(European) Extinguishing systems with the AF-X Fireblocker Carbon Series can be designed using one of the
following control panels:
1.
Kentec Sigma XT or A-XT panel
2.
Honeywell Notifier RP1r-SURPA
3.
Siemens Cerberus, for systems with more than 10 extinguishing generators
4.
AF-X Marine Panel for shipping
5.
DECU2
6.
AF-X TEC
All these control panels have their own prices and possibilities. If the usage of other brands or types of control
panels is considered it is required to contact the technical department of AF-X Systems first for an opinion and
approval regarding compatibility. Also, if a certifying authority requires the usage of a specific panel.
For proper installation of the panel of your choice, we expressly refer you to the manufacturer’s installation
requirements.
For installations designed for countries where European Rules & Regulations do not apply, we advise to consult the
technical department of AF-X Systems first for proper advice regarding this matter.
5.2 AF-X MCU (monitoring & control unit)
The AF-X MCU provides connection from the Kentec XT, AX-T or the Honeywell Notifier RP1r-SURPA fire control
panel to the AF-X Fireblocker Carbon Series generators.
•
A maximum of 18 AF-X MCU’s can be connected to each extinguishing line,
•
A maximum of 2 generators on each MCU.
Connection diagram Notifier RP1r-SURPA:
Connection diagram Kentec Sigma XT or A-XT panel: