Aereco S.A.
3.
INSTALLATION
3.1. LOCATION OF THE INSTALLATION
The unit must be installed into the heated space, in parts of the dwelling relatively
insensitive to noise, not in the unheated space (attic, etc.). Upper and lower temperature
limits for the main unit are 5°C and 50°C
Ductwork should be installed in the heated space. If not, they must be insulated with
50 mm minimum of glass wool (or equivalent). The non compliance with these conditions
leads to the degradation of the heat recovery performance.
Features and uses
DXR Unit and DX Hub
CO
2
sensor
Exhaust compensation valve
Max. altitude of the product installation
2000 m
2000 m
2000 m
Temperature range of the installation place
5°C – 50°C
5°C – 40°C
5°C – 40°C
Humidity range of the installation place
5 % - 95 %
Max. 80 % at 31°C, linear
decrease up to 50 % at 40°C.
5 % - 95 %
3.2. DXR UNIT AND DX HUB
The caps on the DXR Unit and the DX Hub must stay during the entire duration of the
work, in order to keep dust and pollution from getting into the boxes.
3.2.1. LOCATION
Before the installation, be sure of the solidity of the ceiling where you plan to install DXR
Unit and DX Hub.
·Weight of DXR Unit = 46 kg
·Weight of DX Hub 5 = 11 kg
·Weight of DX Hub 6 = 18 kg
The DXR Unit must be attached so that the gap between the ceiling and the top of the unit is
at least 10 mm, and positioned exactly horizontally (max 1° tolerance).
The non compliance to this requirement may lead to serious problems of condensate
evacuation.
Positioning of the DXR Unit
D > 10 mm
ceiling
ceiling
When mounting the DX Hub, the top must be closed, otherwise the Hub may warp.