55
EN
IMDCFJ. 12.05 6343841_03
Setting cooling temperature setpoint 1
Index - String
MIN
value
MAX
value
Parameter function
-20 °C
26 °C
This parameter indicates the maximum value of the cooling setting, corresponding with the minimum
outside air temperature (index (7) user menu). This parameter is only visible if the compensation fun-
ction has been activated (index (5) user menu).
Setting the outside air temperature 1
Index - String
MIN
value
MAX
value
Parameter function
-40 °C
50 °C
This parameter indicates the minimum outside air temperature taken into consideration for cooling
compensation. This parameter is only visible if the compensation function has been activated (index (5)
user menu).
Setting cooling temperature setpoint 2
Index - String
MIN
value
MAX
value
Parameter function
-20 °C
26 °C
This parameter indicates the minimum value of the cooling setting, corresponding with the maximum
outside air temperature (index (9) user menu). This parameter is only visible if the compensation fun-
ction has been activated (index (5) user menu).
Setting the outside air temperature 2
Index - String
MIN
value
MAX
value
Parameter function
-40 °C
50 °C
This parameter indicates the maximum outside air temperature taken into consideration for cooling
compensation. This parameter is only visible if the compensation function has been activated (index (5)
user menu).
Setting the outside air temperature 1 (heating)
Index - String
MIN
value
MAX
value
Parameter function
-40 °C
50 °C
This parameter indicates the minimum outside air temperature taken into consideration for heating
compensation. This parameter is only visible if the compensation function has been activated (index (5)
user menu).
Setting heating set 1
Index - string
Value
MIN
Value
MAX
Parameter function
25 °C
(*)
This parameter indicates the maximum value set at heating, in correspondence with
the minimum outdoor air temperature (user menu index (b) This parameter is visible
only if the compensation function is activated (use menu index (5)).
(*):
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes
70°C in order to allow insertion of a set-point for boiler adjustment;
Parameter visible ONLY on units suitable for the production
of hot water
Parameter visible ONLY on units suitable for the production
of DHW
Parameter visible ONLY on units with condensation control
device on board
Parameter ONLY visible on units fitted with twin compressor
Parameter ONLY visible on units fitted with inverter com-
pressor