Aerovent IM-895 Installation, Operation & Maintenance Manual Download Page 11

Installation, Operation & Maintenance Manual

IM-895

11

4.  With the Fan On/Off switch still in the "Off" position, turn on the electrical supply to the unit.
5.  Move the Fan On/Off switch to the "On" position (to activate the unit with heat disabled).
6.  Check the blower for proper rotation per the airflow arrow on the blower.
7.  Check the motor voltage. For three phase systems, check to make sure the voltage on all 3 legs vary less than 2%.
8.  Check the motor Amp draw to be sure it does not exceed the motor nameplate FLA rating.
9.  Measure the unit air volume being delivered and compare to the rated air volume on the unit serial plate. The most accurate 

way to measure the air volume is by using a pitot traverse method downstream of the blower. Other methods can be used but 

should be proven and accurate.

10. Recheck the gas supply pressure by installing a gas pressure gauge connected to the inlet gas pressure test port indicated on 

the piping diagram included with the unit.

  If the unit has an inlet gas pressure gauge, the pressure can be read directly from the gauge without needing to connect 

a separate gauge. Refer to rating plate for proper gas supply pressure to unit. If inlet gas pressure exceeds the maximum 

pressure specified on the rating plate, a gas pressure regulator needs to be added upstream of the factory furnished and piped 

components.

  Refer to the heater rating plate for determining the minimum gas supply pressure to obtain the full heating capacity for which 

this heater is specified.

11. The unit includes Direct Spark Ignition (no pilot line), check the flame rod 

flame sensor signal with the following steps:

  a.  Check that all manual reset safety devices have been reset to their  

 

  normal operating position.

  b.  Set the Burner On/Off switch to "On" and set the temperature controls  

  to call for heat.

  d. The spark ignitor should begin to spark in approximately 10 seconds  

  and the burner flame should be established within 10 seconds.

12. Check the pressure differential across the burner profile per the following:

  a.  Remove the tubing plug from the burner gas pressure tap labeled  

 

  "BGPT" and connect an inclined manometer.

  b.  If the outdoor air temperature is below 60°F, fire the main burner to achieve a discharge air temperature of approximately  

  70°F. If the burner does not fire under these conditions, refer to the Troubleshooting Guidelines section of this manual for  

  additional guidance. If the outdoor temperature is 60°F or greater, do not fire the main burner.

  c.  Read the pressure differential reading on the burner pressure gauge or manometer. The actual installed pressure differential  

  reading must be 0.55" w.c. +/- 0.05" w.c. or 0.50" w.c. to 0.60" w.c.

  d.  If the differential pressure is out of range and cannot be achieved, contact the factory for additional guidance.

  e.  When the correct burner velocity pressure differential is verified, turn the unit off and open the main disconnect switch.  

  Remove the manometer and replace the tubing plugs in the burner gas pressure tap.

13. The high fire manifold (burner) pressure must be checked to ensure it matches the pressure shown on the unit serial plate. 

Over-firing from high pressure can result in poor combustion and undesirable levels of combustion byproducts being 

introduced to the heated space. The procedure is outlined in the following steps:

  a.  With the unit off, close the main gas manual hand valve. If not equipped with a burner gas pressure gauge, remove the  

  1/8" pipe plug test port at the burner and attach a water manometer or "U" tube that is at least 12" high. See piping diagram  

  furnished with the unit for pressure tap locations.

  b.  Start the unit and record the burner suction pressure present at the test port and record the negative number. Next, open  

  the gas valve and allow the burner to ignite (resetting the burner lockout if necessary). Observe the flame during the 10  

  second at low fire start to make sure it lights across the entire length of the burner and is stable with a clean blue flame.

  c.  Add the high fire pressure listed on the rating plate to the negative burner suction pressure recorded above. The resulting  

  sum is the actual measured gas pressure required for high fire in the next step.

  d. Initiate a short (10-second) period of high fire. High fire can be achieved by removing wire 29 from terminal 4 on the  

  Maxitrol amplifier.

Check, Test & Start-Up Procedure

 (cont.)

Direct Spark Ignition Components

SIDE VIEW

INTO AIRFLOW VIEW

Summary of Contents for IM-895

Page 1: ...Additional product and engineering information is available at www aerovent com Refer to the Safety section s in this manual prior to installing or servicing the door air heater The most current versi...

Page 2: ...is isolated by closing off the inlet or outlet to prevent wind driven rotation If an impeller is chocked to prevent rotation ensure that the chocks are removed prior to start up Wear appropriate pers...

Page 3: ...the unit after acceptance is not the responsibility of Twin City Fan Companies Ltd Unpack each carton or crate and verify for conformance with description of product ordered and all required parts an...

Page 4: ...g down and attach to the angle rings on the door air heater Make sure the rod locations do not interfere with gas train or electrical control panel access If desired provide one suspension type vibrat...

Page 5: ...alent for testing 2 Gas pressure to the unit controls must never exceed the pressure shown on the unit rating plate The unit and its individual shutoff valve s must be disconnected from the gas supply...

Page 6: ...f the process 7 External electrical connections to be installed include Supply power connection 115 208 230 380 460 or 575 volts Connection of thermostats and remote monitoring panels that may be supp...

Page 7: ...voltage to the voltage required for the unit controls 3 Flame Safeguard Control The flame safeguard control monitors safety devices to determine if the gas ignition sequence should be initiated Once i...

Page 8: ...re supplied with redundant automatic main gas shut off valves to control gas flow to the modulating gas valve 11 These valves may be a combination gas valve as shown which have two valve seats in one...

Page 9: ...n of the door air heater Remote monitoring panel features include Fan Switch All panels include a fan On Off switch Burner Switch All panels include a burner On Off switch Temperature Control Discharg...

Page 10: ...ment or installation Check burner and fan impeller to ensure it is secure Check all electrical connections for tightness Check to ensure there are no obstructions to the inlet air supply or the discha...

Page 11: ...nect an inclined manometer b If the outdoor air temperature is below 60 F fire the main burner to achieve a discharge air temperature of approximately 70 F If the burner does not fire under these cond...

Page 12: ...e to make sure the burner lights smoothly and the flame is present across the entire length of the burner 14 With the unit off close the main gas manual hand valve If applicable remove the U tube mano...

Page 13: ...r temperature does not exceed the maximum allowable limit for safe operation 2 With the safety devices described in the above steps verified the flame safeguard control is enabled to initiate the igni...

Page 14: ...accumulation of scale or foreign material on either side of the mixing plates should be removed with a wire brush 2 Add fresh di electric grease Grainger p n 23YC40 inside the flame rod boot 3 Check...

Page 15: ...f the unit and in the gas supply line to the unit 2 Turn off the electric supply to the unit at the unit disconnect Lock the disconnect to prevent tampering 3 Protect outside air openings to prevent t...

Page 16: ...ot 6 Defective flame rod 6 Check and or replace 7 Defective flame safeguard controller 7 Check and or replace 8 Short in flame sensor leads 8 Check and or replace 9 Excessive air velocity across burne...

Page 17: ...ice of the unit s to which this applies must be performed by a qualified installation and service agency 3 After completion of start up make a copy of this completed form for your files as necessary a...

Page 18: ...nect Wiring is over 200 Long Please Consult Factory 2 Gas supply connected with proper gas pressure regulator drip leg etc Yes No 3 Electrical supply connected with proper voltage amperage as stated o...

Page 19: ...Electrical Service Provided to Unit Volts Phase Hertz Amps 2 Unit Nameplate Electrical Requirements Volts Phase Hertz Amps 3 Main Fusing Size if applicable Volts Amps 4 Overload Relay Setting if appl...

Page 20: ...but with fan and gas on and unit in forced high fire 7 The Service Pressure with burner in high fire is __________ w c or ________oz or ________psig 8 The High Temperature Limit Switch is field set to...

Page 21: ...ts IV Miscellaneous Operational Checks 1 With the unit fan and burner operating all of the circuit check lights are illuminated except the burner lock out pilot light and the low temperature switch pi...

Page 22: ...ussed the unit controls and operation was Name Title please print please print CUSTOMER S AUTHORIZED SIGNATURE I acknowledge that I have been instructed on the operation of this unit Signature Date Ph...

Page 23: ...Installation Operation Maintenance Manual IM 895 23...

Page 24: ...WWW AEROVENT COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7500 Fax 763 551 7501 2021 Aerovent...

Reviews: