AFi MT-915D Instruction Manual Download Page 5

 

5

CHANNEL BIAS / TERMINATION SWITCHES 

Switches are available internally that allow offset bias and termination features to be activated when 
using RS485 data. These switches also allow termination features to be activated when using RS422 
data. In order to reconfigure the RS485/422 channel, the module needs to be opened up. To open the 
MT-915D, remove the end panel on the terminal block side and remove the screw on the bottom of the 
module. Slide the PCB assembly out about half way. The configuration switch bank is located at the 
lower right corner of PCB next to the data terminals (See drawing below). 
The MT-915D is shipped with these switches in the off 
(down) position. When transmitting RS232 or 
Manchester data, the bias and termination switches 
must remain in the off (down) position. The S1 
switches correspond to channel 1. The chart below 
describes the layout of the S1 switch bank.  
 

 

 
 
 
 
 
 
 
 
 
Please remember when using offset bias switches 
that they must be used in pairs. If switch # 1 is up then 
switch # 3 must also be up. The same situation 
applies for switch # 4 and switch # 6. Also, if using 
offset bias, it is important that the corresponding termination resistor switch be in the on (up) position. 
Using offset bias without a termination on the line will cause communications to fail. An explanation 
follows on general bias and termination guidelines. 

 
RS485 DATA TERMINATION 

The RS485 protocol is an expanded version of the original RS422 protocol. RS485 differs from RS422 
in the ability of the transmitter devices to go into a high impedance (Hi-Z) state. This allows multiple 
transmitter devices to reside on the same wire pair. The software must dictate a protocol that allows 
only one device to transmit at any one time to prevent data crashes. In many cases the system head 
end controller will continuously poll data from all remote devices. The remote devices all respond back 
to the head end (one at a time) as they are addressed. The driver chips that are used in RS485 
communications are capable of changing into their high impedance state very rapidly. On even short 
lengths of wire there can exist a residual voltage after a driver circuit turns off. This can interfere with 
circuits that are used to detect the Hi-Z state. It is very important that the copper communications lines 
be terminated with resistors across the data wire pair. The best place to locate such resistors is at the 
furthest electrical devices at the ends of the wire pair. For instance, if several RS485 devices are 
connected in a daisy chain fashion, the wire connection would loop across all devices in a chain. The 
furthest two points in the chain would need to be terminated. 

 
OFFSET BIAS – RS485 

The RS485 specification requires receivers to detect input signals down to 200mVp-p of voltage level. 
In many cases this can cause systems to be sensitive to noise on the data wires. In an effort to 
eliminate the effects of low levels of noise, some manufacturers of equipment that communicate using 
RS485 have introduced a small voltage bias to the data lines. This is usually accomplished using a 470 
Ohm resistance to +5V on the positive line and 470 Ohm resistance to ground on the negative line. 
When used in conjunction with the appropriate termination resistors referred to in the previous section, 
this introduces about a 300 mV offset, improving noise immunity. 

Summary of Contents for MT-915D

Page 1: ...Copyright 2005 American Fibertek Inc 1109JD Instruction Manual MT 915D Video Transmitter With Bi directional Multi Protocol Data Bi directional Contact Closure And Remote Diagnostic Interface...

Page 2: ...i directional data over one multimode fiber optic cable The MT 915D multiplexes a single video input signal along with up to two data signals into a high speed serial data stream This serial data stre...

Page 3: ...SUPPLY ONLY This unit requires a 12VDC power source with a current rating of 1 25 amps for proper operation The DC input is diode protected In the USA and in Canada an American Fibertek PS 12D is supp...

Page 4: ...ignals Using this terminology the driver of an electronic signal is labeled TX or Data Out Correspondingly the receiver of an electronic signal is labeled RX or Data In Following this standard the Dat...

Page 5: ...transmitter devices to reside on the same wire pair The software must dictate a protocol that allows only one device to transmit at any one time to prevent data crashes In many cases the system head...

Page 6: ...Data Flow Not Detected DATA 1 RX A green LED indicator is provided to monitor the data coming in from the fiber through the MT 915D and out onto the electrical interface The intensity of this indicat...

Page 7: ...n Proper Optical Input Power Present Red On Optical Input Not Detected Off Off Check Power Supply SYNC A bi color LED indicator is provided to monitor the proper serialization of the electrical data s...

Page 8: ...THE FOREGOING WARRANTY THERE IS NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE EXPRESSED OR IMPLIED WHICH EXTENDS BEYOND THE WARRANTY SET FORTH IN THIS AGREEMENT In a...

Reviews: