Aerovent IM-895 Installation, Operation & Maintenance Manual Download Page 16

Installation, Operation & Maintenance Manual

IM-895

16

Troubleshooting Guidelines

 (cont.)

PROBLEM

POSSIBLE CAUSE

POSSIBLE REMEDY

D. Burner Not

Operating

1. See Problems "A" thru "C".

1. See Problems "A" and "C"

2. Damper end switch not functioning

2. Check and/or replace

3. Failed air flow switch

3. Check and/or replace

4. Loose wiring connection at air proving

4. Check and tighten

5. No pilot

5. See Problem "F"

6. Flame safeguard in lockout mode

6. Check and reset

7. High limit tripped

7. Check and/or replace

8. Too high or low gas pressure

8. Check pressure switches and gas pressure

9. Failed control transformer

9. Check and/or replace

10. Blown control transformer fuse

10. Check and/or replace

11. Failed or malfunctioning main gas valve(s)

11. Check and/or replace

12. Faulty or failed freeze stat or inlet on/off stat

12. Check and/or replace

13. Failed safeguard control

13. See vendors instructions shipped with unit

14. Airflow too low, low airflow proving switch is 

open

14. Check for reason of insufficient airflow and 

correct

15. Airflow too high, high airflow cutoff switch is 

open

15. Check for reason of excessive airflow and 

correct

E. Flame Will Not 

Prove

1. Inadequate signal to safeguard control

1. Check micro-Amps or Vdc from flame sensor

2. Insufficient gas pressure to pilot

2. Check and adjust

3. Loose wires from flame sensor

3. Check and correct

4. Dirty flame rod

4. Clean and/or replace

5. Moisture on flame rod leads

5. Check and dry leads. Use di-electric grease inside 

boot

6. Defective flame rod

6. Check and/or replace

7. Defective flame safeguard controller

7. Check and/or replace

8. Short in flame sensor leads

8. Check and/or replace

9. Excessive air velocity across burner

9. Check burner velocity and correct

F. Erratic 

Temperature

1. Defective temperature selector or sensor

1. Check and/or replace

2. Temperature sensor subject to poor air flow or 

located in drafty area

2. Check sensor location and move if required

3. Discharge sensor blocked by duct insulation

3. Check and remove blockage

4. Faulty amplifier or modulating valve

4. Check and/or replace

G. Unable to 

Achieve High Fire

1. Low gas supply pressure

1. Check and adjust

2. Modulating controls improperly set

2. See vendor literature shipped with unit

3. Faulty temperature sensor

3. Check and/or replace

4. Faulty amplifier or modulating valve

4. Check and/or replace

H. Unable to 

Achieve Low Fire

1. Modulating controls improperly set

1. See vendor literature shipped with unit

2. Faulty temperature sensor

2. Check and/or replace

3. Faulty amplifier or modulating valve

3. Check and/or replace

I. No Gas Flow

1. Manual gas valve(s) closed

1. Open manual gas valve(s)

2. See Problem "D", Items 2 thru 13

2. See Problem "D", Items 2 thru 13

J. Unable to 

Achieve Desired 

Discharge 

Temperature or 

Space Temperature

1. Temperature sensors improperly set or faulty

1. Adjust or replace

2. Improper gas supply pressure

2. Check and correct

3. Faulty amplifier or proportioning motor

3. See vendor literature shipped with unit

4. Airflow too high

4. Check blower speed and/or burner velocity 

differential pressure

5. Burner capacity undersized

5. Check rating plate for conformance to design 

specifications

Summary of Contents for IM-895

Page 1: ...Additional product and engineering information is available at www aerovent com Refer to the Safety section s in this manual prior to installing or servicing the door air heater The most current versi...

Page 2: ...is isolated by closing off the inlet or outlet to prevent wind driven rotation If an impeller is chocked to prevent rotation ensure that the chocks are removed prior to start up Wear appropriate pers...

