49
INPUTS/OUTPUTS menu - Evaporators pump magnet circuit breaker digital inputs
Visualisation on unit display
Index
Display/Parameter
A
Inputs/Outputs:
Indicates the state of the different entries/exits.
B
Master:
indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C/D
13-14:
indicates the status of the evaporator pump magnet
circuit breaker indicated. The status of this input can be one of
the following:
• Closed = normal functioning;
• Open = the pump load has exceeded the maximum thresh-
old (Pump magnet circuit breaker alarm);
B
Input/Output
Master digital input
A
C
13= Ovrl.evap.pump 1:
Close
14= Ovrl.evap.pump 2:
---
D
INPUTS/OUTPUTS menu - Compressor 2 magnet circuit breaker digital inputs
Visualisation on unit display
Index
Display/Parameter
A
Inputs/Outputs:
Indicates the state of the different entries/exits.
B
Master:
indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C
11:
indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
D
12:
indicates the status of the compressor magnet circuit breaker
indicated, the status of this input can be one of the following:
• Closed = normal functioning;
• Open = the compressor load has exceeded the maximum
threshold (Compressor magnet circuit breaker alarm);
B
Input/Output
Master digital input
A
C
11= Ovrl.cmp.1 circ.2
Close
12= Ovrl.cmp.2 circ.2
Close
D
INPUTS/OUTPUTS menu - Condenser pump magnet circuit breaker digital inputs
Visualisation on unit display
Index
Display/Parameter
A
Inputs/Outputs:
Indicates the state of the different entries/exits.
B
Master:
indicates the type of data displayed; the displays can be:
• Analogue inputs;
• Digital inputs;
• Digital outputs;
C/D
13-14:
indicates the status of the condenser pump magnet
circuit breaker indicated. The status of this input can be one of
the following:
• Closed = normal functioning;
• Open = the pump load has exceeded the maximum thresh-
old (Pump magnet circuit breaker alarm);
B
Input/Output
Master digital input
A
C
15= Ovrl.cond.pump 1:
Close
16= Ovrl.cond.pump 2:
---
D