This cleaning is without fail regularly required! 

During construction site effort, after every effort or once a week!  

 
No other maintenance work is required for the air dryer. 
 

9.Trouble shooting 

 

Assign that dehumidifier a putative defect on, please, first check the following points. 
If this should provide no relief, please contact your technical consultant. 
 
1)The dehumidifier shows a bad or no drying capacity  
-  The humidity is lower than 40% r.h. or the temperature in that room is lower than  
   +3°C. The using of the dryer is uneconomical in the case of these conditions. It is  
   recommended to disconnect the dryer. 

Tipp

: Put the built-in hygrostat on an  

   attainable value (e.g. approx. 50%r.F.), with it the dryer punctually may switch off. 
-  The air filter is soiled.  The dryer does not receive air sufficiently. Clean the filter 

and/or install a new one. A soiled air filter can in the long run lead to 
disadvantages at the dryer. 

Tipp

: Control the filter regularly. 

 
2) 

The fan of the dehumdifier does not work

-  The unit is in defrost mode. In this case the compressor still runs and the fan does 

not run. The red neon in the operation panel lights up. After some minutes, the 
unit will start with regular working. 

 
3) 

The complete dryer is out of operation. Fan and compressor does not run

-  Is the dryer switched on? The On-/Off-switch must be in position `I´ and must light 

up. 

-  Is the unit supplied with voltage? The On/Off-switch must light up in Pos. `I´. 

Check the main cable, an additional cable, the socket and the main fuse.   

-  The humidity value adjusted at the hygrostat is achieved. The dryer will start again 

after exceeding the adjusted humidity.  

Only at units with optional extra „ThermoLogic“ 

 >>Thermostat switch off“<< 

 (= red neon in the operation panel): 
The ambient temperature in that room is lower than +3°C or higher than +32°C. 
The red neon lights up (see  5.3 / 5.4 / 5.5 „operation panel“). The unit will start 
again when the temperature in that room has achieved normal conditions between  
+3°C and +32°C. 

Only at AD 740 / AD 750

 >>water collecting bucket is full<< The red neon lights 

up (see  5.3 / 5.4 / 5.5 „operation panel“). Empty the water bucket and put it back 
into the unit. (see 5.7 „condensate outlet“) 

 
4) 

Strong icing up at the evaporator. 

-  Put the dryer into a room with min. +10°C room temperature and wait until 

complete ice is defrosted. Switch on the unit again (in that room with min. +10°C) 
and let work for approx 3 hours. If there is icing up again, please contact your 
dealer. Otherwise make sure that the units is only been used in rooms with more 
than +3°C. Also the storage of the dehumidifier at inadmissible temperature 
conditions can lead to damages / problems while immediate switch-on. 

 
 
 
 

Summary of Contents for AD 740

Page 1: ...Page 1 of 15 Instruction manual _____________________________________ Dehumidifier AD 740 750 770 790 _____________________________________ valid 02 2008...

Page 2: ...50 6 5 4 Operation panel AD 770 790 7 5 5 Description of operation panel 7 5 6 Hygrostat control 7 8 5 7 Condensate outlet AD 740 750 9 5 8 Condensate outlet AD 770 790 9 5 9 Condensate pump option 9...

Page 3: ...er to be able to send the device safe for guarantee repair In order to save space you open simply the adhesive tape with a knife and you fold the carton 2 Mode of functioning The AD air dryer is const...

Page 4: ...tion dryers are intended for the drying of air with atmospheric pressure Risk by accessory Hoses for condensate removal and air filters must be fit expertly and must not take the protective devices of...

Page 5: ...therwise it must be secured against rolling off That dehumidifier can be transported upright or laid flat The upright transportation is to be preferred if possible The appliance must be used exclusive...

Page 6: ...eturn into the compressor We recommend this procedure since it extends the service life of the compressor Put the plug into the socket Check whether the bucket is placed in the unit AD 730 740 standar...

Page 7: ...andard The unit has switched off because the humidity in thet room is ok has achieved the requested value 6 Hygrostat see 5 6 Hygrostat control 7 On Off Switch 8 Make sure a free space in front of air...

Page 8: ...umidity values of a minimum of 40 45 r h can be achieved with a condensation dryer An adsorption dryer is to be employed if lower values are required For this purpose ask your technical consultant Opt...

Page 9: ...ater tank at AD 770 790 optional extra does NOT disconnect the device in the case of full state During unattended using AD 770 790 with built in pump is advisable 5 9 Condensate pump optional Optional...

Page 10: ...ooms of aggressive atmospheres for example ammonia and wood acid In rooms with water which shows a pH value outside of 7 0 to 7 4 Remark In The case of lower pH value corrosion occurs at all metals an...

Page 11: ...NTION When performing any repair or maintenance the general safety rules and provisions must be adhered to In order to guarantee a troublefree function of the dryer the device should be cleaned regula...

Page 12: ...s out of operation Fan and compressor does not run Is the dryer switched on The On Off switch must be in position I and must light up Is the unit supplied with voltage The On Off switch must light up...

Page 13: ...se the dryer needs some time to remove that water and to achieve an acceptable humidity in that room ATTENTION The appliance must be repaired by trained and expert personnel only In the case of interv...

Page 14: ...Page 14 of 15 11 Circuit diagram...

Page 15: ...EN ISO 12100 Safety of Machinery EN 50081 1 92 Electromagnetic Compatibility EMC Basic Specification Emitted Interference EN 50082 1 97 Electromagnetic Compatibility EMC Basic Specification Emitted I...

Reviews: