11
MINIMUM TECHNICAL SPACES
D
B
C
A
E
F
L
* Minimum technical space, to be ensured in order for the chiller to work properly and for possible maintenance.
ATTENTION with this space, the condenser coil can only be pulled out from above; to pull it out from the side you must
leave at least 91 in.
1
Panel type
F
in
41,8
Electric power
board
Unit
Vers.
V-block
Fans
Panel type
A
B
C
D
E
NRB H
n°
n°
in
in
in
in
in
800
HA/HE
3
6
1
39*
43
39*
32
118
900
HA/HE
4
8
1
39*
43
39*
32
118
1000
HA/HE
4
8
1
39*
43
39*
32
118
1100
HA/HE
4
8
1
39*
43
39*
32
118
1200
HA/HE
4
8
1
39*
43
39*
32
118
1400
HA/HE
5
10
1
39*
43
39*
32
118
1600
HA/HE
6
12
1
39*
43
39*
32
118
1800
HA/HE
7
14
1
39*
43
39*
32
118
2000
HA/HE
7
14
1
39*
43
39*
32
118
2200
HA/HE
8
16
1
39*
43
39*
32
118
2400
HA/HE
8
16
1
39*
43
39*
32
118
3000 mm
3000 mm
C1 - C2
2300 mm
118 in
118 in
39/45 in
91 in