INSTALLATION
INSTALLING THE UNIT
- Make the water connections.
- In the event of disassembly and rein-
stallation, use new gaskets.
Refer to the size data for the position,
type and diameter of the water con-
nections.
You are advised to adequately insulate
water lines
and/or fit the auxiliary
condensate drain tray (available as an
accessory), to prevent dripping during
the cooling function.
After installing, check the seal on the
connections.
WATER CONNECTIONS
A
A
B
B
A
B
To install the unit, proceed as follows:
- Remove the covering cabinet
- Use wall plugs (not supplied) for wall-
mounted installations
- Apply any accessories.
M a k e t h e wa t e r c o n n e c t i o n s a s
described in the relative chapter.
Make the condensate discharge con-
nection as described in the relative
chapter. The fan coils that work in heat
mode only do not require condensate
discharge.
Make the electrical wiring as shown in
the relative chapter and in the wiring
diagrams.
Install and connect any accessories.
Complete the installation by reassem-
bling the casing and air filter.
Start up the fan coil and check all the
components and functions are operat-
ing correctly.
In the event of horizontal installation,
assemble the condensate discharge
connection supplied
.
Make sure you
seal the connection between the drip
tray and the fitting with silicone. The
condensate drain network must be
properly scaled and the piping situ-
ated in such a way as to keep an ade-
quate slope along the route (min. 1%).
If condensate is discharged into the
sewage system, install a siphon to
prevent the return of unpleasant odours
into the room.
Carry out a functioning and seal test of
the condensate drain system by pour-
ing water into the tray
CONDENSATE DRAIN
Ø 0.807 inches
Ø 20.5 mm