Page 3: ...the unit after acceptance is not the responsibility of Twin City Fan Companies Ltd Unpack each carton or crate and verify for conformance with description of product ordered and all required parts an...

Page 4: ...g down and attach to the angle rings on the door air heater Make sure the rod locations do not interfere with gas train or electrical control panel access If desired provide one suspension type vibrat...

Page 5: ...alent for testing 2 Gas pressure to the unit controls must never exceed the pressure shown on the unit rating plate The unit and its individual shutoff valve s must be disconnected from the gas supply...

Page 6: ...f the process 7 External electrical connections to be installed include Supply power connection 115 208 230 380 460 or 575 volts Connection of thermostats and remote monitoring panels that may be supp...

Page 7: ...voltage to the voltage required for the unit controls 3 Flame Safeguard Control The flame safeguard control monitors safety devices to determine if the gas ignition sequence should be initiated Once i...

Page 8: ...re supplied with redundant automatic main gas shut off valves to control gas flow to the modulating gas valve 11 These valves may be a combination gas valve as shown which have two valve seats in one...

Page 9: ...n of the door air heater Remote monitoring panel features include Fan Switch All panels include a fan On Off switch Burner Switch All panels include a burner On Off switch Temperature Control Discharg...

Page 10: ...ment or installation Check burner and fan impeller to ensure it is secure Check all electrical connections for tightness Check to ensure there are no obstructions to the inlet air supply or the discha...

Page 11: ...nect an inclined manometer b If the outdoor air temperature is below 60 F fire the main burner to achieve a discharge air temperature of approximately 70 F If the burner does not fire under these cond...

Page 12: ...e to make sure the burner lights smoothly and the flame is present across the entire length of the burner 14 With the unit off close the main gas manual hand valve If applicable remove the U tube mano...

Page 13: ...r temperature does not exceed the maximum allowable limit for safe operation 2 With the safety devices described in the above steps verified the flame safeguard control is enabled to initiate the igni...

Page 14: ...accumulation of scale or foreign material on either side of the mixing plates should be removed with a wire brush 2 Add fresh di electric grease Grainger p n 23YC40 inside the flame rod boot 3 Check...

Page 15: ...f the unit and in the gas supply line to the unit 2 Turn off the electric supply to the unit at the unit disconnect Lock the disconnect to prevent tampering 3 Protect outside air openings to prevent t...

Page 16: ...ot 6 Defective flame rod 6 Check and or replace 7 Defective flame safeguard controller 7 Check and or replace 8 Short in flame sensor leads 8 Check and or replace 9 Excessive air velocity across burne...

Page 17: ...ice of the unit s to which this applies must be performed by a qualified installation and service agency 3 After completion of start up make a copy of this completed form for your files as necessary a...

Page 18: ...nect Wiring is over 200 Long Please Consult Factory 2 Gas supply connected with proper gas pressure regulator drip leg etc Yes No 3 Electrical supply connected with proper voltage amperage as stated o...

Page 19: ...Electrical Service Provided to Unit Volts Phase Hertz Amps 2 Unit Nameplate Electrical Requirements Volts Phase Hertz Amps 3 Main Fusing Size if applicable Volts Amps 4 Overload Relay Setting if appl...

Page 20: ...but with fan and gas on and unit in forced high fire 7 The Service Pressure with burner in high fire is __________ w c or ________oz or ________psig 8 The High Temperature Limit Switch is field set to...

Page 21: ...ts IV Miscellaneous Operational Checks 1 With the unit fan and burner operating all of the circuit check lights are illuminated except the burner lock out pilot light and the low temperature switch pi...

Page 22: ...ussed the unit controls and operation was Name Title please print please print CUSTOMER S AUTHORIZED SIGNATURE I acknowledge that I have been instructed on the operation of this unit Signature Date Ph...

Page 23: ...Installation Operation Maintenance Manual IM 895 23...

Page 24: ...WWW AEROVENT COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7500 Fax 763 551 7501 2021 Aerovent...

Reviews: