clearance must be at least 50 mm.
Ambient temperature in the cabinet must not exceed the limit defined in section Safe Operating Area
(SOA).
If amplifiers are mounted on a backplane, the backplane temperature must not exceed the limit
defined section Safe Operating Area (SOA).
It is recommended to install a cooling fan at the bottom of the cabinet for best circulation.
Figure 4. Mounting multiple amplifiers within cabinet