CONTROL PANEL OPERATING PROCEDURES
3-5
NOTE
The Outdoor Temp display item shown with an asterisk in Table 3-2 will
not be displayed unless the Outdoor Sensor function has been enabled
in the Configuration Menu (Table 3-4).
Table 3-2. Operating Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Status Message
Active Setpoint
40°F
240°F
Aux Temp
30°F
245°F
Outdoor Temp*
-70°F
130°F
Valve Position In
0%
Max Valve
Position
Flame Strength
0%
100%
Run Cycles
0
999,999
Run Hours
0
999,999
Fault Log
0
19
0
Table 3-3. Setup Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Passsword
0
9999
0
Language
English
English
Time
12:00 am
11:59 pm
Date
01/01/00
12/31/99
Unit of Temp
Fahrenheit
Celsius
Fahrenheit
Comm Address
0
127
0
Baud Rate
2400
4800
9600
19.2K
9600
Software
Ver 0.00
Ver 9.99
3.6. CONFIGURATION MENU
The Configuration Menu shown in Table 3-4
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.
NOTE:
The Configuration Menu settings shown in Table
3-4 are factory set in accordance with the
requirements specified for each individual order.
Therefore, under normal operating conditions,
no changes will be required.