27
DMH - DMH_C - DMV
EN
GND
S01
GND
S02
GND
RES
GND
HP
NR
FR
NV
FV
NC
FC
N
F
GND
BP
NA
FA
GND
TIMER
GND
INT
P
230 V / 50 Hz/ 1 ph
[ID2]
[ID1]
[ID3]
[ID4]
[R02]
[R03]
[R01]
[R07]
Bianco
Blu
Nero
Rosso
Comune/Common
min
med
max
230 V
[S01]
[S02]
SONDA ACQUA
SONDA ARIA
ALTA PRESSIONE
BASSA PRESSIONE
UMIDOSTATO
ON/OFF MODALITA' TERMOVENTILANTE
COMPRESSORE
VENTILATORE
ALL (230V)
CONTATTO PULITO
PER ALLARME
250mA
9. ELECTRICAL CONNECTIONS
B E F O R E S T A R T I N G A N Y
OPERATION, MAKE SURE THAT THE
MAIN POWER SUPPLY LINE HAS
BEEN ISOLATED
PERFORM THE CONNEC TIONS
WITH CABLES FEATURING CABLES
FEATURING A SUITABLE CROSS-
SECTION
• The electric connections to the
control board must be made by
specialised staff according to
the diagram supplied.
• Make sure that the voltage and
the frequency stated on the
plate correspond with those of
the electric connection line.
• The use of adapters, multiple
sockets and/or extensions
is not allowed to power the
dehumidifier.
• It is the installer's responsibility
to assemble the unit as near as
possible to the power supply
isolator and the necessary to
protect the electric parts.
• Connect the unit to an efficient
earth socket, using the relevant
screw inserted in the unit itself.
• Use the cable gland (external
for horizontal versions, internal
for the recessed version) near
the panel to turn it on.
WATER PROBE
AIR PROBE
HUMIDISTAT
LOW PRESSURE
HIGH PRESSURE
POTENTIAL FREE CONTACT
FOR ALARM
FAN
COMPRESSOR
White
Common
min
average
max
Red
Blue
Black
FORCED AIR HEATER MODE ON/OFF
CONNECTION
TYPE I/O
MEANING I/O
STATE I/O
S01 - GND
Analog input
Water input temperature
Probe reading S01
S02 - GND
Analog input
Inlet air temperature
Probe reading S02
ID1 - GND
Digital input
High pressure switch
HP pressure switch status
0 = Closed
1 = Open (Warning)
ID2 - GND
Digital input
Low pressure switch
BP pressure switch status
0 = Closed
1 = Open (Warning)
ID3 - GND
Digital input
Humidistat consent
Dehumidifier status
0 = Off
1 = On
ID4 - GND
Digital input
Forced air heater mode On/Off
Thermoventilating state
0 = Off
1 = On
R01 - GND
Digital output
Compressor consent
Compressor status
0 = Off
1 = On
R02 - GND
Digital output
Alarm circuit (230 V) (*)
Circuit alarm status
0 = Absent
1 = current
R03 - GND
Digital output
Fan consent
Fan status
0 = Off
1 = On
R07 - GND
Digital output
Set-up (potential free contact)(**)
Circuit alarm status
0 = Absent
1 = current
(*) the installer is responsible for any external circuit
(**) The contact in question is normally open and closes in the event of an alarm on the unit: can be connected, for example, as a consensus for powering on
a LED alarm signal.