background image

EN

21.11 - 6755517_05

31

COMPRESSOR 

THERMOMAGNETIC

POWER

SUPPLY

ANL 100

[A]

ANL 150

[A]

MTC

220V-3-60Hz

19.0

23.0

MTCA

220V-3-60Hz

19.0

23.0

MTC

460V-3-60Hz

10.0

12.5

MTCA

460V-3-60Hz

10.0

12.5

PUMP

 THERMOMAGNETIC

POWER

SUPPLY

ANL 100 

HP/HA

[A]

ANL 150 

HP/HA

[A]

MTP

220V-3-60Hz

3.5

5.7

460V-3-60Hz

1.8

3.0

AUXILIARY

 

THERMOMAGNETIC

ANL 100 HP/HA

[A]

ANL 150 HP/HA

[A]

MTA

6.0

6.0

The units are completely wired at the factory and only require connection 

to the electric power supply mains, downstream from a unit switch, 

according to that envisioned by the Standards in force on this subject in the 

country of installation. 

It s also advised to check that:

-  The electrical mains features are suitable for the absorption values 

indicated in the electrical data table, also taking into consideration any 

other machines functioning at the same time.

-  The unit is only powered when installation has been completed 

(hydraulic and electric).

-  Respect the connection indications of the phase, and earth wires.

-  The power supply line must have a relevant protection mounted 

upstream against short circuits and dispersions to earth, which isolates 

the system with respect to other utilities.

-  The voltage must be within a tolerance of ±10% of the nominal power 

supply voltage of the machine (for unbalanced three-phase unit 

max 3% between the phases). Whenever these parameters are not 

respected, contact the electric energy public body. 

-  For electric connections, use the cables with double isolation according 

to the Standards in force on this subject in the different countries.

it is mandatory:

-  The use of an omnipolar magnet circuit breaker switch, in compliance 

with the current Standards (contact opening at least 0.12 in), with 

suitable cut-off power and differential protection on the basis of the 

electric data table shown below, installed as near as possible to the 

appliance.

-  To make an effective earth connection. The manufacturer cannot 

be considered responsible for any damage caused by the lack of or 

ineffective appliance earth connection.

-  For units with three-phase power supply, check the correct connection 

of the phases. 

ATTENTION

•  All the electrical operations must be carried out by personnel in 

possession of the necessary qualifications by law, suitably trained and 

informed on the risks related to these operations. 

•  The characteristics of the electrical lines and of the related 

components must be determined by  staff qualified to design 

electrical systems, in compliance with the international and national 

regulations of the place of installation of the unit and in compliance 

with the regulations in force at the moment of installation

•  For the installation requirements refer only to the wiring diagram 

supplied with the unit. - The wiring diagram along with the manuals 

must be kept in good condition and always available for any future 

servicing on the unit.

•  It is mandatory to verify that the machine is watertight before making 

the electrical connections and it must only be powered up after the 

hydraulic and electrical works have been completed.

•  If the supply cord is damaged, it must be replaced by the manufacturer 

or its service agent or a similarly qualified person in order to avoid a 

hazard

ELECTRICAL DATA

The cable section shown in the table are recommended for maximum 

lengths of 50m. For longer lengths or different cable laying,

it is up to the PLANNER to calculate the appropriate line switch, the power 

supply line as well as the connection to the earth wire and connection 

cables depending on:

-  The length

-  The type of cable

-  The absorption of the unit and the physical location, and the ambient 

temperature.

ELECTRICAL CONNECTIONS

23.  ELECTRICAL CONNECTIONS

24.  ELECTRICAL DATA

24.1.  COMPRESSOR THERMOMAGNETIC

24.2.  PUMP THERMOMAGNETIC

24.3.  AUXILIARY THERMOMAGNETIC

ELECTRICAL 

DATA

MODELS POWER 

SUPPLY

M.U.

