9.9. MAINTENANCE
Taking into account the slow circulation speed at the level of sensitive elements, the measurement of CO
2
is not affected by dust or water vapour. The
sensor does not require recalibration during its life cycle. It has two infra-red sources with different operating cycles, which enables it to be recalibrated
automatically.
0%
20%
40%
60%
80%
100%
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
1 100 ppm
700 ppm
Level CO
2
% ventilation airflow
Level CO
2
And in a more general way:
“Full or little” mode
(press start-up
between 10 and 15 s) :
SCO
2
= set value according to the cursor of
the CO
2
sensor = CO
2
(SCO
2
= 700 ppm (0-1) 900 ppm (2-4)...
1 700 ppm (14-15))
Proportional Mode:
(press start-up between 5 and 10 secs):
The average over the 10 mins should be
greater than 1,100 ppm to be at 100% for
the following 10 mins.
0%
20%
40%
60%
80%
100%
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
CO
2
> SCO
2
CO
2
< SCO
2
CO
2
< SCO
2
CO
2
>
SCO
2
10 % with jumper on Main module
0 % with no jumper on Main module
% ventilation airflow
VMX S-PRE Det
ect
or