TECHNICAL AND MAINTENANCE DOCUMENTATION 

HAT

www.aereco.com

 

·

Incorrect start-up can lead to damage of the fan.

 

·

The start-up can be carried out by the AERECO service with prior agreement.

Before applying voltage you have to check that:

 

·

installation materials, possible waste and tools have been removed from inside the fan,

 

·

the fan impeller turns easily without rubbing or jamming,

 

·

the fan is securely mounted,

 

·

the direction of air flow through the fan corresponds to the installation design,

 

·

electrical connections have been made correctly,

 

·

the wire fixing is secure and made using the correct materials,

 

·

electric wires connected to the fan are properly fastened, without risk of breaking or 

fraying due to vibrations,

 

·

the protective (earthing) conductor and possibly also the equipotential bonding con-

ductor are correctly connected to the fan and to the grounding point (busbar)

 

·

safety devices have been installed and they comply with the general safety regulations 

and the requirements of section 4 of the documentation,

 

·

the voltage supply corresponds to the rated values within the tolerances: max. voltage 

+ 6%, - 10% according to EN 60038:2012 (unless other tolerances are indicated on 

the nameplate of the fan).

After applying voltage you have to check that:

 

·

the fan works without any abnormal sounds.

5.  START-UP

ATTENTION!!! 

 -

Start-up must be documented 

by an entry in the warranty 

card.

 -

Causing damage to the fan 

as a result of installation error 

or the use of inappropriate 

electrical protection is 

grounds for invalidating the 

guarantee.

Summary of Contents for HAT-100-B

Page 1: ...HAT FANS FOR MEDIUM PRESSURE AERECO VENTILATION SYSTEMS TECHNICAL AND MAINTENANCE DOCUMENTATION HAT HD ...

Page 2: ......

Page 3: ...TABLE OF CONTENTS 1 General information 2 Fan installation 3 Fan models 4 Electrical specifications and connections 5 Start up 6 Use 7 Transport and storage ...

Page 4: ...ers reduces the fan s energy consumption In addition the HD PD MD automated system can be equipped with the day night function TS which is activated by connecting an external control signal from the ACC DN2 automated system This allows for the fan speed to be lowered during the night hours In addition to the savings in electricity consumption the automated control of fan performance enables better...

Page 5: ...er the power supply has been disconnected The installer is responsible for the compliance with all applicable safety regulations for electrical connections and protection against accidental contact Clearance must be provided around the fan the automated system and the measuring stub to allow for future maintenance The automated control system must be located in an easily accessible place During in...

Page 6: ...z 1 7 170 HAT 160 C 230 VAC 50Hz 1 7 170 HAT 200 C 230 VAC 50Hz 1 7 170 HAT 250 C 230 VAC 50Hz 1 7 170 HAT 250 D 230 VAC 50Hz 1 75 170 Connecting the HD automated system The power supply for the fan with a HD automated system should be connected as shown in the drawing BN BU YG Y G Y G B U B U B U B U B N B N B N B N Y G YG Y G Y G Y G Y G B N BN BN BN BN BN B U BU BU BU BU BU BU BU B N B N B N B ...

Page 7: ... To open the housing of HD automated unit use a screwdriver Do not use a power screw driver because of the danger of damaging the screws and loss of tightness of the casing 1 PG11 cable gland enables connection of 1x230 V power supply The power wires should be connected to the corresponding terminal blocks 2 in accordance with point 4 of the technical and propulsion documentation The potentiometer...

Page 8: ...thout risk of breaking or fraying due to vibrations the protective earthing conductor and possibly also the equipotential bonding con ductor are correctly connected to the fan and to the grounding point busbar safety devices have been installed and they comply with the general safety regulations and the requirements of section 4 of the documentation the voltage supply corresponds to the rated valu...

Page 9: ... the weights balancing the impeller are in place and the impeller is not deformed After cleaning make sure that the fan works without any abnormal noises Check that the impeller is not jammed and that the motor protection is not loosened HAT fans are factory packed in appropriate cardboard boxes It is recommended to leave the fans in their original packaging during the whole transport to the place...

Page 10: ...NOTES ...

Page 11: ...B 125 1B 160 1B 160 1C 200 1C 250 1C 250 1D 100 3B 125 3B 160 3B 160 3C 200 3C 250 3C 250 3D 3 We declare the conformity of the product with the following directives standards and documents Directive 2014 30 EU Directive 2014 35 EU Directive 2006 42 EC European Commission Regulation 1253 2014 Łomna Las 01 April 2020 Marcin Gasiński Technical and Energy Requirements Specialist ...

Page 12: ...AERECO S A 62 rue de Lamirault Collégien 77615 MARNE LA VALLEE CEDEX 3 FRANCE www aereco com FLY728_v1_NOT_INST_HAT HD ...

Reviews: