PASSWORD = 031
INSTALLER 2 menu
To access the INSTALLER_2 menu, follow the same procedure described for the INSTALLER menu; the only difference
is the value of the password, which is 31.
WARNING The following parameters
must only be modifi ed by qualifi ed
personnel authorised to install the
unit.
Setting operational parameters (installer level)
Threshold for reactivation after shutdown force off
Index - String
MIN
value
MAX
value
Parameter function
0 °C
30 °C
If the parameter value rin = 4 (parameter 8 of the Installer menu), then this is a probe storage system,
this parameter indicates how much lower the threshold of force off so as to prevent the compressor is
reactivated after the intervention of ForceOff dynamic extinguished soon after.
Configuration of the heating cable (ANK only)
Index - String
MIN
value
MAX
value
Parameter function
0
2
Setting the output to which the heating cable is connected:
0- no heating cable
1- heating cable on the CPA output
(the parameter (0) of the menu with password=72 “according to CP must be 0”
2- heating cable on the VGC output if not used (the configuration of the dip switches must be: DIP1 =
ON, DIP2=ON, DIP5=ON, DIP8=OFF, DIP9=OFF)
Heating cable setpoint (ANK only)
Index - String
MIN
value
MAX
value
Parameter function
-20 °C
10 °C
Heating cable activated with an external air temperature lower than the value of this parameter.
Heating cable deactivated with an external air temperature higher than the value of this parameter, plus
1.0° hysteresis.
Thermostat pump switch-off
Index - String
MIN
value
MAX
value
Parameter function
0
1
0 = the pump continues to function when the set point temperature is reached. 1 = the pump switches
off when the set point temperature is reached (when this option is selected, the adjustment is automati-
cally activated on the basis of the input temperature). This parameter is only visible with the adjustment
on the basis of the input temperature (parameter (0) =1 or 2).