11.3- Condensate drain pump Auxiliary (PSCC-BI)
The supplementary condensate drain pump is supplied assembled outside of the box, at the side of the
drainage pipe. Then must provide for the possibility of inspection also on this side.
Maximum water flow
20 l/h
Maximum discharge height
10m (4l/h)
Sound pressure 1m
28dB(A)
Supply
230V
– 50/60Hz
Micro switch alarm
NC 8° resistivi 250V
Thermal Protection
90°C (riarmo automatico)
Protection
IP54
11.4- Speed motor control board SC3
The 3-speed motor board allows you to control the EC motor with a traditional thermostat 3-speed or with a
thermostat with 0-10V signal. With this accessory, it is also possible to control more than one unit with a
single thermostat (not addressable master-slave).
For each double cassette, you need two cards SC3 (to be considered as a slave of the other).
CONTROL FROM EXTERNAL THERMOSTAT
VH
Contact on-off valve heating (4 tubes)
VC
Contact on-off valve cooling (2-4 tubes)
MIN
Minimum fan speed
MED
Minimum fan speed
MAX
Maximum speed fan
GND
Reference signal 0-10V
0-10V
0-10V signal for motor control