7-TECHNICAL DATA(EC motors)
7.1-Cassette with 3 rows coil
2 PIPES
4 PIPES
133
163
135
165
Speed
(E)
4V
7V
10V
4V
7V
10V
4V
7V
10V
4V
7V
10V
Airflow
mc/h
410
760
1120
570
1050 1520
410
760
1120
570
1050 1520
COOLING
– Air 27°C d.b. , 19°C w.b.. – inlet water temperature 7°C , output water temperature 12°C
Total capacity
(E)
kW
3,11
5,28
7,35
4,17
6,96
9,42
2,61
4,56
6,13
3,58
5,83
7,66
Sens.capacity
(E)
kW
2,19
3,85
5,22
2,99
4,95
6,60
1,98
3,25
4,29
2,61
4,09
5,35
Water flow
l/h
534
905
1260
716
1195 1616
448
783
1052
614
1001
1315
Δp water
(E)
kPa
2,1
5,3
9,4
3,5
8,6
14,8
2,2
6,0
10,1
3,9
9,3
15,3
HEATING
– Air 20°C – inlet water temperature 50°C , same for cooling flow
Capacity
(E)
kW
3,60
6,24
8,57
4,87
8,12 10,95
-
-
-
-
-
-
Water flow
l/h
534
905
1260
716
1195 1616
-
-
-
-
-
-
Δp water
(E)
kPa
1,8
4,9
9,0
3,3
8,2
14,2
-
-
-
-
-
-
HEATING
– Air 20°C - inlet water temperature 70°C , output water temperature 60°C
Capacity
(E)
kW
-
-
-
-
-
-
4,16
6,47
8,29
5,32
7,96
10,16
Water flow
l/h
-
-
-
-
-
-
377
586
751
481
721
919
Δp water
(E)
kPa
-
-
-
-
-
-
2,2
5,1
8,1
3,5
7,4
11,7
ELECTRIC MOTOR ABSORTION
Consumption
(E)
W
6
18
42
10
36
97
6
18
42
10
36
97
Max absorption
A
0,34
0,76
0,34
0,76
DATI SONORI
Sound power
(E)
dB(A)
34
48
59
41
57
66
34
48
59
41
57
66
Sound pressure
dB(A)
25
39
50
32
48
57
25
39
50
32
48
57
ENERGY SAVING CLASS
FCEER
(E)
A
A
A
A
FCCOP
(E)
A
A
A
A
(E)
= EUROVENT certificated data