background image

19

18.03. 5719210_03

ANL / 290-650

EN

to  (U) phase, (N) neutral, (PE) earth in the case 

of single phase units (230V/50Hz),

8. 

U-V-W for phases, N for neutral and PE 

for earth in the case of three phase units 

(400V/3N/50Hz).

9. 

Replace the inspection panels. 

10. 

Ensure that all protection removed for the elec-

trical connection are replaced before powering 

the unit.

11. 

Place the main isolator (external to the unit) 

to “ON”.

9. 

CHECKS AND FIRST START-UP

9.1.  PREPARING FOR FIRST START-UP

It is reminded that for units of this series, if requested 

by the Aermec client or the legal owner and only 

on ITALIAN territory, free start-up is provided by the 

regional Aermec technical assistance service. The 

start-up must be previously agreed based on the 

intended time of completion of installation. Before the 

start-up all the works (electrical and hydraulic connec-

tions, filling and venting of air in the system) must be 

completed.

9.2.  START-UP 

9.2.1.  PRELIMINARY CHECKS BEFORE 

POWERING UP

CHECK

:

1. 

All safety precautions have been followed.

2. 

The unit has been appropriately fixed to the 

support base.

3. 

Minimum clearance spaces have been ob-

served.

4. 

Power supply cables are correctly sized and ca-

pable of supporting the electrical requirements 

of the unit (see section on electrical data) and 

that the unit is correctly earthed. 

5. 

All electrical connections are correctly termi-

nated and tightened.

9.2.2.  CHECKS TO BE DONE WHEN POWERED UP

1. 

Apply power to the unit by turning the main iso-

lator to the ON position. The display will power 

up after several seconds after applying power, 

check that the operating status is on OFF (OFF BY 

KEYB on the lower part of the display). 

2. 

Check with a tester that the power supply volt-

ages on the phases U-V-W are 400V ±10%, check 

that the phase imbalance is not greater than 3%.

3. 

Check that the connections made by the installer 

comply with the documentation.

4. 

Check that the compressor crankcase heater(s) 

are operating by measuring the increase of oil 

sump temperature. The heater(s) must be in 

operation for at least 24 hours before starting 

the compressor, and in all cases the sump oil 

temperature must be 10-15 K above ambient 

temperature.

  HYDRAULIC CIRCUIT

1. 

Check that all hydraulic connections have been 

correctly installed, that the instructions on the 

labels have been followed, and that a mechani-

cal filter has been installed on the inlet to the 

evaporator. (Mandatory component otherwise 

the warranty will be voided).

2. 

Confirm that the pump(s) are operating and that 

the flow rate is sufficient to make the contact on 

the flow switch.

3. 

Check the water flow rate by measuring the 

differential pressure across the evaporator inlet 

and outlet and calculating the flow from the 

evaporator pressure drop diagram provided in 

the documentation.

4. 

Check the correct functioning of any flow 

switch installed; close the isolating valve on the 

evaporator outlet and observe the result on the 

unit display panel; open the valve and reset the 

flow trip alarm.

9.3.  FIRST START-UP

After having rigorously followed the above checks it is 

possible to start the unit:

1. 

Close the electrical panel.

2. 

Turn the main isolator to ON.

3. 

Press the key ON   for 3 seconds to start the 

unit. 

 

Pressing the key ON   displays the water 

temperature and the operating mode of the unit. 

Check the operating setpoint parameters and 

reset any alarms present . After a few minutes 

the unit will start.

9.3.1.  CHECKS WITH THE UNIT RUNNING

  REFRIGERANT CIRCUIT 

  CHECK:

-  That the compressor input current of the compres-

sors is less than that indicated in the table of electri-

cal data.

-  That in three phase models the compressor noise is 

not abnormal, indicating a reverse rotation. In this 

case reverse one of the phases.

-  That the voltage values are within the determined 

limits and that the phase imbalance (three phase 

power) is less than 3%.

