Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2022 ]
9.22 Type 22: alarm indicating that the hours limit for the major maintenance has been
reached
• Conditions:
• The hours limit must be configured with a value greater than 0.
• Causes:
• The hours limit for the major maintenance has been reached.
The instructions in this manual for the 12 months maintenance should be followed.
Reset the hours for major maintenance after this operation, this will reset automatically the alarm and
give it again after the same period. Reset also minor maintenance hours.
• Effects:
Displayed on Touchpanel
Code
Text displayed
Level
M.11
MAJOR MAINTENANCE ALARM
1
TAC control board
ALARM OUTPUT
AL dPa OUTPUT
LED ALARM
Fans
/
/
ON
/
Auto reset: via dedicated reset