24 / 34
TF5814GB_E
Aereco S.A.
BEHAVIOUR OF THE LEDS
red LED
(fast)
(sequence)
orange LED
(flashes)
green LED
(flashes)
INTERPRETATION
level of CO
2
≤ threshold
level of CO
2
> threshold
measures every
10 s
not configured
modification of threshold without
memorisation of main module
breakdown
9.8. OPERATING MODES
The "full or little" mode
(if the jumper is present on the main module) or the "full or none" mode (if the jumper is pulled out on the main module) is
obtained by pressing the "memory" button on the main module for between 10 and 15 seconds.
1 flash
}
9.7. INTERPRETATION OF SENSOR SIGNALS
0%
20%
40%
60%
80%
100%
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
10 mn
CO
2
level>
700 ppm
CO
2
level<CO
2
threshold (700 ppm)
CO
2
level<
threshold CO
2
(700 ppm)
pic CO
2
>
700 ppm
% ventilation airflow
·"full or little" operation according to CO
2
threshold
·processing information by a single module
·modulation of airflow by controlling a
motorised valve (multizone) or by acting on
the fan speed (unizone).
0
20
40
60
80
100
120
0
20
40
60
80
100
120
level of CO
2
<
700 ppm
level of CO
2
> 1 100 ppm
% ventilation air
flow
Time
The "chrono-proportional" mode
is obtai-
ned by pressing the "memory" button on the
main module for between 5 and 10 seconds.
·Level of CO
2
< 700 ppm => minimum
ventilation (0% with no jumper on main
module, 10% with jumper on main module)
·Level of CO
2
between [700 ppm ; 1,100
ppm => ventilation % included in the
interval [minimum ventilation ; 100%]
·Level of CO
2
> 1,100 ppm => maximum
ventilation at 100%
VMX S-PRE Det
ect
or
Operation in the "full or little" mode, for example with a CO2 threshold regulation at 700 ppm
Just as for the "full or little" mode, the flow diminishes every 10 mins a maximum of 10% (in order to ventilate the premises sufficiently after all the occu-
pants have left). But where necessary it can increase by n x 10% in the following cycle, according to requirements.