24
FCX B-U-UA-UE
EN
IFCXBULJ 1412 - 6456062_01
Dry-bulb temperature of ambient air (Ta) [°C]
21
23
25
27
29
31
Wet-bulb temperature
of ambient air (Ta) [°C]
15
3
3
3
3
3
3
17
3
3
3
3
3
3
19
3
3
3
3
3
3
21
6
5
4
3
3
3
23
-
8
7
6
5
5
MINIMUM AVERAGE WATER TEMPERATURE (Tw) [°C]
20.
OPERATING LIMITS
FCX
17
22
32
36
42
50
56
62
82
102
24
34
44
54
64
84
Maximum water inlet temperature (Tw)
°C
80
Maximum water inlet temperature recommended
(Tw)
°C
65
Maximum operating pressure
bar
8
Environment temperature limits (Ta)
°C
0 < Ta < 45
Relative humidity limits in the environment (R.H.)
R.H. < 85%
Electric power supply
230V ( ±10% ) ~ 50Hz
Standard main coil • Cooling circuit for double-circuit coils
FCX
17
22
32
36
42
50
56
62
82
102
Standard coil
Minimum water flow rate (Qw)
l/h
100
100
100
100
150
150
150
300
300
300
Maximum water flow rate (Qw)
l/h
750
750
750
750
1100 1100 1100
2200 2200 2200
Larger coil
FCX
24
34
44
54
64
84
Larger coil
Minimum water flow rate (Qw)
l/h
150
150
150
150
300
300
Maximum water flow rate (Qw)
l/h
1100 1100
1100 1100
2200 2200
Heating only coil (BV accessory) • Heating circuit for double-circuit coils
FCX
BV
17
117
22
122
32
132
36
132
42
142
50
142
56
142
62
162
82
162
102
162
Minimum water flow rate (Qw)
l/h
50
50
50
50
50
50
50
100
100
100
Maximum water flow rate (Qw)
l/h
400
400
400
400
400
400
400
900
900
900
If the fan coil runs continuously in cooling
mode in an environment with high relative
humidity, condensate may form on the air
flow. This condensate could drip onto the
floor and onto any underlying objects. To
prevent condensation phenomena on the
external structure of the appliance with the
fan running, the average water temperature
must not drop below the limits indicated in
the table. These limits depend on the tem
-
perature and humidity conditions of the
room air. These limits refer to operation with
the fan running at minimum speed.
Condensation may form in the event the fan
is off for a prolonged period and cold water
flows in the coil;
therefore, we recommend
installing the 3-way valve (accessory).
In order to prevent air stratification in the envi
-
ronment and thus, have better mixing, the fan coil
should not be supplied with water that is hotter
than 65 °C. Using water at a very high tempera
-
ture can cause creaking due to the heat expansion
of the elements (plastic and metal). However, this
does not cause damage to the unit unless the
maximum operating temperature is exceeded.
Minimum average water temperature
Water temperature
Summary of Contents for FCX 102
Page 2: ......
Page 77: ...77 FCX B U UA UE IFCXBULJ 1412 6456062_01 WMT10 VCF WMT10 VF VC WMT10 VF RX...
Page 78: ...78 FCX B U UA UE IFCXBULJ 1412 6456062_01 FM10 VCF FMT10 VF VC FMT10 VF RX...
Page 79: ...79 FCX B U UA UE IFCXBULJ 1412 6456062_01 FMT21 VCF FMT21 VF VC FMT21 VF RX FMT21 FMT21 FMT21...
Page 80: ...80 FCX B U UA UE IFCXBULJ 1412 6456062_01 PXAE SIT3 SIT5...
Page 89: ......
Page 90: ......