Incorrect start-up can lead to damage of the fan.
·
The start-up can be carried out by the AERECO service with prior agreement.
Before applying voltage you have to check that:
·
installation materials, possible waste and tools have been removed from inside the fan,
·
the fan impeller turns easily without rubbing or jamming,
·
the fan is securely mounted,
·
the direction of air flow through the fan corresponds to the installation design,
·
electrical connections have been made correctly,
·
the wire fixing is secure and made using the correct materials,
·
electric wires connected to the fan are properly fastened, without risk of breaking or
fraying due to vibrations,
·
the protective (earthing) conductor and possibly also the equipotential bonding con-
ductor are correctly connected to the fan and to the grounding point (busbar)
·
safety devices have been installed and they comply with the general safety regulations
and the requirements of section 4 of the documentation,
·
the voltage supply corresponds to the rated values within the tolerances: max. voltage
+ 6%, - 10% according to EN 60038:2012 (unless other tolerances are indicated on
the nameplate of the fan).
After applying voltage you have to check that:
·
the fan works without any abnormal sounds.
5. START-UP
ATTENTION!!!
-
Start-up must be documented
by an entry in the warranty
card.
-
Causing damage to the fan
as a result of installation error
or the use of inappropriate
electrical protection is
grounds for invalidating the
guarantee.