WARNING: before carrying out any work, make sure the 
power supply is disconnected.
WARNING: electrical wiring, installation of the fan coils and 
relevant accessories should be performed by a technician 
who has the necessary technical and professional expertise to 
install, modify, extend and maintain systems, and who is able 
to check the systems for the purposes of safety and correct 
operation. 
In the specific case of electrical wirings, the following must 
be checked:
- measurement of the electrical system insulation strength
- continuity test of the protection wires.
Instructions essential for the proper installation of the 
equipment are shown here.

The completion of all the operations in accordance with the 
specific requirements is, however, left to the experience of the 
installation engineer.
The command device is made up of an electronic control 
panel, to be flush-mounted in the wall in a standardised, 
3-module rectangular box (type 503).
The control panel is fitted with two covering plates, a white 
one and a black one.
Avoid installing the control panel in places directly exposed 
to sun rays, draughts, heat sources and fan coil flow. Install 
the unit at about 150 cm from the floor, on an internal, air-
conditioned wall.
Connect the wires to the control board as indicated in the 
wiring diagrams.
Use wires with a maximum length of 6 metres.

INSTALLATION

106

71

L1

~

HIGH

MED

LOW

HEA
T

COOL

L2 - 0

C650 FS - 1C - 1H

EXT. SENSORS

A

W

PROBE INSTALLATION (SWA ACCESSORY)

If the system configuration allows it, the FMT20AW panel can 
be connected simultaneously to 2 SWA probes.

The probe connection cable measures 6 metres.

The probe is connected to the connectors (A) and (W) positio-
ned on the back of the control panel (see wiring diagrams).

WATER TEMPERATURE CONTROL
The SWA probe detects the temperature of the water in the 
system if connected to the connector (W).
It must be positioned on the inlet pipe downstream from any 
valve. 
The SWA probe for water temperature control can only be used 
on 2-pipe systems without electric resistance.
The maximum/minimum water temperature control is only 
active with the thermostat ventilation 

; the control will be 

deactivated if continuous ventilation 

 is selected.

The control will also be deactivated if the 
“ventilation only” functioning mode is selected.
This control allows to prevent the ventilation if 
the system water temperature is not suitable for 
the functioning mode.
The control is only activated at the moment 
when functioning in heating or cooling mode is 
requested by the thermostat.
The probe-holder and bands for fixing to the 
water pipe are also supplied with the accessory 
(see diagram).

AIR TEMPERATURE CONTROL
The SWA probe detects the temperature of the room air if 
connected to the connector (A). The air temperature probe, 
incorporated in the panel, is automatically disabled.
The SWA probe must be positioned in a point such that it can 
correctly detect the 
room temperature. 
The vicinity to heat 
sources, lights and 
windows or the direct 
exposure to the sun’s 
rays and to currents of 
air prevent the correct 
detection of the room 
temperature.
The SWA accessory 
is also supplied with 
band for fixing the 
fancoil intake probe 
(see diagram).

A I R

A I R

A I R

20mm

FCX / FCS

AIR

W

A

TER

Summary of Contents for FMT 20 AW

Page 1: ...TRONIQUE POUR VENTILO CONVECTEURS INSTALLATION MURALE ELEKTRONISCHE BEDIENTAFEL F R GEBL SEKONVEKTOREN ZUR WANDMONTAGE TABLERO DE MANDOS ELECTR NICO PARA FAN COILS INSTALACI N DE PARED MANUALE D USO E...

Page 2: ...aracteristics Use Installation Wiring diagrams INDEX 13 14 17 28 Caract ristiques Utilisation Installation Sch mas lectriques TABLE DES MATI RES 18 19 22 28 Technische Daten Verwendung Installation Sc...

Page 3: ...al termostato VENTILAZIONE CONTINUA La ventilazione rimane attiva indipendentemente dal raggiungimento della temperatura impostata il controllo della temperatura viene quindi ottenuto tramite l apertu...

Page 4: ...o il pulsante per circa 12 secondi la visualizzazione della temperatura si converte da C a F e viceversa 6 SONDA TEMPERATURA Rileva la temperatura ambiente 7 VISUALIZZAZIONE SCALA DELLE TEMPERATURE C...

Page 5: ...rigeratore FMT20AW pu essere abbinato anche a ventilconvettori per raffrescamen to solo sensibile 1 MODO AUTOMATICO Selezionare con il tasto il modo di funzionamento in automatico sul display appaiono...

Page 6: ...TATATA Per scegliere tra la ventilazione continua e la ventilazione termostata ta premere il pulsante ed entro tre secondi premere indiffe rentemente uno dei pulsanti oppure VENTILAZIONE CONTINUA Non...

Page 7: ...e a 2 sonde SWA Il cavo di collegamento della sonda lungo 6 metri La sonda va collegata ai connettori A e W posti sul retro del pannello comandi vedi schemi elettrici CONTROLLO DELLA TEMPERATURA DELL...

Page 8: ...nserted in the system Do not use this setting in systems without water interception valves as the ventilation will be continuous and not controlled by the thermostat T H E R M O S T A T C O N T R O L...

Page 9: ...bout 12 seconds the visualisation of the temperature changes from C to F and vice versa 6 TEMPERATURE PROBE Reveals the room temperature 7 VISUALISATION OF TEMPERATURE SCALE C F Indicates the temperat...

Page 10: ...th fan coils for sensitive only cooling 1 AUTOMATIC mode Use the key to select the Automatic working mode the symbols will appear on the display Using the keys select the desired temperature the corre...

Page 11: ...TROLLED VENTILATION To choose between continuous ventilation and thermostat controlled ventilation press the button and within three seconds press either one of the buttons or CONTINUOUS VENTILATION D...

Page 12: ...FMT20AW panel can be connected simultaneously to 2 SWA probes The probe connection cable measures 6 metres The probe is connected to the connectors A and W positio ned on the back of the control pane...

Page 13: ...ation Ne pas utiliser ce r glage dans les installations sans vannes d arr t de l eau car la ventilation sera continue et non contr l e par thermostat VENTILATION THERMOSTAT E La ventilation s teint au...

Page 14: ...llumer et teindre le ventilo convecteur 6 SONDE DE TEMP RATURE Elle mesure la temp rature ambiante 7 VISUALISATION DE L CHELLE DESTEMP RATURES C F Elle indique l chelle de temp rature utilis e C ou F...

Page 15: ...r avec des ventilo convecteurs pour refroidissement seulement sensible 1 MODE AUTOMATIQUE S lectionner avec la touche le mode de fonctionnement en automatique les symboles s affichent sur l afficheur...

Page 16: ...ILATION CONTINUE VENTILATION THERMOSTAT E Pour choisir entre la ventilation continue et la ventilation thermostat e appuyer sur le bouton et dans les trois secondes qui suivent appuyer sur n importe l...

Page 17: ...ion le permet le panneau FMT20AW peut tre connect simultan ment 2 sondes SWA Le c ble de connexion de la sonde a une longueur de 6 m tres La sonde doit tre reli e aux connecteurs A et W situ s l arri...

Page 18: ...bt unabh ngig vom Erreichen der eingestellten Temperatur aktiv Die Steuerung der Temperatur erfolgt somit durch das ffnen und Schlie en des der Wasserventils e in der Anlage Verwenden Sie diese Einste...

Page 19: ...ltetem Thermostat und Bet tigung der Taste f r etwa 12 s wird die Anzeige der Temperatur von C in F und umgekehrt umgewandelt 6 TEMPERATURF HLER Ermittelt die Raumtemperatur 7 ANZEIGE DER TEMPERATURSK...

Page 20: ...zur sensiblen K hlung kombiniert werden 1 BETRIEBSART AUTOMATISCH W hlen Sie mit der Taste den Automatikbetrieb und auf dem Display erscheinen die Symbole W hlen Sie mit den Tasten die gew nschte Tem...

Page 21: ...emperatur festgelegt 1 L FTUNG DAUERL FTUNG DURCH THERMOSTAT GESTEUERTE BEL FTUNG Dr cken Sie zur Wahl zwischen der Dauerl ftung und der mit Thermostat geregelten L ftung die Taste und innerhalb von d...

Page 22: ...uration der Anlage dies zul sst Das Verbindungskabel der Sonde ist 6 Meter lang Die Sonde muss mit den Verbindern A und W auf der R ckseite des Steuerpaneels verbunden werden siehe Schaltpl ne KONTROL...

Page 23: ...ventilaci n ser continua y no controlada por el termostato VENTILACI N CONTINUA La ventilaci n permanece activa pese a haberse alcanzado la temperatura programada el control de la temperatura se real...

Page 24: ...prox 12 segundos la visualizaci n de la temperatura se convierte de C a F y viceversa 6 SONDA TEMPERATURA Detecta la temperatura ambiente 7 VISUALIZACI N DE LA ESCALA DE LASTEMPERATURAS C F Indica la...

Page 25: ...tambi n con fan coils para refrigeraci n s lo sensible 1 MODO AUTOM TICO Seleccione con la tecla el modo de funcionamiento en autom tico en la pantalla aparecen los s mbolos Seleccione con las teclas...

Page 26: ...entre la ventilaci n continua y la ventilaci n controlada por termostato apriete el bot n y antes de tres segundos apriete indiferentemente uno de los botones o bien VENTILACI N CONTINUA No utilice es...

Page 27: ...de conexi n de la sonda es de 6 metros de largo La sonda se conecta a los conectores A y W puestos en la parte trasera del panel de mandos vea esquemas el ctricos CONTROL DE LA TEMPERATURA DEL AGUA Si...

Page 28: ...e 3 v as calor VCF Valvola a tre vie caldo freddo Three way valves heat cool Vanne trois voies chaud froid Dreiwegeventil Heinz K hl V lvula agua de 3 v as calor fr o VF Valvola a tre vie freddo Three...

Page 29: ...V C MS MS M FCX M 5 5 1 4 4 3 3 2 2 6 6 1 MV BL NE MA RO BL NE MA RO M 1 MAX MED MIN FMT20AW impianto 4 tubi fan coil con 2 valvole 4 tube system fan coil with 2 valves installation 4 tuyaux ventilo...

Page 30: ...30...

Page 31: ......

Page 32: ...A se r serve le droit de modifier tous moments les donn es consid r es n cessaires l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to i...

Reviews: