IMPROPER USE
27.
allow the refrigerant to escape and
unload the circuit, causing appliance
malfunctioning. In these cases the
leakage points must be found and
repaired and the cooling circuit must
be refilled, operating in compliance
with the Law 28 n°549 dated 28
December 1993.
i
ATTENTION
It is prohibited TO LOAD the cool-
ing circuits with a refrigerant
different to that indicated. Using
a different refrigerant gas can
cause serious damage to the
compressor.
The amount of refrigerant gas contai-
ned in the plate is shown on a feature
board machine
The appliance is designed and built
to guarantee maximum safety in the
immediate vicinity.
IMPORTANT SAFETY
27.1.
INFORMATION
Correct functioning of the unit is not
guaranteed following a fire; before re-
starting the machine, have it checked
by an authorised after-sales service
centre.
Wind, earthquakes, and other natural
phenomena of exceptional intensity
have not been considered.
If the unit is used in an aggressive at-
mosphere or with aggressive water,
please contact the head offices.
ATTENTION
Following extraordinary maintenance
−
work
on the cooling circuit involving the
−
replacement of components, before
restarting the machine, carry out
the following operations:
Pay the maximum attention in
−
restoring the load of refrigerant
indicated on the machine plate
Open all the cocks present in the
−
cooling circuit.
Connect the electric power supply
−
and earth correctly.
VXT
6
8
10
14
16
SEZ A
230V n° x mm
2
3 x 10
3 x 10
3 x 10
-
-
400V n° x mm
2
-
5 x 4
5 x 6
5 x 6
5 x 6
Terra
230V mm
2
10
10
10
-
-
400V mm
2
-
4
6
6
6
IL
230V
A
40
40
40
-
-
Type
3 phase
3 phase
3 phase
-
-
400V
A
-
40
40
40
40
Type
-
3 phase + N 3 phase + N 3 phase + N 3 phase + N
ELECTRICAL DATA
28.
KEY
SEZ.A
Alimentazione
TERRA
connection to earth
IL
General switch