-  Presence of any refrigerant leaks, in particular 

from connections to gauges, pressure transducers 

and pressostats. (Vibrations during transportation 

may have loosened connections).

-  Superheat                                                                                               

  Compare the compressor suction temperature with 

a contact temperature sensor reading with the 

temperature of the low pressure gauge (saturated 

suction temperature corresponding to the evaporat-

ing pressure). The difference between these two 

temperatures is the superheat value. The optimal 

values are between 4 and 8 K.

-  Discharge temperature                                                                                                                 

If the values of sub-cooling and superheat are 

normal the temperature measured in the discharge 

line from the compressor must be 30/40 K above 

the condensing temperature.

  SAFETY AND CONTROL DEVICES

 

CHECK

:

-  The manual high pressure pressostat, which stops 

the compressor and generates and alarm when the 

discharge pressure exceeds the preset value. The 

correct operation is checked by closing the refriger-

ant isolating valve to the heat exchanger (in cooling 

mode) and keeping a check on the high pressure 

gauge, verify the operation corresponds to the rated 

value. Warning: in the event the pressostat does 

not operate at the rated value immediately stop 

the compressor and investigate the cause. Reset is 

manual but can only be done when the pressure 

drops below the differential setting. (For the values 

of the trip and differential setting refer to the tech-

nical manual).

-  Anti-freeze protection

  The electronic control of the anti-freeze protection 

is from the water temperature sensor leaving the 

evaporator prevents freezing of water when the 

temperature is too low. The operation of the anti-

freeze protection can be checked by increasing the 

setpoint value until it is above the temperature of 

leaving water and checking the water temperature 

with a high precision sensor. Confirm that the unit 

stops and generates the responding alarm. After this 

check reset the anti-freeze setpoint to the original 

value.

Summary of Contents for Variable Multi Flow ANL 290

Page 1: ...BARCODE EN Installation and Maintenance Manual CHILLERS EXTERNAL UNITS HIGH EFFICIENCY ANL 290 650 18 03 5719210_03...

Page 2: ...es In addition the applied mark guarantees that our appliances fully comply with the safety requirements defined by the applicable product s rules We constantly monitor the quality level and as a resu...

Page 3: ...EN 60335 2 40 A2 2009 CEI EN 55014 1 2017 CEI EN 60335 2 40 A13 2012 CEI EN 55014 2 2016 La presente dichiarazione di conformit rilasciata sotto la responsabilit esclusiva del fabbricante This declara...

Page 4: ...7 3 Dimensions ANL 580 620 650 mm 15 7 4 Position of hydraulic connections mm 16 7 5 ANL C 290 300 340 400 mm 17 7 6 ANL C 580 620 650 mm 17 8 Electrical connections 18 8 1 Electrical power supply con...

Page 5: ...h the equipment as this could result in accidents for which the manufacturer will not be held responsible The warranty will be voided if the above mentioned warnings are not respected 1 2 SAFETY INSTR...

Page 6: ...ifting capability of the equipment being used taking into account the information provided with the packaging When lifting insert through the unit s base holes lifting bars NOT PROVIDED of sufficient...

Page 7: ...nnection to the unit This clean ing eliminates welding slag dirt rust or any other impurities from the piping These impurities may otherwise be deposited within the unit and cause a malfunction The co...

Page 8: ...freezing 1 Complete draining of water from the unit 2 Operating with glycol with a percentage of glycol se lected in accordance with the minimum anticipated external temperature 3 Use of electric hea...

Page 9: ...ly sized for the required flow rate The water flow rate through the heat exchanger must always be constant WARNING Carefully clean the system prior to connection to the unit This clean ing eliminates...

Page 10: ...must always be constant WARNING Carefully clean the system prior to connection to the unit This clean ing eliminates welding slag dirt rust or any other impurities from the piping These impurities ma...

Page 11: ...heat exchanger must always be constant WARNING Carefully clean the system prior to connection to the unit This clean ing eliminates welding slag dirt rust or any other impurities from the piping Thes...

Page 12: ...217 2 28 75 221 6 21 32 164 4 21 76 167 7 VT17 12 0 0 6 ANL 400 L P2 797 754 1049 536 52 805 1080 542 27 56 220 5 28 37 226 9 21 72 173 7 22 35 178 8 VT17 12 0 0 6 ANL 400 L P3 778 735 1032 537 54 788...

Page 13: ...25 1160 1100 800 800 800 1100 3000 A Gy Gx B C D 1610 40 16 16 16 16 40 420 420 2050 200 200 2050 200 200 20 20 1060 7 1 DIMENSIONS ANL 290 300 340 mm 7 1 1 MAXIMUM OVERALL mm 1610 40 16 16 16 16 40 4...

Page 14: ...0 16 16 16 16 40 420 420 2050 200 200 2050 200 200 20 20 1060 7 2 2 LIFTING POINTS mm 16 16 16 16 2050 200 200 2050 200 200 20 20 1060 7 2 3 POSITION ANTI VIBRATION MOUNTS mm 1605 1735 2450 2525 1160...

Page 15: ...IMUM OVERALL mm 1875 3200 3275 2005 1100 1160 800 800 800 1100 3000 40 16 16 16 16 16 16 40 1525 1275 200 200 1525 1275 200 200 Gy Gx 1956 40 16 16 16 16 16 16 40 644 600 1525 1275 200 200 1525 1275 2...

Page 16: ...UT 2 IN 2 195 180 670 ANL 290 300 340 400 VERSION 00 ANL 290 300 340 400 VERSION 01 02 03 04 P1 P2 P3 P4 IN 2 OUT 2 IN 2 OUT 2 205 180 492 205 180 670 IN 2 OUT 2 IN 2 OUT 2 IN 2 OUT 2 205 180 492 195...

Page 17: ...ANL 290 650 EN 7 5 ANL C 290 300 340 400 mm 7 6 ANL C 580 620 650 mm 191 184 152 233 189 183 138 219 A C B D 189 183 138 219 C D A Inlet Intake line 35 B Otlet Liquid line 22 C Inlet Intake line 42 D...

Page 18: ...e below 2 The unit is only powered up on completion of any hydraulic and electrical works 3 Comply with the indicated phasing and earth requirements 4 The power supply cable must have the appropri ate...

Page 19: ...ct functioning of any flow switch installed close the isolating valve on the evaporator outlet and observe the result on the unit display panel open the valve and reset the flow trip alarm 9 3 FIRST S...

Page 20: ...t the control panel is off WARNING For the installation refer to the electrical wiring schematics provide with the unit The electrical wiring schematic and manuals must be carefully conserved and made...

Page 21: ...n and energy efficiency The fundamental required annual checks are 11 1 HYDRAULIC CIRCUIT CHECK 1 Water circuit is filled 2 Water filter is clean 3 Operation of the differential pressure or flow switc...

Page 22: ...vents and of the terminal units 14 5 UNIT DRAINING WARNING During the winter period the water in the heat exchanger may freeze when the system is off causing irreversible damage to the heat exchanger...

Page 23: ...installed PR3 Not installed Go to question 3 Installed Enter in parameter PAN index 9 menu INSTALLER with the appropriate value Value 1 Season selection controlled from the chiller circuit board ON OF...

Page 24: ...ns loose Operating outside of limits Check against operating limits chart Pressostat faulty Replace the component Thermal cut out operates Check voltage and settings Check insulation of windings Compr...

Page 25: ...02 04 P2 P4 9 Liquid sight glass 10 Desuperheater optional 11 Water filter 12 Pump s optional 13 Expansion tank standard with hydronic module 14 Buffer tank optional 15 Flow switch 16 Gauge 17 Air ven...

Page 26: ...nal valve only for versions 02 04 P2 P4 9 Liquid sight glass 10 Desuperheater optional 11 Water filter 12 Pump s optional 13 Expansion tank standard with hydronic module 14 Buffer tank optional 15 Flo...

Page 27: ......

Page 28: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...

Reviews: