The unit must be handled by qualified personnel. Carefully follow the 

lifting instructions on the labels placed on the unit. 

The unit must be lifted with extreme care to prevent knocks to the frame, 

panels, electrical panel, etc..

NOTE: Plastic elements can be used to protect the units against damage 

during transport. The machine is also wrapped in packaging. We recom-

mend keeping this protection during all transport and lifting operations 

and not remove the plastic elements until commissioning.

If the unit has anti-vibration supports, they must be installed on the unit 

before final positioning.

Inspection upon receipt

Perform the following check upon receipt of the product.

-   Check that the exterior has not been damaged in any way.

-   Check that the lifting and transport devices are appropriate to the 

type of equipment and compliant with the transport and handling 

instructions attached to this manual.

-   Check that the accessories required for on-site installation have been 

delivered and are operational.

-   If the unit is provided pre-loaded with refrigerant, make sure there have 

been no leaks.

-   Check that the equipment supplied corresponds to the order and 

delivery note

Product identification

The Aermec products can be identified by the 

packaging label

 bearing 

the identification data of the product and by the 

technical plate

 bearing 

the performance and technical data of your unit.

If the product is damaged, send a registered letter with the details of 

the problem to the shipping company within 48 working hours from 

delivery.

LIFTING

 

Before lifting the unit, place protections between the belts (or ropes and 

chains) and the framework to prevent damage to the structure.

 

CAUTION: ALWAYS USE ALL THE UNIT LIFTING POINTS PROVIDED

•   Follow all safety regulations and standards

•   Wear safety glasses, work gloves and safety shoes

•  Pay the utmost attention to heavy and bulky equipment during lifting 

and handling, and when placing it on the ground.

•   All panels must be tightly fixed before moving the unit

•   Before lifting, check the specific weight on the technical plate.

•   Use all, and only, the lifting points indicated;

•   Use ropes in compliance with Standards and of equal length;

•   Use a spacer in accordance with the sling (not included) see drawing

•   Handle the unit with care and without sudden movements

•  Do not stand under the unit during lifting

Attention: the units cannot be stacked

16.  RECEPTION

Technical plate

DISEGNO SPECIFICO DEL MODELLO-

SOLLEVAMENTO UNITÀ CON CINGHIE, 

CORDE O FUNI

RICEVIMENTO

TRASPORTO

 

E

 

MOVIMENTAZIONE

La movimentazione dell’unità deve essere eseguita da personale 

qualificato. Seguire scrupolosamente le istruzioni di sollevamento indicate 

con delle etichette poste sull’unità. 

Le operazioni di sollevamento dell’unità devono essere eseguite con 

estrema attenzione per evitare urti su telaio, pannelli, quadro elettrico, 

ecc.

NOTA: Le unità possono essere protette dai danni durante il trasporto 

tramite elementi di plastica. La macchina è anche avvolta in un 

imballo. Si raccomanda di mantenere questa protezione durante tutte 

le operazioni di trasporto e di sollevamento e di non rimuovere gli 

elementi di plastica fino alla messa in funzione.

Se l’unità prevede i supporti antivibranti, essi devono essere installati 

prima del posizionamento finale.

Controlli al ricevimento

Al ricevimento del prodotto, effettuare i seguenti controlli.

-   Controllare che l’esterno non sia stato danneggiato in alcun modo.

-   Controllare che i dispositivi di sollevamento e trasporto siano adeguati 

al tipo di apparecchiatura e siano conformi alle specifiche imposte nelle 

istruzioni di trasporto e movimentazione accluse al presente manuale.

-   Controllare che gli accessori necessari all’installazione in loco siano stati 

consegnati e siano funzionanti.

-   Se l’unità viene fornita precaricata con il refrigerante, verificare che non 

vi siano state delle perdite.

-   Controllare che l’apparecchiatura fornita corrisponda all’ordine e alla 

bolla di consegna

Identificazione del prodotto

I prodotti Aermec sono identificabili dalla 

etichetta imballo

 che riporta i 

dati identifictivi del prodotto, e dalla 

targhetta tecnica

 che riporta i dati 

tecnici prestazionali e identificativi dell’unità in vostro possesso.

Se il prodotto è danneggiato, occorre inviare una lettera raccomandata 

con i dettagli del problema alla società di spedizione entro 48 ore 

lavorative dalla consegna.

SOLLEVAMENTO

 

Le unità vengono fornite su di un pallet, per il sollevamento usare 

cinghie

adatte e affinché la struttura non venga danneggiata frapporre delle

protezioni tra le cinghie (o funi, catene) e la carpenteria.

Qualora si volesse sollevare con il muletto si raccomanda di aprire le 

forche

il più possibile per rendere sicura la movimentazione

• Seguire tutti i regolamenti e le normative di sicurezza

• Indossare occhiali protettivi e guanti da lavoro

• Fare molta attenzione alle attrezzature pesanti e voluminose durante le

operazioni di sollevamento e di movimentazione, e durante l’appoggio

a terra.

• Tutti i pannelli devono essere saldamente fissati prima di movimentare

l’unità

• Prima del sollevamento, verificare il peso specifico nella targhetta

tecnica.

• Utilizzare tutti, e solo, i punti di sollevamento indicati;

• Utilizzare funi a norma e di pari lunghezza

• Movimentare l’unità con cautela e senza movimenti bruschi

• Non sostare sotto l’unità durante il sollevamento

• È d’obbligo tenere sempre la macchina in posizione verticale

Attenzione: le unità non si possono accatastare

Targhetta tecnica

Etichetta Imballo

16.1.  LIFTING AND HANDLING

ATTENTION

The unit comes fixed on a pallet. 

Use forklifts for handling 

Before proceeding with the installation of the equipment agree the 

location with the client, taking into account the following points:

• 

The base must be able to support the weight of the unit.

• 

The safe distances between the unit and other equipment or 

structures must be strictly respected to ensure the intake and outlet 

air is free to circulate.

• 

The equipment must be installed by a competent and qualified 

technician, in compliance with the applicable national legislation 

of the country of destination, respecting the required minimum 

maintenance access spaces.

Before lifting the unit verify the lifting capability of the equipment being 

used, taking into account the information provided with the packaging. 

• 

To move units ANL use forklifts or similar in the most 

appropriate manner taking into account the weight distribution 

of the unit.

Position the unit in the place indicated by the client, inserting between 

the unit's base and the base support a rubber pad (minimum 10 mm 

thick) or feet anti-vibration mounts (ACCESSORY). For further information 

refer to the dimensional tables. 

Secure the unit and ensure it is level; check that sufficient access is 

provided for hydraulic and electrical connections.  

In the case of installation where gusts of wind may occur adequately 

secure the unit using appropriate ties.

 

Accessory

Height

Width

Length

CRATE_ANL

in

60.6

37.9

74.7

If accessory CRATE is included:

Summary of Contents for ANL

Page 1: ...and Maintenance Manual TRANSLATION FROM ORIGINAL 21 11 6755517_05 EN DHW PRODUCTION UP TO 122 F EXTERNAL AIR TEMPERATURE UP TO 14 F AVAILABLE VERSION WITH BUILT IN HYDRONIC KIT ANL 60Hz Technical and...

Page 2: ......

Page 3: ...st grade materials and with cutting edge technology The quality level is being constantly monitored so AERMEC products are synonymous with Safety Quality and Reliability The data may undergo modificat...

Page 4: ......

Page 5: ...BRATION 19 14 SOUND DATA 20 15 GENERAL WARNINGS 21 16 RECEPTION 23 16 1 LIFTING AND HANDLING 23 17 STORAGE 24 18 HYDRAULIC CONNECTIONS 25 19 HYDRAULIC CIRCUITS OF PRINCIPLE 26 19 1 HYDRAULIC CIRCUIT F...

Page 6: ...utdoor condensed in the air with R410A Series ANL have been designed and manufactured to satisfy heating and cooling needs and the production of domestic hot water DHW in medium to small commercial or...

Page 7: ...Model H heat pump 8 VERSION standard P with pump A with storage tank and pump 9 HEAT RECOVERY without heat recovery units 10 COILS in aluminium 11 FIELD OF USE standard 1 12 EVAPORATOR standard PED n...

Page 8: ...transducer HPS High pressure switch LPT Low pressure transducer VIC Cycle reversing valve CN Finned coil CV One way valve F Dehydrator filter AL Liquid storage tank TEV Thermostatic valve BHE Plate e...

Page 9: ...ers and mechanically by anti intrusion metal grids according to the IEC EN 60335 2 40 Standard 5 3 HYDRAULIC CIRCUIT STANDARD COMPONENTS WATER FILTER Equipped with steel filtering mesh prevents the he...

Page 10: ...g times of the compressor in systems with low water content Intelligent defrosting for pressure reduction allows to determine when the coil is effectively defrosted avoiding useless defrosting Set poi...

Page 11: ...NET The device allows the control the management and the remote monitoring of a Chiller with a PC smartphone or tablet using Cloud connection AERNET works as Master while every unit connected is confi...

Page 12: ...k The combined effects of the salt loaded mist and industrial emissions accelerate corrosion Within the manufacturing plants corrosive gas may result from the processing of chemicals or by the typical...

Page 13: ...3 HP HA 220V 3 60Hz A 34 45 42 86 HP HA 460V 3 60Hz A 18 76 22 93 Peak current LRA H 220V 3 60Hz A 168 4 193 2 H 460V 3 60Hz A 82 4 95 3 HP HA 220V 3 60Hz A 171 4 198 8 HP HA 460V 3 60Hz A 83 9 98 1 M...

Page 14: ...fm 8 240 7 946 Input current A 2 2 Input power kW 0 6 0 6 SOUND DATA Sound power dB A 76 0 77 0 Sound pressure 10m 33ft dB A 44 0 45 0 DIMENSION Height in 53 53 Width in 30 30 Depth in 69 69 Weight H...

Page 15: ...15 5 10 14 5 0 32 5 10 50 15 20 68 25 30 86 35 40 104 45 46 C 114 8 F 46 C 114 8 F 50 122 C F 2 35 6 3 4 5 6 41 7 8 9 10 50 11 12 13 14 15 59 16 17 18 19 20 68 C F EXTERNAL AIR TEMPERATURE TEMPERATURE...

Page 16: ...Corrective factor of pressure drop PROPYLENE GLYCOL COOLING MODE CORRECTION FACTOR WITH PROPILENE GLYCOL COOLING MODE Freezing Point C 0 3 43 5 30 7 44 9 98 13 08 16 86 21 47 27 04 33 72 Percent PROP...

Page 17: ...5 80 7 25 8 70 10 15 11 60 0 1000 2000 3000 4000 5000 6000 7000 8000 l h gpm 0 4 9 13 18 22 26 31 35 1 2 1 ANL 100 2 ANL 150 0 2 4 6 8 10 12 14 16 18 20 0 0 0 58 0 29 0 87 1 16 1 45 1 74 2 03 2 32 2 6...

Page 18: ...40 50 Multiplicative coefficients 1 02 1 0 985 0 97 0 95 0 93 0 91 12 2 1 USEFUL HEADS The static pressures stated here are at net of the pressure drops of the heat exchang ers filter storage tank Th...

Page 19: ...tem also for glycoled water functioning Values are worked out by multiplying the reference value by the corrective coefficient 13 2 EXPANSION VESSEL CALIBRATION Standard pre load pressure value of exp...

Page 20: ...tor Q 2 at 10mt 33ft distance from external surface of unit in compliance with ISO 3744 regulations KEY Water input temperature 12 C 53 6 F Temperature of produced water 7 C 44 6 F External air tempe...

Page 21: ...check for leaks and make any necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate v...

Page 22: ...ections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appropriate precautions to prevent their...

Page 23: ...asporto e movimentazione accluse al presente manuale Controllare che gli accessori necessari all installazione in loco siano stati consegnati e siano funzionanti Se l unit viene fornita precaricata co...

Page 24: ...istance Check that the contact surfaces of the anti vibration supports are levelled to the base If necessary use spacers or level the base but in any case make sure that the anti vibration supports re...

Page 25: ...near the suction of the pump High concentration of glycol could stuck the pump Do not use the pump to mix water and glycol HYDRAULIC CONNECTIONS The units may be available with or without integrated...

Page 26: ...3 70 300 ppm Chloride ions Cl 50 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressur...

Page 27: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Differential pressure switch 3 Water temperature pr...

Page 28: ...0 ppm Sulphate ions SO4 50 ppm Sulphide ion S none Ammonium ions NH4 none Silica SiO2 30ppm COMPONENTS PROVIDED AS STANDARD 1 Plate heat exchanger 2 Water temperature probe 3 Differential pressure swi...

Page 29: ...AVITY A B C D KIT VT Gy Gx ANL100H 650 381 604 32 2 33 3 17 0 17 5 15 P 690 381 640 31 2 32 2 18 0 18 6 15 A 800 381 640 30 1 30 9 19 2 19 8 15 ANL150H 710 382 630 31 4 32 6 17 7 18 3 15 P 756 382 671...

Page 30: ...EN 21 11 6755517_05 30 22 MINIMUM TECHNICAL SPACES A1 C1 B2 C2 B1 ANL 100 150 A1 in 118 2 118 2 B1 in 31 5 31 5 B2 in 43 3 43 3 C1 in 31 5 31 5 C2 in 31 5 31 5...

Page 31: ...ance earth connection For units with three phase power supply check the correct connection of the phases ATTENTION All the electrical operations must be carried out by personnel in possession of the n...

Page 32: ...rator pressure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel mus...

Page 33: ...tions to prevent their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position P...

Page 34: ...ust be replaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropr...

Page 35: ...tor to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn of...

Page 36: ...cular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simulta...

Page 37: ...proper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMM...

Page 38: ...lth from uncontrolled disposal of Waste Electrical and Electronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased P...

Page 39: ......

Page 40: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...

Reviews: