User Manual AF-X Firestopper November 2015 version 1 

 

 
 

 

 
 

 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 
 

 
Installation and User Manual  
AF-X Fireblocker Carbon Series 

 
 

Original issue date:    July 2018 
 
Revision date:  

07-12-2019 

 

Version: 

   

2.3 

 

 

 

Summary of Contents for Carbon BL

Page 1: ...1 User Manual AF X Firestopper November 2015 version 1 Installation and User Manual AF X Fireblocker Carbon Series Original issue date July 2018 Revision date 07 12 2019 Version 2 3 ...

Page 2: ... mail info af x com Lay out In accordance with NEN 5509 This manual is the manufacturer s design installation operating and maintenance instruction manual for detailed instructions for correct usage and maintenance Please read this user manual carefully before installing AF X Fireblocker Carbon Based Fire Extinguishers AF X Systems BV general terms and conditions can be retrieved at the Chamber of...

Page 3: ...ing generators 11 5 5 AF X Fireblocker Carbon Series aerosol behaviour 11 5 6 Calculation of quantity and type 11 5 7 Projection of the generators within the area 11 5 8 Guidelines for the correct positioning and distribution in the area 11 5 9 Determination of the correct discharge direction 12 5 10 Mounting guidelines AF X Fireblocker Carbon generators 14 6 0 Product Label 16 7 0 Storage and tra...

Page 4: ...Manual AF X Fireblocker Carbon Based Fire Extinguishers version 2 2 4 Signs to indicate prohibitions mandatory actions and cautions used in this manual PROHIBITION MANDATORY ACTION Beware No switching off No switching on Foot protection MANDATORY ACTION Attention important Eye protection Head protection Hand protection Unplug disconnect CAUTION Fragile Fall danger Hot surface Damage ...

Page 5: ...ations When this document went to print the editions mentioned were in force All norms can be subject to revision however parties entering into agreements based on this document are therefore recommended to ascertain that they are using these norms latest versions The AF X Fireblocker Carbon Series has been designed developed and built in accordance with the guidelines of the following norms stand...

Page 6: ...efore not included in this user manual In case of incorrect use of this manual neither AF X Systems BV nor the AF X Fireblocker Carbon Series distributor or dealer can assume any responsibility 2 0 Scope AF X Fireblocker Carbon Series is based on a condensed aerosol and designed to be part of a fire extinguishing system Precondition for powerful performance is the unit s connection to and activati...

Page 7: ... the extinguishing agent and convert it into dispersed micro and nano particles The aerosol is then cooled by the heat absorbing elements and discharged into the protected area blocking the fire by stopping the combustion chain reaction Activation simultaneously triggers other chemical reactions ensuring a final product that is harmless to man matter and the environment All generators of the Carbo...

Page 8: ...re 7 Open nozzle for optimal mixture with air in the protected space 4 0 Precautions and safety instructions Read this user manual carefully before putting the AF X Fireblocker Carbon Series into use This user manual contains precaution and safety instructions to ensure a safe execution of the necessary steps The term steps may refer to all actions in the various product phases transport receipt s...

Page 9: ...ch that activates at 65 ºC see annex 2 The self activation temperature of the compound is 350 ºC The self activation time of the electronically controlled activation device is 170 ºC Please note that equipment used for heating or welding and other sources of energy might provoke activation of the fire extinguishing generator if the self activation temperature is reached The standard requirements f...

Page 10: ... it is required to contact the technical department of AF X Systems first for an opinion and approval regarding compatibility Also if a certifying authority requires the usage of a specific panel For proper installation of the panel of your choice we expressly refer you to the manufacturer s installation requirements For installations designed for countries where European Rules Regulations do not ...

Page 11: ... and whirls present in the area either caused by fire or just by the active equipment make the tiny aerosol particles actively move through the protected space The AF X Fireblocker aerosol of the Carbon Series has been designed to make use of these currents and movements so that the convection currents caused by the seat of the fire draw the particles into that seat Even when the fire is just in i...

Page 12: ...dly and evenly After all every nook and cranny need to be filled with sufficient aerosol When in doubt do not hesitate to contact the AF X Systems experts 5 9 Determination of the correct discharge direction There are always several solutions The challenge is to come up with the optimal mix of choices in type position and discharge direction and length that makes maximum use of AF X Fireblocker s ...

Page 13: ...AF X Fireblocker Carbon Based Fire Extinguishers version 2 2 13 Away from windows or other potential openings 6 In an area with a height of less than 1m generators should preferably discharge horizontally Horizontal discharge in areas lower than 1m 7 In an area higher than 1m generators should preferably discharge downwards at an angle cf drawing Downward discharge in areas higher than 1m ...

Page 14: ...blocker generators should be mounted in static environments a Please study the entire systems projection plan carefully before mounting any generator b Systems with a fire extinguishing control panel should at all times contain a maintenance switch separating the extinguishing units from the control panel during installation as well future maintenance activities c For the installation of cables us...

Page 15: ...h a protection cover on the nozzle After unpacking remove the protection cover j Check whether the electric circuit of the AF X Fireblocker generators is intact with an ohmmeter with an accuracy of at least 2 5 The resistance must be between 6 1 and 7 5 Ohm The test current should not exceed 20 mA for a maximum of 300 seconds k Attach the AF X Fireblocker firmly to the mounting brackets with the c...

Page 16: ... containing the following information Details of the fabrication location Serial number Month year of production 7 0 Storage and transport During transport and storage the AF X Fireblocker Carbon Series needs to be put up and protected against dirt moisture and precipitation The AF X Fireblocker Carbon Series needs to be stored in its original packaging in racks in warehouses either heated or unhe...

Page 17: ...vation the SAFCO converts into rapidly dispersing aerosols consisting of solid micro particles suspended in gas The concentration of solid particles suspended in the aerosol phase is a few milligrams per m The particles are water and moisture free and after passing the hold time settle as dust in the protected area The dust should be removed before it absorbs moisture Thorough cleaning by removing...

Page 18: ... surpassed its operational life span a Before any other activity assure that the maintenance switch is switched to off Note the red LED on the maintenance switch is ON if the system is off line b Disconnect the power supply cable from the unit c Short circuit the unit by connecting entrance 1 with entrance 2 in the connector d Gently remove the Fireblocker out of its mounting bracket and place it ...

Page 19: ...mpère within x minutes Gross weight in kilograms 2 7 4 0 14 2 18 7 29 4 Casing Steel Steel Steel Steel Steel Shape Cylinder Cylinder Square Square Square Dimensions in mm 94 x310 94 x450 250x250x213 250x250x304 250x250x457 Outflow time in seconds 60s 60s 120s 120s 120s Outflow Length in meters projection 3m 5m 4m 6m 8m Discharge openings 1 1 1 1 1 Minimum installation height 25cm 25cm 50cm 50cm 50...

Page 20: ...0 Annex 2 General technical data Bimetal Switch ÜËÝáÏÑ ÝÞÏÜÎË ÒÏ ÏÞÒÏÜÖËØÎÝ Р ÓØÐÙ ËÐ â ÍÙ ááá ËÐ â ÍÙ 1 5 7 1 1 250 7 21 1RUPDOO RSHQ VZLWFK YHUVLRQ VZLWFKLQJ FXUUHQW QXPEHU RI FLUFXLWV PD LPXP VZLWFKLQJ FXUUHQW QXPEHU RI FLUFXLWV PD SRZHU DFWLYDWLRQ WHPSUDWXUH HUWLILHG 8 8 77 5 WHFKQRORJ W SH GLPHQVLRQV QRPLQDO FDSDFLW VWDQGDUG GLVFKDUJH FXUUHQW QRPLQDO YROWDJH PD SXOVH FXUUHQW RSHUDWLQJ WHPSHUD...

Page 21: ...rements for compiling a safety data sheet 0 2 1 The safety data sheet shall enable users to take the necessary measures relating to protection of human health and safety at the workplace and protection of the environment The writer of the safety data sheet shall consider that a safety data sheet must inform its audience of the hazards of a substance or a mixture and provide information on the safe...

Page 22: ...xtinguisher unit 1 2 Relevant identified uses of the substance or mixture and uses advised against Main use category Industrial use professional use Consumer use Use of substance mixture Fire Extinguisher Remark relevant uses Dry Fire Extinguisher suitable for confined area s e g engine rooms technical areas server rooms for computers cargo compartments vehicles storage facilities etc 1 3 Details ...

Page 23: ...plicable as Extinguishing Unit is not to be regarded to be a substance or mixture 2 3 Other hazards Extinguishing Agent The mixture does not meet the criteria for PBT or vPvB according to REACH No 1907 2006 Annex XIII Harmful in contact with skin and if swallowed irritating to skin and eyes Note This substance mixture contains no components considered to be either persistent bio accumulative and t...

Page 24: ... move person into fresh air and keep at rest in a position comfortable for breathing or if available provide medical oxygen If not breathing give artificial respiration and seek medical attention immediately Consult a physician First aid measures after skin contact If skin contact wash off with soap and plenty of water for at least 15 minutes Cold water may be used If irritation persists consult a...

Page 25: ... extinguishing agent Flame point material around 350 ºC Explosion hazard No direct explosion hazard in vicinity of product in powder and tablet form Flame point material around 350 ºC Hazard due to combustion products after initiation Combustion products CO2 N2 H2O gas phase 88 wt K2CO3 solid phase 12 wt 5 3 Advice for firefighters Precautionary measures Exposure to fire heat keep upwind consider ...

Page 26: ...r non emergency personnel 6 2 Environmental precautions Prevent contamination in sewers Prevent uncontrolled discharges into the environment rivers water courses sewers etc Prevent soil and water pollution Stop leaks if possible 6 3 Methods and material for containment and clean up For containment Minimize generation of dust Stop leaks if safe to do so Methods for cleaning up First ensure that the...

Page 27: ...ot eat drink or smoke when using this product Wash contaminated clothing before reuse 7 2 Conditions for safe storage including any incompatibilities Technical measures Store in a dry and cool well ventilated place away from sources of heat ignition and direct sunlight Storage conditions Store in a dry preferably in the original storage transport packaging Substance is hygroscopic Storage temperat...

Page 28: ...safety showers are close to the workstation Handle in accordance with good industrial hygiene and safety practice Wash hands before breaks and at the end of workday Personal protective equipment Hand protection In case of repeated or prolonged contact wear gloves tested to EN 374 Take advice to gloves supplier The selected protective gloves have to satisfy the specifications of EU Directive 89 686...

Page 29: ...s modifications will be necessary to reduce emissions to acceptable levels Other information Keep product away from foodstuffs and beverages Do not eat drink or smoke when using this product Take off contaminated clothing and shoes immediately After use wash hands and apply hand or skin care cream Training staff on good practice Regular cleaning of equipment Minimization of manual phases SECTION 9...

Page 30: ...tions to avoid Avoid high temperatures Prevent moisture contact Also avoid direct sunlight sources of heat incompatible materials open flame and sparks 10 5 Incompatible materials Keep substance away from strong acids strong bases and oxidation agents combustible materials reducing agents organic materials 10 6 Hazardous decomposition products Mainly Nitrogen oxides and oxygen could be released On...

Page 31: ...cal physical and toxicological properties have not been thoroughly investigated Liver Irregularities Based on Human Evidence Symptoms injuries after inhalation AFTER INHALATION OF DUST Dry sore throat Coughing Irritation of the respiratory tract Symptoms injuries after skin contact Red skin ON CONTINUOUS EXPOSURE CONTACT Tingling irritation of the skin Symptoms injuries after eye contact Redness o...

Page 32: ...icable 12 3 Bio accumulative potential Potassium Nitrate 70 of mixture Potassium nitrate CAS no 7757 79 1 Bio accumulative potential No bioaccumulation or biomagnifications are expected based on substance properties Log Pow 1 12 4 Mobility in soil Potassium Nitrate 70 of mixture Potassium nitrate CAS no 7757 79 1 Ecology soil Soluble in water Low potential for adsorption based on substance propert...

Page 33: ...hipping name Proper Shipping Name Not applicable the product does not meet the UN Criteria to be classified and identified 14 3 Transport hazard class Class UN Not applicable Hazard labels UN Not applicable 14 4 Packing group Packing group UN Not applicable 14 5 Environmental hazards Other information No supplementary information available 14 6 Special precautions for user 14 6 1 Overland transpor...

Page 34: ...tance SECTION 16 OTHER INFORMATION Version 1 0 USDS 261018 Abbreviations and acronyms bw body weight CLP Classification labeling and packaging DNEL Derivative No Effect Level PNEC Predicted No Effect Concentration REACH Registration evaluation and authorization of chemicals NOAEL no observed adverse effect level OECD Organization for Economic Cooperation and Development SCL Specific concentration ...

Page 35: ...Amsterdam The Netherlands This Safety Data Sheet is prepared by AF X Systems BV in close cooperation and based on the data as supplied by Aerosol Extinguishing Technologies BV Amsterdam Aerosol Extinguishing Technologies BV produces this fire extinguishing gas generators exclusively for AF X Systems BV Prepared by AF X Systems BV Email ralph af x com gilbert i4safety nl Creation Date 26 October 20...