ANL100

ANL150

Peak current 

(LRA)

H

220V 3 ~ 60Hz

A

168.4

193.2

H

460V 3 ~ 60Hz

A

82.4

95.3

HP-HA

220V 3 ~ 60Hz

A

171.4

198.8

HP-HA

460V 3 ~ 60Hz

A

83.9

98.1

MCA

H

220V 3 ~ 60Hz

A

47.4

55.7

H

460V 3 ~ 60Hz

A

24.3

29.9

HP-HA

220V 3 ~ 60Hz

A

50.4

61.3

HP-HA

460V 3 ~ 60Hz

A

25.8

32.7

MOP

H

220V 3 ~ 60Hz

A

60.0

75.0

H

460V 3 ~ 60Hz

A

30.0

40.0

HP-HA

220V 3 ~ 60Hz

A

60.0

80.0

HP-HA

460V 3 ~ 60Hz

A

30.0

40.0

Summary of Contents for ANL

Page 1: ...and Maintenance Manual TRANSLATION FROM ORIGINAL 21 11 6755517_05 EN DHW PRODUCTION UP TO 122 F EXTERNAL AIR TEMPERATURE UP TO 14 F AVAILABLE VERSION WITH BUILT IN HYDRONIC KIT ANL 60Hz Technical and...

Page 2: ......

Page 3: ...st grade materials and with cutting edge technology The quality level is being constantly monitored so AERMEC products are synonymous with Safety Quality and Reliability The data may undergo modificat...

Page 4: ......

Page 5: ...BRATION 19 14 SOUND DATA 20 15 GENERAL WARNINGS 21 16 RECEPTION 23 16 1 LIFTING AND HANDLING 23 17 STORAGE 24 18 HYDRAULIC CONNECTIONS 25 19 HYDRAULIC CIRCUITS OF PRINCIPLE 26 19 1 HYDRAULIC CIRCUIT F...

Page 6: ...utdoor condensed in the air with R410A Series ANL have been designed and manufactured to satisfy heating and cooling needs and the production of domestic hot water DHW in medium to small commercial or...

Page 7: ...Model H heat pump 8 VERSION standard P with pump A with storage tank and pump 9 HEAT RECOVERY without heat recovery units 10 COILS in aluminium 11 FIELD OF USE standard 1 12 EVAPORATOR standard PED n...

Page 8: ...transducer HPS High pressure switch LPT Low pressure transducer VIC Cycle reversing valve CN Finned coil CV One way valve F Dehydrator filter AL Liquid storage tank TEV Thermostatic valve BHE Plate e...

Page 9: ...ers and mechanically by anti intrusion metal grids according to the IEC EN 60335 2 40 Standard 5 3 HYDRAULIC CIRCUIT STANDARD COMPONENTS WATER FILTER Equipped with steel filtering mesh prevents the he...

Page 10: ...g times of the compressor in systems with low water content Intelligent defrosting for pressure reduction allows to determine when the coil is effectively defrosted avoiding useless defrosting Set poi...

Page 11: ...NET The device allows the control the management and the remote monitoring of a Chiller with a PC smartphone or tablet using Cloud connection AERNET works as Master while every unit connected is confi...

Page 12: ...k The combined effects of the salt loaded mist and industrial emissions accelerate corrosion Within the manufacturing plants corrosive gas may result from the processing of chemicals or by the typical...

Page 13: ...3 HP HA 220V 3 60Hz A 34 45 42 86 HP HA 460V 3 60Hz A 18 76 22 93 Peak current LRA H 220V 3 60Hz A 168 4 193 2 H 460V 3 60Hz A 82 4 95 3 HP HA 220V 3 60Hz A 171 4 198 8 HP HA 460V 3 60Hz A 83 9 98 1 M...

Page 14: ...fm 8 240 7 946 Input current A 2 2 Input power kW 0 6 0 6 SOUND DATA Sound power dB A 76 0 77 0 Sound pressure 10m 33ft dB A 44 0 45 0 DIMENSION Height in 53 53 Width in 30 30 Depth in 69 69 Weight H...

Page 15: ...15 5 10 14 5 0 32 5 10 50 15 20 68 25 30 86 35 40 104 45 46 C 114 8 F 46 C 114 8 F 50 122 C F 2 35 6 3 4 5 6 41 7 8 9 10 50 11 12 13 14 15 59 16 17 18 19 20 68 C F EXTERNAL AIR TEMPERATURE TEMPERATURE...

Page 16: ...Corrective factor of pressure drop PROPYLENE GLYCOL COOLING MODE CORRECTION FACTOR WITH PROPILENE GLYCOL COOLING MODE Freezing Point C 0 3 43 5 30 7 44 9 98 13 08 16 86 21 47 27 04 33 72 Percent PROP...

Page 17: ...5 80 7 25 8 70 10 15 11 60 0 1000 2000 3000 4000 5000 6000 7000 8000 l h gpm 0 4 9 13 18 22 26 31 35 1 2 1 ANL 100 2 ANL 150 0 2 4 6 8 10 12 14 16 18 20 0 0 0 58 0 29 0 87 1 16 1 45 1 74 2 03 2 32 2 6...

Page 18: ...40 50 Multiplicative coefficients 1 02 1 0 985 0 97 0 95 0 93 0 91 12 2 1 USEFUL HEADS The static pressures stated here are at net of the pressure drops of the heat exchang ers filter storage tank Th...

Page 19: ...tem also for glycoled water functioning Values are worked out by multiplying the reference value by the corrective coefficient 13 2 EXPANSION VESSEL CALIBRATION Standard pre load pressure value of exp...

Page 20: ...tor Q 2 at 10mt 33ft distance from external surface of unit in compliance with ISO 3744 regulations KEY Water input temperature 12 C 53 6 F Temperature of produced water 7 C 44 6 F External air tempe...

Page 21: ...check for leaks and make any necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate v...

Page 22: ...ections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate precautions to prevent their...

Page 23: ...asporto e movimentazione accluse al presente manuale Controllare che gli accessori necessari all installazione in loco siano stati consegnati e siano funzionanti Se l unit viene fornita precaricata co...

Page 24: ...istance Check that the contact surfaces of the anti vibration supports are levelled to the base If necessary use spacers or level the base but in any case make sure that the anti vibration supports re...

Page 25: ...near the suction of the pump High concentration of glycol could stuck the pump Do not use the pump to mix water and glycol HYDRAULIC CONNECTIONS The units may be available with or without integrated...

Page 26: ...3 70 300 ppm Chloride ions Cl 50 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressur...

Page 27: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressure switch 3 Water temperature pr...

Page 28: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Water temperature probe 3 Differential pressure swi...

Page 29: ...AVITY A B C D KIT VT Gy Gx ANL100H 650 381 604 32 2 33 3 17 0 17 5 15 P 690 381 640 31 2 32 2 18 0 18 6 15 A 800 381 640 30 1 30 9 19 2 19 8 15 ANL150H 710 382 630 31 4 32 6 17 7 18 3 15 P 756 382 671...

Page 30: ...EN 21 11 6755517_05 30 22 MINIMUM TECHNICAL SPACES A1 C1 B2 C2 B1 ANL 100 150 A1 in 118 2 118 2 B1 in 31 5 31 5 B2 in 43 3 43 3 C1 in 31 5 31 5 C2 in 31 5 31 5...

Page 31: ...ance earth connection For units with three phase power supply check the correct connection of the phases ATTENTION All the electrical operations must be carried out by personnel in possession of the n...

Page 32: ...rator pressure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel mus...

Page 33: ...tions to prevent their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position P...

Page 34: ...ust be replaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropr...

Page 35: ...tor to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn of...

Page 36: ...cular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simulta...

Page 37: ...proper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMM...

Page 38: ...lth from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased P...

Page 39: ......

Page 40: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...

Reviews: