background image

- 17 -

7. SYSTEM PROTECTIONS/ ERROR CODES

When an error occurs or the protection mode is set automatically, the wired controller will display an 
error code as below. 

Code 

Failure 

Possible reasons 

Remedy 

Er01 

Phase dislocation 

Wrong connection of live wires 

1) Reverse  position  of  2  live

wires(3-Phase units only).

Er02 

Phase loss 

Live wires loose or without power 

1) Check  if  live  wires  loose  or

without power
(3-Phase units only).

Er03 

Water flow switch failure 

1) Inadequate water flow

2) Water flow switch damaged

3) Main PCB damaged

1) Check the pump

2) Replace  the  water  flow

switch

3) Replace the PCB

Er04 

Anti-freeze protection in winter 

This function occurs when 
ambient temp is too low. 

No action needed 

Er05 

High pressure protection 

1) Inadequate flow rate

2) Uncompressed

gas 

in 

refrigerant system

3) Overcharge with refrigerant

4) Water temp setting too high

5) Poor  connection  of  pressure

switch

6) Pressure switch failure

7) Main PCB damaged

1) Check  pump  and  water

control valve

2) Discharge 

and

then 

recharge the refrigerant

3) Discharge some refrigerant

4) Set lower water temp

5) Reconnect the switch

6) Replace

the 

pressure 

switch

7) Replace the PCB

Er06 

Low pressure protection 

1) Undercharged refrigerant

2) Capillary block

3) Poor  connection  of  pressure

switch

4) Pressure switch failure

5) Main PCB damaged

1) Add some refrigerant

2) Replace the capillary

3) Reconnect the switch

4) Replace

the 

pressure 

switch

5) Replace the PCB

Er09 

Communication failure 

The control pad and PCB 
connection failure 

Check the wire connection 

Er12 

Over-high compressor exhaust gas 
temp protection 

1) Refrigerant Undercharged

2) Possible reasons as Er05

1) Add some refrigerant

2) Similar corrections as Er05

Er15 

Inlet 

water temp sensor failure 

1) Sensor open circuit

2) Sensor short circuit

3) Main PCB damaged

1) Check

the 

sensor 

connection

2) Replace the sensor

3) Replace the main PCB

--

Automated Environmental Systems Ltd., Unit 1, 1 Wimbledon Avenue, Brandon, Suffolk IP27 0NZ

01842 819130 | [email protected] 

Summary of Contents for Remora Mini

Page 1: ...POOL HEAT PUMP MANUAL Remora Mini Swimming Pool Heat Pump 1 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co u...

Page 2: ...12 6 4 Parameter checking and adjustment 15 7 SYSTEM PROTECTIONS ERROR CODES 17 8 MAINTENANCE AND INSPECTION 19 9 WIRING DIAGRAM ELECTRICAL CONNECTION 25 9 1 Wiring diagram 25 9 2 Electrical connecti...

Page 3: ...manual Use genuine standard spare parts only Failure to comply with these recommendations will invalidate the warranty Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperat...

Page 4: ...ance shall be installed in accordance with national wiring regulations Before obtaining access to terminals all supply circuits must be disconnected Spaces where refrigerant pipes shall be compliance...

Page 5: ...r the use of harmful substances in electric and electronic devices 4 The unit CANNOT be installed near the flammable gas Once there is any leakage of the gas fire can occur 5 Make sure that there is c...

Page 6: ...s are found inside the box Carton Box Item Image Quantity Swimming pool heat pump 1 Operation and Installation Manual 1 Winter Cover 1 Accessories 1 Set Automated Environmental Systems Ltd Unit 1 1 Wi...

Page 7: ...emora m3 Remora m5 Remora m7 A 647mm B 480mm C 98mm D 257mm E 530mm F 506mm G 180mm H 102mm Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales au...

Page 8: ...14 Wired controller 5 Fan blade 15 Electrical control box 6 Fan motor 16 Compressor 7 Evaporator 17 4 way valve 8 Titanium heat exchanger 9 Liquid separator Not available for mini units 10 EEV Not ava...

Page 9: ...The controller could be mounted on the wall 5 2 Swimming Pool Heat Pumps Location The unit will perform well in any outdoor location provided that the following three factors are presented 1 Fresh Air...

Page 10: ...can be run straight into the unit Location Connect the unit in the pool pump discharge return line downstream of all filter and pool pumps and upstream of any chlorinators ozonators or chemical pumps...

Page 11: ...y to or from the pool water Grounding the unit is still required to protect you against short circuits inside the unit 5 6 Initial startup of the Unit NOTE In order for the unit to heat the pool or sp...

Page 12: ...DIGITAL CONTROLLER GET WET THIS MAY CAUSE AN ELECTRIC SHOCK OR FIRE NEVER PRESS THE BUTTONS OF THE DIGITAL CONTROLLER WITH A HARD POINTED OBJECT THIS MAY DAMAGE THE DIGITAL CONTROLLER NEVER INSPECT OR...

Page 13: ...s press and to set temperature in current mode Timer button Press this button to enter into Timer ON OFF setting mode combing with and buttons to set 2 groups of Timer ON OFF Hold for 5 seconds to acc...

Page 14: ...setting Timer 1 ON minute digit press again to enter into Timer 1 OFF hour digit the setting way is same as above When finish setting Timer OFF time press again to confirm current Timer settings and e...

Page 15: ...it turns off to cancel defrost Remove error history record On error history query interface screen press and for 5 seconds to remove error history records Reset Under unit OFF status press and for 5 s...

Page 16: ...of the compressor 10 15 Heat 10 25 Cool A3 Compressor exhaust gas temp Refrigerant gas temperature at the outlet of the compressor 40 80 Heat 60 95 Cool A4 Ambientairtemp Surrounding ambient air temp...

Page 17: ...to set water temperature 28 in heat mode for instance If this parameter is set to 2 heat pump won t restart until water temperature drops to 26 1 5 2 L3 Heat Mode Water Temp Set Set target water temp...

Page 18: ...re switch failure 7 Main PCB damaged 1 Check pump and water control valve 2 Discharge and then recharge the refrigerant 3 Discharge some refrigerant 4 Set lower water temp 5 Reconnect the switch 6 Rep...

Page 19: ...ce the sensor 3 Replace the main PCB Er29 Compressor suction gas temp sensor failure 1 Sensor open circuit 2 Sensor short circuit 3 Main PCB damaged 1 Check the sensor connection 2 Replace the sensor...

Page 20: ...mable refrigerants safety checks are necessary to ensure that the risk of ignition is minimised Work procedure Work shall be undertaken under a controlled procedure so as to minimise the risk of a fla...

Page 21: ...all be followed If in doubt please consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants a The charge size...

Page 22: ...ly Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with...

Page 23: ...itrogen OFN shall then be purged through the system both before and during the brazing process Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpos...

Page 24: ...t release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not...

Page 25: ...ess it has been cleaned and checked Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of different refrigerants...

Page 26: ...iring diagram Please refer to the wiring diagram on the electric box Models Remora m3 Remora m5 Remora m7 Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 8...

Page 27: ...26 9 2 Electrical connection Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Page 28: ...e power and installation requirements Please refer to table below Heat Pump Model Cable Size Remora m3 Remora m5 Remora m7 3 x 1 5mm2 The above are for references only Please refer to qualified electr...

Page 29: ...28 NOTES Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Page 30: ...29 NOTES Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Page 31: ...30 NOTES Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk...

Reviews: